background image

SURFACE STEAMER SS-400TT

13

P/N 1011073 Rev. H 12/13 

McDonald’s

A.J. Antunes & Co.

TROUBLESHOOTING (continued)

Problem

Possible Cause

Corrective Action

Excessive  

condensation in 

Food Compartment.

Water pressure is too high.

Verify that the Water Pressure Regulator is set to  

10 psi. Adjust accordingly.

Programming and or 

SHOT 

and 

Intr 

values were adjusted improperly 

(Timer Models only).

Reprogram the 

SHO

 and 

H2O

 values as described 

in the Programming section of this manual to factory 

settings. See “Factory Resets.”

Excessive Steam 

escapes from front 

or sides of steamer.

Worn or damaged Bun Caps.

Replace Bun Caps.

Steam Generator’s 

surface becomes 

flooded (fills with 

excess water).

Water Pressure Regulator is faulty or 

not properly installed.

Verify that a Water Pressure Regulator is installed 

and set to 10 psi. Adjust accordingly or replace.

Programming and/or the 

SHO

 value 

was adjusted or changed improperly.

Reprogram the Control Board to the recommended 

settings. Refer to the Programing section of this 

manual. See “Factory Resets.”

Solenoid Valve is leaking due to 

debris trapped inside the plunger. 

Attempt to flush the debris out of the valve by 

operating the unit on a number of cycles and then 

letting it rest. If the unit still leaks, disassemble 

the Solenoid Valve and clean out the plunger.  

Reassemble the unit and test again. If a leak is still 

present, replace the Solenoid Valves. Contact your 

maintenance person or Authorized Service Agency.

Improper Daily/Monthly cleaning.

Follow the Daily/Monthly cleaning procedures  

carefully.

The Generator surface temperature 

is too low.

Verify that the Generator set point temperature is 

between 400°F (204°C). See “Factory Resets.”

Insufficient or excessive calcium/

mineral deposits on the Generator 

surface.

Verify that a thin layer of calcium/mineral deposits 

is present on the Generator surface. Refer to the 

Maintenance section of this manual.

Solenoid Valve is installed incorrectly. If the Solenoid Valve was replaced, verify that the 

”IN” and “OUT” labels on the valve correspond to 

the water flow.

Summary of Contents for SS-400TT

Page 1: ...and in no event shall A J Antunes Co or any of its Divisions be liable for special consequential or incidental damages for the breach or delay in the performance of this warranty WARRANTY EXCLUSIONS The cost of Installation Equipment that has been damaged due to shipment Purchaser should make damage claim directly upon carrier Alteration misuse abuse Improper storage or handling Improper maintenan...

Page 2: ...of Surface Steamer at the same time Water is superheated into steam which penetrates the bun to heat it quickly and efficiently This manual provides the safety installation and operating procedures for the Surface Steamer We recommend that this manual be read prior to installing and operating the unit OWNER INFORMATION IMPORTANT Keep these instructions for future reference If the unit changes owne...

Page 3: ...2 3 4 READY STEAM POWER A C B Model Mfg No Height A Width B Depth C SS 400TT 9100906 8 20 3 cm 7 1 4 18 4 cm 26 7 8 68 3 cm Model Mfg No Volt Watts Amps Hz Plug Description Plug Configuration SS 400TT 9100906 208 4800 23 0 60 330P6W 30 Amp 250 VAC Pin Sleeve P N 0700482 Electrical Ratings and Plug Configuration ...

Page 4: ...uipment should be serviced by qualified personnel only Contact the nearest Authorized Service Agency for adjustment or repair Do NOT block or cover any openings on the unit Do NOT immerse the cord or plug in water Keep cord away from heated surfaces Do NOT allow the cord to hang over edge of table or counter The following warnings and cautions appear throughout this manual and should be carefully ...

Page 5: ...ed con tact A J Antunes Technical Service IMMEDIATELY at 1 877 392 7854 North America only or 630 784 1000 INSTALLATION Figure 1 SS 400TT Surface Steamer CAUTION All electrical connections must be in accordance with local electrical codes and any other applicable codes CAUTION This equipment is to be installed to comply with the basic plumbing code of the Building Officials and Code Administrators...

Page 6: ...ses sets Do NOT reuse old water hose sets 1 Connect the steamer line Reverse Osmosis Quick Disconnect to the Water Pressure Regulator 2 Turn the unit on its side so the Water Pressure Regulator is facing up Figure 2 3 Loosen the Locknut counterclockwise Figure 2 then turn the Water Pressure Adjustment Knob clockwise until the Water Pressure Regulator Gauge reads 10 psi CAUTION Operating pressure s...

Page 7: ...ion of this manual 4 Open the Bun Cap and then lift the Flipper to remove the buns from the steam area 5 Complete the assembly of the sandwich Figure 4 Front View Primary Control Panel View CAUTION Buns will be hot after steaming Lift the Flipper to remove buns Use caution to avoid burns OK 1 2 3 4 READY STEAM POWER Heat Generators 2 Pairs Bun Cap 2 total Flipper 2 total OK 1 2 3 4 READY STEAM POW...

Page 8: ...76ºC to 400ºF 204ºC Increments 1 400 RPT Repeat Number of times the audio signal repeats at the conclusion of a steam cycle 1 to 255 Increments 1 2 DEGF DEGC Allows the user to select whether the unit displays temperatures in degrees Fahrenheit or Celsius DEGF OK 1 2 3 4 READY STEAM POWER Channels 1 through 4 Unit Display Steam Activation Button Power Button Program Button Up Arrow Button Down Arr...

Page 9: ...s Remove the diffusers Clean the Steam Generators with a paper towel damp ened with water Make sure all crumbs and seeds are removed from the generators Clean the dif fusers with a clean sanitized towel sprayed with EXCEED Wipe the diffusers with a clean sani tized towel sprayed with SolidSense Sanitizer 6 Clean the top steamer surface Wipe the top steamer surface with a clean sanitized towel spra...

Page 10: ...amer is working properly 1 Check for proper operation Turn the unit on and let it warm up Steam 2 or 4 buns If the unit steams the buns correctly you do not need to continue If the buns are not steamed correctly continue with this procedure 2 Turn off unit Turn the steamer s power switch to the off position Unplug the power cord from the out let Allow the steamer to cool for at least 30 minutes 3 ...

Page 11: ...e indicator light is on Hi Limit Thermostat is tripped or inoperable Contact your maintenance person or Authorized Service Agency for service Solid State Relay is inoperable Thermocouple is inoperable Main Control Board is inoperable Steam Generator is inoperable Loose burnt or broken wires in heat circuit Relay Board is inoperable Main electrical panel circuit breakers trips Damaged receptacle pl...

Page 12: ...tenance section of this manual Generator surface is bare little or no traces of mineral deposits The Generator surface must have a thin coating of calcium mineral deposits for proper steaming Refer to the Maintenance section of this manual The internal rubber hoses are pinched or kinked Straighten and reposition the rubber hoses Generator Diffusers are missing Install Generator Diffuser or replace...

Page 13: ...e Control Board to the recommended settings Refer to the Programing section of this manual See Factory Resets Solenoid Valve is leaking due to debris trapped inside the plunger Attempt to flush the debris out of the valve by operating the unit on a number of cycles and then letting it rest If the unit still leaks disassemble the Solenoid Valve and clean out the plunger Reassemble the unit and test...

Page 14: ...ch 4 40 x 1 4 1 26 0506038 Bracket Display 2 27 1001369 Label Filet 1 28 0012522 Solenoid Valve Assembly 1 29 308P144 Screw Mach 8 32 x 1 4 w 6 Head 1 30 4010215 Momentary Switch Assembly Rear 1 31 4070148 Rear Board Surface Steamer 1 32 0012523 Water Pressure Regulator Assembly 1 33 0400375 Strain Relief Cord Connector 1 34 4010239 Momentary Switch Assembly Front 1 35 7000542 Rocker Switch with G...

Page 15: ...SURFACE STEAMER SS 400TT 15 P N 1011073 Rev H 12 13 McDonald s A J Antunes Co REPLACEMENT PARTS continued 1 2 3 7 4 5 6 9 10 11 12 13 14 15 16 17 18 19 21 22 23 24 8 20 10a ...

Page 16: ...v H 12 13 McDonald s A J Antunes Co REPLACEMENT PARTS continued 25 26 30 28 See Inset A 29 31 32 33 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 52 Inset A Cutaway view showing the installation of item 28 Solenoid Assembly in white 27 34 50 51 ...

Page 17: ... WHT YEL RED ORG RED YEL ORG GRN YEL TB1 GND GRN YEL ACTIVATION SWITCH J14 J1 J12 J11 1 1 2 2 1 2 1 2 BLK 18 GA 200 C RED WHT SW1 REAR FRONT WIRE NUMBER J1 J15 200 400 BLK 3 3 RED YEL RED YEL BLK BRN WHT BLU GRN YEL CONTROL BOARD BLK 1 2 3 4 5 6 ORG ORG 3 4 1 2 WIRE LEGEND ORG ORG BLK A B A2 A1 B1 B2 4 BUTTON REAR 8 BUTTON FRONT BLK WHT WHT WHT HI LIMIT FRONT HLF HI LIMIT REAR HLR RELAY BRD 25 AMP...

Page 18: ...SURFACE STEAMER SS 400TT 18 P N 1011073 Rev H 12 13 McDonald s A J Antunes Co NOTES ...

Page 19: ...SURFACE STEAMER SS 400TT 19 P N 1011073 Rev H 12 13 McDonald s A J Antunes Co NOTES continued ...

Page 20: ......

Reviews: