TROUBLE SHOOTING GUIDE

Problem

No lights are visible in
the sensor eye.
Valve does not flush.

Light flashes randomly in
sensor eye and valve
does not flush

Lights follow normal
sequence, valve does
not flush.

Valve flushes but does
not shut off.

Valve leaks

LED flashes every 30
seconds.
Valve operates back-
wards.

Possible Cause

Valve could be sensing a
close by surface or reflections
from some opposite surface.

Lens could be dirty or dam-
aged.
Solenoid lead disconnected,
reversed or broken wire.
Battery corrosion has caused
loss of contact.

Sensor not detecting user.

Electronics fault

Sensing range too short.

Water not turned on.

Plugged filter.

Stop valve closed.
Wiring fault.

Solenoid malfunction.

Diaphragm damage or plugged
diaphragm orifice.
Solenoid malfunction

Incorrectly installed.

Damaged O-ring on inlet tube.
Low battery voltage

Solenoid connector not
properly aligned.

Diagnosis

Hold a flat object at an acute
angle to the valve and see if it
flushes ( three ring binder
works well)
Visual inspection of lens.

Check plug insertion and wire
continuity.
Visual inspection

Hold hand at different ranges
in front of valve to see if it can
be detected.
Run through reset procedure
below
Hold hand close to lens to see
if it will produce the 4 flash/2
flash pattern.
Close stop, disconnect valve,
crack stop to check for water.
Close stop, remove and
inspect filter.
Check stop screw.
Check solenoid leads and
insertion of solenoid plug.
Remove solenoid and inspect
diaphragm and plunger.

Visual inspection.

Remove solenoid and inspect
diaphragm and plunger.

Check for leak location.

Check for cuts.

Solution

Reduce sensing range
Eliminate reflective
object.

Clean or replace if
obstructed or damaged
Reinsert plug or repair
leads
Replace batteries and
clean or replace battery
housing.
Reset sensor range
(Appendix A)

Reset range.

Find source valve and
turn on.
Clean and reinstall filter

Open stop valve
Reinsert plug or repair
wiring
Clean P6900-SRK
components.  See parts
list
Replace diaphragm

Clean P6900-SRK
components.  See parts
list
Remove and reinstall.
Pay close attention to
alignment of inlet tube
and outlet boss with
mating pieces.
Replace O-ring
Replace batteries

Reconnect plug properly.

Electronics Reset Procedure

: Remove battery cover (J) Figure 7).  Allow electronics to set for a minimum of 4 minutes.

Resecure the battery cover and gasket with screw provided.  Reconnect solenoid wire connector.  Place top cover assembly
back on valve housing, carefully tuck wires into housing.  Secure cover with two screws provided.

Содержание ZEG6003EV

Страница 1: ...charges or any loss injury or damages whatsoever including incidental or consequential damages The sole and exclusive remedy shall be limited to the replacement of the defective goods Before installation and use the purchasershalldeterminethesuitabilityoftheproductforhisintendeduseandthepurchaserassumesallriskandliability whateverinconnectiontherewith Where permitted by law the implied warranty of...

Страница 2: ... stops are connected to the water supply and water pressure is available it is recommended that the supply piping be flushed to remove dirt metal chips etc from system A Before the valve is installed open each stop fully for a brief time and catch the water in a two gallon or larger bucket For multiple installations start with the stop valve closest to the water supply and work toward the most rem...

Страница 3: ...tall the AA cell batteries provided Remove the battery box cover screw using the 1 8 allen wrench provided Turn the top assembly upside down and the screw will drop down and can be used to pull the cover off Load the four heavy duty AA alkaline batteries following the battery orientation guide on the battery box cover Note that the coil springs always contact the flat negative end of the battery I...

Страница 4: ... the magnet and stand in front of sensor about 20 away for the rest of the calibration The calibration process takes about 60 seconds Do not move during this process 4 When calibration is completed the solid red light will dis appear and the LED will blink twice brightly 8 9 LOW BATTERY WARNING The LED will double flash every 30 seconds when the bat teries reach a predetermined depletion level The...

Страница 5: ...e detected Run through reset procedure below Hold hand close to lens to see if it will produce the 4 flash 2 flash pattern Close stop disconnect valve crack stop to check for water Close stop remove and inspect filter Check stop screw Check solenoid leads and insertion of solenoid plug Remove solenoid and inspect diaphragm and plunger Visual inspection Remove solenoid and inspect diaphragm and plu...

Страница 6: ...41 3 4 Spud Friction Washer 42 3 4 Spud Sleeve 43 3 4 Spud Escutcheon 44 Setscrew for Control Stop Cover 45 Vandal Resistant Control Stop Cover 46 Stop Cap 47 Adjusting Screw 48 Guide Holder 49 Piston Guide 50 Guide O Ring 51 Piston 52 Piston Seal 53 Stop Body 54 Sweat Solder Adapter 55 Supply Cover Tube Flush Connections and Spud Coupling Kits Product No 3 4 Flush Connection and Spud Coupling Ite...

Отзывы: