background image

13

Fire and Explosion Hazard

• 

Improper use can result in fire or 

explosion.

Read the instruction manual before 

installing, using, or servicing the water 

heater. 

• 

Maintain required clearances to 

combustibles.

Minimum  clearances  from  combustible  materials  are  stated  on 

the data plate located on the front of the water heater. Standard 

clearances are 0 mm (0”) at the sides and rear, 0 mm (0”) from the 

front, and 0 mm (0”) from the top. If the clearances from combustible 

material  stated  on  the  water  heater  differ  from  the  standard 

clearances,  install  the  water  heater  according  to  the  clearances 

stated on the water heater.

Adequate clearance for inspection and service should be considered 

before installation. A minimum of 610 mm (24”)  of front clearance 

and 102 mm (4”) on each side should be provided for access to 

replaceable and/or serviceable parts such as drain valve, condensate 

drain, temperature-pressure relief valve, and the vent connection 

(exhaust elbow).

Figure 9

 may be used as a reference guide to locate the specific 

clearance locations. When installing the water heater, consideration 

must be given to proper location. The location selected should be 

as close to the wall as practicable and as centralized with the water 

piping system as possible.

CEILING

FRONT VIEW

0 mm

(0") MIN.

0mm

(0") MIN.

*102mm

(4") MIN.

*For service access

LEFT

WALL

RIGHT

WALL

TOP VIEW

OF CLOSET

WITHOUT DOOR

WATER

HEATER

0mm

(0") MIN.

0mm

(0") MIN.

*610mm

(24") MIN.

TOP VIEW

OF CLOSET

WITH DOOR

WATER

HEATER

Figure 9. Clearance Locations

COMBUSTION AIR AND VENTILATION

A  gas  water  heater  cannot  operate  properly  without  the  correct 

amount of air for combustion. Never obstruct the flow of ventilation 

air. If you have any doubts or questions at all, call your gas supplier. 

Failure to provide the proper amount of combustion air can result in 

a fire or explosion and cause death, serious bodily injury, or property 

damage.

Breathing carbon monoxide can cause brain damage or death.

Always read and understand instruction manual.

• Install water heater in accordance with the 

instruction manual and B149.1.

• To avoid injury, combustion and ventilation air 

must be taken from outdoors.

• Do not place chemical vapour emitting products 

near water heater.

Breathing Hazard - Carbon Monoxide Gas

WARNING

12” max

100 sq in

Front View of Closet Door

Ventilation 

Air 

Opening

Rectangular 

Air Duct

3” min.

Figure 10. Closet Door Ventilation

Propellants of aerosol sprays and volatile compounds, (cleaners, 

chlorine  based  chemicals,  refrigerants,  etc.)  in  addition  to  being 

highly flammable in many cases, will also react to form corrosive 

acids when exposed to the combustion products of the water heater. 

The results can be hazardous, and also cause product failure. Air 

for  combustion  and  ventilation  must  not  come  from  a  corrosive 

atmosphere. Any failure due to corrosive elements in the atmosphere 

is excluded from warranty coverage.

It is imperative that the water heater(s) be installed direct vent so 

that all air for combustion and ventilation is taken from outdoors.

CORROSION AND WATER QUALITY

Water quality will vary from location to location and may contain 

contaminates that may reduce the life or performance of the water 

heater.

Contaminates which can reduce the life or performance of the water 

heater if present in high quantities include those which contribute 

to  hardness  (dissolved  minerals  such  as  sodium,  calcium  and 

magnesium); plus chlorides and sulfates. Additionally, water that is 

too acidic or alkaline (measured as pH) can reduce the life of the 

water heater. Water treatment systems (such as water softeners for 

hardness) should be used and maintained properly if the contaminate 

levels exceed the following:

Warranty  is  void  in  applications  which  exceed  the  water  quality 

requirements listed below.

Table 3. Water Quality Requirements

Total Hardness

205 mg/liter (12 grains per gal.) max.

Chloride

200 mg/liter (12 grains per gal.) max.

pH

6.5-8.0

Alkalinity

200 mg/liter (12 grains per gal.) max.

Summary of Contents for 100 Series

Page 1: ...ch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier c...

Page 2: ...Installation 31 Space Heating and Potable Water System 32 Combo Heating Inlet And Outlet Side Taps 32 Combo Heating 32 System Requirements 32 Installation 33 Electrical Supply 33 Dedicated Power Wiri...

Page 3: ...hazardous situation which if not avoided could result in property damage All safety messages will generally tell you about the type of hazard what can happen if you do not follow the safety message an...

Page 4: ...flow THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN Explosion Hazard Flammable hydrogen gases may be present Keep all ignition sources away from faucet when turning o...

Page 5: ...sources away from faucets after extended periods of non use Maintain required clearances to combustibles Do not expose water heater controls to excessive gas pressure Fire Hazard Do not install water...

