Installation Manual
H3C S9500 Series Routing Switches
Chapter 2 Preparing for Installation
2-15
2)
Connect the DC input terminal blocks and the air switches with 6 mm
2
cables and
fix the cable properly. Also use a 6 mm
2
cable for grounding, as illustrated in
Figure 2-11
.
Figure 2-11
Backplane diagram for connecting DC input terminal blocks and air
switches
3)
Fix the DC power distribution box onto the back of the cabinet.
Figure 2-12
Diagram for fixing the power distribution box to the rear of the N68 cabinet
4) You can make the air switches to supply power to DC power modules by
connecting the lower terminals of the air switches to DC power input terminals and
supply voltages to DC power. (Refer to
Figure 2-9
for detail. Note that the
diameters of the cables need to be 6 mm
2
or 10 mm
2
.)
5) You can use the BGND and PGND terminal blocks as needed. The rightmost
PGND terminals must be connected to the cabinet using 6 mm
2
cables, as
illustrated in
Figure 2-12
.
6) Fasten the connected power cables with a wire and secure them onto the power
distribution box.
7)
Use two 16 mm
2
cables to connect the cabinet and the DC power distribution box.
You need to connect the two cables to the leftmost terminal blocks of the cabinet,
as illustrated in
Figure 2-9
.