The option "reset to default" will perform the reorganization of the priority of the ports to the default configuration. After
clicking the button, it will ask for confirmation to make sure we want to make the change.
Battery Test Schedule
This section provides a program for periodic battery discharge tests.
The "Type" option allows you to select the trial period for daily, weekly, monthly and yearly options.
In the second field "Repeat every" we can select the frequency of the test.
And finally, in "Start Time", the time the test begins with the hh: mm format.
Once all the parameters have been selected, we must double click on the "Save" button to save the modifications.
Example:
If we choose the following configuration:
Type: Day
Repeat every: 5
Start time: 02:00
Every 5 days, at hour 2:00 the battery discharge test will start
6
.
6
For more information on the battery test, see the section “Battery charger module”
Figure 24 – Selection of the behaviour mode
Figure 25 – Battery discharge test programming