Page 6: ...e essential to the proper operation of the water heater and your safety Detailed installation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference...

Page 7: ...pply Pressure Maximum Supply Pressure Electrical Characteristics Gas Type In W C kPA In W C kPA In W C kPA Volts Hz Amperes Natural 0 0 3 5 1 10 14 3 49 120 60 10 The manifold pressure is the factory...

Page 8: ...l 25 Control Panel 26 Outlet Air Pressure Switch OAPS 27 Blower 28 Gas Control Valve 29 Combo Heating System Return Inlet Optional 30 Temperature Sensor 31 Burner Insulation Shield 32 Burner Refractor...

Page 9: ...9 34 35 33 31 32 27 37 38 41 42 44 43 Figure 3 Blower and Burner Components 44 42 39 35 36 40 34 41 43 Figure 4 Blower and Intake Air Components...

Page 10: ...s the unit from igniting most likely the exhaust is blocked by some means Check to see if the condensate is allowed to flow freely from the condensate trap and for obstructions in the exhaust venting...

Page 11: ...nstall without adequate drainage Property Damage Hazard CAUTION Carefully choose a location for the new water heater The placement is a very important consideration for the safety of the occupants in...

Page 12: ...and liquids in the vicinity of this or any other appliance Avoid all ignition sources if you smell gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate M...

Page 13: ...amage Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Install water heater in accordance with the instruction manual and B149 1 To avoid injury...

Page 14: ...shows various end termination details and clearances for PV installations Note The information provided in Figure 2 page 8 is intended as a guideline for good vent installation practices only This wat...

Page 15: ...to ULC S636 Check local codes to determine which materials are allowed in your area and only use approved material All venting material and components must be joined with the approved primer cleaner a...

Page 16: ...t systems are designed to use specific adaptors to connect the water heater venting These adaptors are available through your venting supplier The PVC vent termination elbow supplied with this heater...

Page 17: ...ntly push the screen into the termination elbow until it sits against the inside shoulder The debris vent screens are self securing Note In the concentric vent application the vent screen is to be ins...

Page 18: ...Air Condensate Tee Installation DIRECT VENT AIR INTAKE MOISTURE PROTECTION The air intake piping in a direct vent system will normally not have any moisture accumulation in it However in certain case...

Page 19: ...15 ft 4 6 m Clearance in accordance with local installation codes and the require ments of the gas supplier I Clearance to service regulator vent outlet 3 ft 91 cm Clearance in accordance with local i...

Page 20: ...te the same side of roof 5 The centerline of the air intake termination and the centerline of the exhaust vent termination must not be closer than 200 mm 8 6 The air intake terminal and the exhaust ve...

Page 21: ...centers can be found in Table 10 2 Slide both the intake and exhaust pipes through the holes Solvent cement both pipes to the base of the vent termination kit follow the solvent cementing procedures...

Page 22: ...tical roof installation Ensure the combustion air intake location is above the anticipated snow level Table 11 Concentric Vent Termination Kits Vent Dia P N 2 100153586 3 100111100 Combustion Air Abov...

Page 23: ...ted and installed in accordance with local building code and CSA B149 1 Natural Gas and Propane Installation Code 1 Once the proper location has been determined cut 2 holes in the wall large enough to...

Page 24: ...t Number IPEX Part Num ber Description Pipe Outside Diameter Hole Spacing Center to Center 100086241 196984 2 Flush Mount Vent Kitt 2 375 5 63 100187887 196985 3 Flush Mount Vent Kit 3 5 7 63 Each Kit...

Page 25: ...e Equivalent Vent Length Water Heater Model Heater Input Btu Hr Vent Size Inside Diam Pressure Switch Settings in w c Low Profile Equiv Vent Length Intake Exhaust Max Min 40 gal 50 000 2 1 88 1 8 60 f...

Page 26: ...r line ex tended above meter regulator assembly 3 ft 91 cm within a height 15 ft 4 6 m Clearance in accordance with local installation codes and the require ments of the gas supplier I Clearance to se...

Page 27: ...nt Length Measured from this Position Vent Pipe to be sloped down toward heater to prevent water from collecting May require a condensate tee Where snow cover is above normal during winter ensure outl...

Page 28: ...be made by the installer Condensation in the venting system is dependent upon installation conditions including but not limited to ambient temperature and humidity of installation location ambient te...

Page 29: ...BURN HOT HOT DANGER Figure 35 Thermostatic Point of Use Mixing Valve Water temperature over 125 F can cause severe burns instantly resulting in severe injury or death Children the elderly and the dis...

Page 30: ...l be a corresponding increase in water pressure due to thermal expansion Thermal expansion can cause premature tank failure leakage This type of failure is not covered under the limited warranty Therm...

Page 31: ...ain inside the building Be certain that no contact is made with any live electrical part The discharge opening must not be blocked or reduced in size under any circumstances Excessive length over 30 o...

Page 32: ...ating at temperatures higher than required for domestic water purposes a mixing valve must be installed See Figure 35 page 29 If the space heating system requires water temperatures in excess of 120 F...

Page 33: ...nions so that the water heater can be isolated from the heating module should servicing of the water heater become necessary 2 Install a drain valve at the lowest point of the heating loop so that wat...

Page 34: ...he water lines of air and sediment and to ensure complete filling of the tank The electrical power may then be turned on See Start Up page 42 GAS SUPPLY SYSTEMS Do not use water heater with any gas ot...

Page 35: ...heater and A sediment trap ahead of the gas control valve to help prevent dirt and foreign materials from entering the gas control valve A ground joint union of proper size between the manual shut of...

Page 36: ...e pressure drop Schedule 40 Steel or wrought iron pipe is the preferred material for the gas line of this water heater It is imperative to follow the sizing recommendations in the latest version of th...

Page 37: ...Z223 1 NFPA 54 HIGH ALTITUDE INSTALLATIONS Breathing carbon monoxide can cause brain damage or death Always read and understand instruction manual Special consideration must be taken with installa ti...

Page 38: ...y setting on the control system see Table 20 This water heater is equipped with a control system See Control System Operation page 40 Hot water temperatures required for automatic dishwasher and laund...

Page 39: ...monitors the state of the temperature sensor thermistors If the ECO activates due to abnormally high water temperature approximately 190 F the Control Board will lock out and display fault code E00 o...

Page 40: ...nd press the or buttons until reaching the desired value The new value will flash on the LCD display twice per second To validate the new setpoint short press the button If the button is not pressed w...

Page 41: ...aust vent system Installed in accordance with prevailing provisions of local codes or in the absence of such the latest edition of Natural Gas and Propane Installation Code B149 1 Horizontal piping sl...

Page 42: ...valves are open FILLING THE WATER HEATER Avoid water heater damage Fill tank with water before operating Property Damage Hazard CAUTION Never use this water heater unless it is completely full of wat...

Page 43: ...technician or gas supplier DANGER INSTRUCTIONS D UTILISATION OPERATING INSTRUCTIONS A Cet appareil n est pas quip d une veilleuse Le br leur est plut t muni d un dispositif d allumage automatique NE t...

Page 44: ...escape of dangerous flue gasses which could cause deadly asphyxiation Obstructions and deteriorated vent systems may present serious health risk or asphyxiation Chemical vapour corrosion of the flue...

Page 45: ...eanout cover once every 6 months at first Deliming maintenance should then be performed based on the time it takes for 1 inch 2 5 cm of lime to accumulate in the bottom of the water heater CHEMICAL LI...

Page 46: ...if water odour or discolouration occurs Note This rod may reduce but not eliminate water odour problems The water supply system may require special filtration equipment from a water conditioning compa...

Page 47: ...se instructions or have any questions regarding the Temperature Pressure Relief Valve call the toll free number listed on the front page of this manual for technical assistance Temperature pressure re...

Page 48: ...ition failures 0 999999 H10_xxx_xxx H11 Total Flame loss failures 0 999999 H11_xxx_xxx H12 Error code History 1 H12_xxx_xxx H13 Error code History 2 H13_xxx_xxx H14 Error code History 3 H14_xxx_xxx H1...

Page 49: ...The heating mode will be maintained until the call for heat is satisfied tank temperature reaches the Setpoint The gas valve will be turned off closed and the blower will operate for the duration of p...

Page 50: ...set in 15 minutes Manual action E05 Blocked flue Outlet Air Pressure SW open 3rd time in less than one hour Soft Fault Reset in 15 minutes Manual action E06 Blocked flue Outlet Air Pressure SW open 1s...

Page 51: ...Table 25 Error Priority Hard Faults ECO error T Tmax 201F E00 Flue ECO Error Tvent Tvent max 165 F E19 Blower Speed error E21 Blower not running E20 Soft Faults Blower Speed Error E21 Flame out of Se...

Page 52: ...weather or the cold water inlet connection may be leaking C Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area D The temp...

Page 53: ...53 DIAGRAMS DIAGRAMS WIRING DIAGRAM Figure 48 Wiring Diagram...

Page 54: ...65K 100344198 K SWITCH PRESSURE N C AIR INTAKE 1 88 100344199 K SWITCH PRESSURE N C FLUE 1 8 100344200 K THERMISTOR 3 4NPT 100344201 K TRAP CONDENSATE POLYPROPYLENE 100344202 K DIPTUBE HT2 3 4NPTX3X34...

Page 55: ...55 NOTES NOTES...

Page 56: ...800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com In Canada contact A O Smith Enterprises Ltd 599 Hill Street West Fergus ON Canada N1M 2X1 Technical Support 1 888 479 8324 www hotwate...

Reviews: