background image

32 

storage tank temperature five degrees lower than the water 

heater’s temperature setting. Using the plug valve, adjust 

the flow in the recirculating line to five gallons per minute.

SPACE HEATING AND POTABLE WATER SYSTEM

Figure 38. Water Heater with Side Taps for Space Heating

This appliance has been design certified as complying with 

CSA 

Standards

 for water heaters and is suitable for combination water 

(potable) heating and space heating but not space heating only 

applications.

Note: 

When there will be no domestic hot water demand for 

an extended period of time, the temperature set point 

should be set at 32°C (90°F) to prevent “Stacking” and 

T&P discharge.

This heater is equipped with additional side taps for use in space 

heating  applications.  See 

Features and Components 

(page  8)  for 

locations. If this water heater is to be used to supply both space 

heating and potable (drinking) water, the instructions listed below 

must be followed:

Toxic Chemical Hazard

WARNING

• 

Do not connect to non-potable water system.

Consult a Qualified Installer or Service Agency. Follow manufacturer’s 

instructions for installation of valves. Before changing the factory 

setting on the control system, see

Temperature Regulation 

(page 38).

Note: 

Water piping and vent piping occupy the space above the 

water heater. Plan the water piping to ensure it does not 

cause interference with the vent piping. See 

Planning the Vent 

System 

(page 14).

If this water heater is to be used to supply both space heating and 

potable water, the instructions listed below must be followed:

• 

Be sure to follow the manual(s) shipped with the air handler or 

other type heating system.

• 

This water heater is not to be used as a replacement for an 

existing boiler installation.

• 

Do not use with piping that has been treated with chromates, 

boiler seal or other chemicals and do not add any chemicals 

to the water heater piping.

• 

When  the  system  requires  water  for  space  heating  at 

temperatures  higher  than  required  for  domestic  water 

purposes, a mixing valve must be installed. See 

Figure 35 

(page 

29).

• 

If  the  space  heating  system  requires  water  temperatures  in 

excess  of  120°F,  install  a  Thermostatic  Mixing  Valve  in  the 

domestic  (potable)  hot  water  supply  at  each  point-of-use  to 

limit the risk of scald injury. See 

Figure 35 

(page 29).

• 

Pumps,  valves,  piping  and  fittings  must  be  compatible  with 

potable water.

• 

A properly installed flow control valve is required to prevent 

thermosiphoning.  Thermosiphoning  is  the  result  of  a 

continuous flow of water through the air handler circuit during 

the off cycle. Weeping (blow off) of the temperature-pressure 

relief valve (T&P) or higher than normal water temperatures 

are the first signs of thermosiphoning.

• 

The  hot-water  line  from  the  water  heater  should  be  vertical 

past any mixing valve or supply line to the heating system to 

remove air bubbles from the system.

• 

Do not connect the water heater to any system or components 

previously  used  with  non-potable  water  heating  appliances 

when used to supply potable water.

COMBO HEATING INLET AND OUTLET SIDE TAPS

Your water heater is equipped with Combo Heating capabilities 

with the two side plumbing taps 

PLUGGED

 (items 24 and item 29 

in

 Features and Components 

(page  8)).  See  also 

Figure 38 

(page 

32). If the heater is to be operated using the side taps for combo 

heating, these plugs must be removed.

COMBO HEATING

This  section  serves  as  a  guide  for  the  installation  and  use  of 

“Combo” heating systems utilizing a domestic water heater that 

has been specifically approved for such use. It is written for those 

knowledgeable in the required trades and professionals involved 

in the design and installation of Combo Heating Systems.

It is the responsibility of the installer/designer to follow all applicable 

codes to ensure the effectiveness and safety of the installation.

SYSTEM REQUIREMENTS

The  following  requirements  must  be  met  for  the  installation  of 

Combo Heating Systems:

1. 

All components used for the distribution of water in the heating 

loop  must  be  suitable  for  potable  water. These  include  all 

Summary of Contents for 100 Series

Page 1: ...ch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier c...

Page 2: ...Installation 31 Space Heating and Potable Water System 32 Combo Heating Inlet And Outlet Side Taps 32 Combo Heating 32 System Requirements 32 Installation 33 Electrical Supply 33 Dedicated Power Wiri...

Page 3: ...hazardous situation which if not avoided could result in property damage All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message an...

Page 4: ...flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN Explosion Hazard Flammable hydrogen gases may be present Keep all ignition sources away from faucet when turning o...

Page 5: ...sources away from faucets after extended periods of non use Maintain required clearances to combustibles Do not expose water heater controls to excessive gas pressure Fire Hazard Do not install water...

Page 6: ...e essential to the proper operation of the water heater and your safety Detailed installation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference...

Page 7: ...pply Pressure Maximum Supply Pressure Electrical Characteristics Gas Type In W C kPA In W C kPA In W C kPA Volts Hz Amperes Natural 0 0 3 5 1 10 14 3 49 120 60 10 The manifold pressure is the factory...

Page 8: ...l 25 Control Panel 26 Outlet Air Pressure Switch OAPS 27 Blower 28 Gas Control Valve 29 Combo Heating System Return Inlet Optional 30 Temperature Sensor 31 Burner Insulation Shield 32 Burner Refractor...

Page 9: ...9 34 35 33 31 32 27 37 38 41 42 44 43 Figure 3 Blower and Burner Components 44 42 39 35 36 40 34 41 43 Figure 4 Blower and Intake Air Components...

Page 10: ...s the unit from igniting most likely the exhaust is blocked by some means Check to see if the condensate is allowed to flow freely from the condensate trap and for obstructions in the exhaust venting...

Page 11: ...nstall without adequate drainage Property Damage Hazard CAUTION Carefully choose a location for the new water heater The placement is a very important consideration for the safety of the occupants in...

Page 12: ...and liquids in the vicinity of this or any other appliance Avoid all ignition sources if you smell gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate M...

Page 13: ...amage Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Install water heater in accordance with the instruction manual and B149 1 To avoid injury...

Page 14: ...shows various end termination details and clearances for PV installations Note The information provided in Figure 2 page 8 is intended as a guideline for good vent installation practices only This wat...

Page 15: ...to ULC S636 Check local codes to determine which materials are allowed in your area and only use approved material All venting material and components must be joined with the approved primer cleaner a...

Page 16: ...t systems are designed to use specific adaptors to connect the water heater venting These adaptors are available through your venting supplier The PVC vent termination elbow supplied with this heater...

Page 17: ...ntly push the screen into the termination elbow until it sits against the inside shoulder The debris vent screens are self securing Note In the concentric vent application the vent screen is to be ins...

Page 18: ...Air Condensate Tee Installation DIRECT VENT AIR INTAKE MOISTURE PROTECTION The air intake piping in a direct vent system will normally not have any moisture accumulation in it However in certain case...

Page 19: ...15 ft 4 6 m Clearance in accordance with local installation codes and the require ments of the gas supplier I Clearance to service regulator vent outlet 3 ft 91 cm Clearance in accordance with local i...

Page 20: ...te the same side of roof 5 The centerline of the air intake termination and the centerline of the exhaust vent termination must not be closer than 200 mm 8 6 The air intake terminal and the exhaust ve...

Page 21: ...centers can be found in Table 10 2 Slide both the intake and exhaust pipes through the holes Solvent cement both pipes to the base of the vent termination kit follow the solvent cementing procedures...

Page 22: ...tical roof installation Ensure the combustion air intake location is above the anticipated snow level Table 11 Concentric Vent Termination Kits Vent Dia P N 2 100153586 3 100111100 Combustion Air Abov...

Page 23: ...ted and installed in accordance with local building code and CSA B149 1 Natural Gas and Propane Installation Code 1 Once the proper location has been determined cut 2 holes in the wall large enough to...

Page 24: ...t Number IPEX Part Num ber Description Pipe Outside Diameter Hole Spacing Center to Center 100086241 196984 2 Flush Mount Vent Kitt 2 375 5 63 100187887 196985 3 Flush Mount Vent Kit 3 5 7 63 Each Kit...

Page 25: ...e Equivalent Vent Length Water Heater Model Heater Input Btu Hr Vent Size Inside Diam Pressure Switch Settings in w c Low Profile Equiv Vent Length Intake Exhaust Max Min 40 gal 50 000 2 1 88 1 8 60 f...

Page 26: ...r line ex tended above meter regulator assembly 3 ft 91 cm within a height 15 ft 4 6 m Clearance in accordance with local installation codes and the require ments of the gas supplier I Clearance to se...

Page 27: ...nt Length Measured from this Position Vent Pipe to be sloped down toward heater to prevent water from collecting May require a condensate tee Where snow cover is above normal during winter ensure outl...

Page 28: ...be made by the installer Condensation in the venting system is dependent upon installation conditions including but not limited to ambient temperature and humidity of installation location ambient te...

Page 29: ...BURN HOT HOT DANGER Figure 35 Thermostatic Point of Use Mixing Valve Water temperature over 125 F can cause severe burns instantly resulting in severe injury or death Children the elderly and the dis...

Page 30: ...l be a corresponding increase in water pressure due to thermal expansion Thermal expansion can cause premature tank failure leakage This type of failure is not covered under the limited warranty Therm...

Page 31: ...ain inside the building Be certain that no contact is made with any live electrical part The discharge opening must not be blocked or reduced in size under any circumstances Excessive length over 30 o...

Page 32: ...ating at temperatures higher than required for domestic water purposes a mixing valve must be installed See Figure 35 page 29 If the space heating system requires water temperatures in excess of 120 F...

Page 33: ...nions so that the water heater can be isolated from the heating module should servicing of the water heater become necessary 2 Install a drain valve at the lowest point of the heating loop so that wat...

Page 34: ...he water lines of air and sediment and to ensure complete filling of the tank The electrical power may then be turned on See Start Up page 42 GAS SUPPLY SYSTEMS Do not use water heater with any gas ot...

Page 35: ...heater and A sediment trap ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve A ground joint union of proper size between the manual shut of...

Page 36: ...e pressure drop Schedule 40 Steel or wrought iron pipe is the preferred material for the gas line of this water heater It is imperative to follow the sizing recommendations in the latest version of th...

Page 37: ...Z223 1 NFPA 54 HIGH ALTITUDE INSTALLATIONS Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Special consideration must be taken with installa ti...

Page 38: ...y setting on the control system see Table 20 This water heater is equipped with a control system See Control System Operation page 40 Hot water temperatures required for automatic dishwasher and laund...

Page 39: ...monitors the state of the temperature sensor thermistors If the ECO activates due to abnormally high water temperature approximately 190 F the Control Board will lock out and display fault code E00 o...

Page 40: ...nd press the or buttons until reaching the desired value The new value will flash on the LCD display twice per second To validate the new setpoint short press the button If the button is not pressed w...

Page 41: ...aust vent system Installed in accordance with prevailing provisions of local codes or in the absence of such the latest edition of Natural Gas and Propane Installation Code B149 1 Horizontal piping sl...

Page 42: ...valves are open FILLING THE WATER HEATER Avoid water heater damage Fill tank with water before operating Property Damage Hazard CAUTION Never use this water heater unless it is completely full of wat...

Page 43: ...technician or gas supplier DANGER INSTRUCTIONS D UTILISATION OPERATING INSTRUCTIONS A Cet appareil n est pas quip d une veilleuse Le br leur est plut t muni d un dispositif d allumage automatique NE t...

Page 44: ...escape of dangerous flue gasses which could cause deadly asphyxiation Obstructions and deteriorated vent systems may present serious health risk or asphyxiation Chemical vapour corrosion of the flue...

Page 45: ...eanout cover once every 6 months at first Deliming maintenance should then be performed based on the time it takes for 1 inch 2 5 cm of lime to accumulate in the bottom of the water heater CHEMICAL LI...

Page 46: ...if water odour or discolouration occurs Note This rod may reduce but not eliminate water odour problems The water supply system may require special filtration equipment from a water conditioning compa...

Page 47: ...se instructions or have any questions regarding the Temperature Pressure Relief Valve call the toll free number listed on the front page of this manual for technical assistance Temperature pressure re...

Page 48: ...ition failures 0 999999 H10_xxx_xxx H11 Total Flame loss failures 0 999999 H11_xxx_xxx H12 Error code History 1 H12_xxx_xxx H13 Error code History 2 H13_xxx_xxx H14 Error code History 3 H14_xxx_xxx H1...

Page 49: ...The heating mode will be maintained until the call for heat is satisfied tank temperature reaches the Setpoint The gas valve will be turned off closed and the blower will operate for the duration of p...

Page 50: ...set in 15 minutes Manual action E05 Blocked flue Outlet Air Pressure SW open 3rd time in less than one hour Soft Fault Reset in 15 minutes Manual action E06 Blocked flue Outlet Air Pressure SW open 1s...

Page 51: ...Table 25 Error Priority Hard Faults ECO error T Tmax 201F E00 Flue ECO Error Tvent Tvent max 165 F E19 Blower Speed error E21 Blower not running E20 Soft Faults Blower Speed Error E21 Flame out of Se...

Page 52: ...weather or the cold water inlet connection may be leaking C Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area D The temp...

Page 53: ...53 DIAGRAMS DIAGRAMS WIRING DIAGRAM Figure 48 Wiring Diagram...

Page 54: ...65K 100344198 K SWITCH PRESSURE N C AIR INTAKE 1 88 100344199 K SWITCH PRESSURE N C FLUE 1 8 100344200 K THERMISTOR 3 4NPT 100344201 K TRAP CONDENSATE POLYPROPYLENE 100344202 K DIPTUBE HT2 3 4NPTX3X34...

Page 55: ...55 NOTES NOTES...

Page 56: ...800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com In Canada contact A O Smith Enterprises Ltd 599 Hill Street West Fergus ON Canada N1M 2X1 Technical Support 1 888 479 8324 www hotwate...

Reviews: