2N® LTE Verso Configuration Manual
57
/
224
•
•
•
•
•
Switch 1–4
Switch enabled
– enable/disable the switch globally. When disabled, the switch cannot
be activated by any of the available codes (including user switch codes), by a call or quick
dial button.
Switch mode
–
set the monostable/bistable mode for the switch. The switch is switched
off after a timeout in the monostable mode and switched on with the first activation and
off with the next activation in the bistable mode.
Switch-on duration
–
set the switch-on time for a monostable switch. This value is not
applied in the bistable mode.
Controlled output
–
assign an electric output to the switch.
Choose one of the available
intercom outputs: relay, power output, extender output. If you select
None
, the switch will
not control any electric output but can control external equipment via HTTP commands.
Output type
–
if you use the
2N
®
IP/LTE Intercom – Security Relay
module, set the
output type to
Security
. In the
Security
mode, the output works in the inverse mode, i.e.
remains closed and controls the
2N
®
IP/LTE Intercom – Security Relay
module using a
specific pulse sequence. If you use the inverse mode (i.e. the door is locked when voltage
is applied), set the
inverse
output type. In case multiple switches are set to the same
output but different output types, the following priority will be applied: 1. security, 2.
inverse, 3. normal.