Instruction manual BFC
43
is
BFC 80 t/m 120 - CO
2
adjustment (partial load)
Note
Turning to the left (anticlockwise) means more less (lower CO
2
level) and
turning to the right (clockwise) means more gas (higher CO
2
level).
Note
After conversion, you must check that the gas control valve is gastight.
23. Remove the CO
2
measurement probe from the measurement nipple of the
flue gas outlet pipe.
24. Put the cap back on the measurement nipple of the flue gas outlet pipe.
25. Shut off the gas supply.
26. Replace the covers.
3.11.4
Switching pressure measurement
To measure the switching pressure, proceed as follows:
1. Isolate (10.3 "Isolating the water heater from the mains") the appliance from
the power supply.
2. Carefully remove the covers from the appliance.
3. The electrical section is now visible.
4. Remove the black caps from the measurement point of the pressure switch.
5. Connect the + of the pressure gauge to the H of the measurement point of
the pressure switch.
6. Connect the - of the pressure gauge to the L of the measurement point of
the pressure switch.
7. Zero the pressure gauge.
8. Start (9 "Starting the water heater") the appliance.
9. The appliance will now run the heating cycle (9.3 "The appliance's heating
cycle").
IMD-1097b R0
Summary of Contents for 120 through 250 Series
Page 4: ...E2 ...
Page 6: ...4 Instruction manual BFC gis ...
Page 10: ...Contents 8 Instruction manual BFC ...
Page 31: ...Instruction manual BFC 29 is Installation types IMD 0789 R0 C43 C13 C53 B23 C33 ...
Page 48: ...Conversion to a different gas category 46 Instruction manual BFC 4 is ...
Page 58: ...Status of the water heater 56 Instruction manual BFC 8 gis ...
Page 62: ...Shutting down 60 Instruction manual BFC 10 gis ...
Page 74: ...Service program 72 Instruction manual BFC 12 is ...
Page 88: ...Service interval 86 Instruction manual BFC 14 is ...
Page 97: ...Instruction manual BFC 95 is ...
Page 102: ...Instruction manual BFC 100 ...