CAPACITY CONTROL AND STAGING

The HVAC system is sized to handle the load of the entire 

home or building. Because of this, when all the zones are not 

calling, the load to the HVAC system can diminish below its 

designed capacity. Left unchecked, the HVAC unit could 

freeze up or overheat. To compensate for this, the Digitract 4 

is furnished with a built in Capacity Controller. The basic 

function of the Capacity Controller is to monitor the leaving

Y1 Cool Operation

 - Upon a cool call, the controller will ener-

gize Y1 and G. If the leaving air temperature drops below the 

low limit setpoint, Y1 will be de-energized, the PWR LED will 

flash indicating a stage 1 capacity cutout. After 4 minutes the 

leaving air temperature will be checked again; if the leaving 

air temperature has risen above the cutout setpoint, then Y1 

will re-energize and PWR LED will stop flashing. If controller is 

for Heat Pump, and the reversing valve is in the O position, 

Upon a heat call, the controller will energize W1 LED if the 

leaving air temperature is less than High Limit setpoint. This 

setpoint is determined by adjusting the potentionmeter 

located in the upper right corner of the controller, HI. W1 well 

de-energize if LAT exceeds the High setpoint, W1 LED will 

de-energize and the PWR LED will flash slowly indicating a 

stage 1 capacity cutout. If the LAT is below the High limit, W1 

will energize, W1 LED will illuminate.

Y1 Heat Operation

 - Upon a call for heat, the controller will 

energize Y1 LED, if the LAT rises above the High Limit (poten-

tiometer located on controller top right corner, marked HI), 

then Y1 LED will de-energize and PWR LED will flash indicat

-

ing a stage 1 capacity cutout. After a 4 minute time delay the 

LAT will be checked; if LAT is less than HI cutout then Y1 LED 

will re-energize and PWR LED will stop flashing. If the O/B 

jumper is in the B position, the O/B LED will illuminate with 

Y1.

Y2 Heat Operation

 - After 4 minutes of continuous Y1 opera-

tion, the leaving air temperature will be checked. If the LAT is 

less than high limit (HI) minus 25° (HI of 120 - 25 = 95°), then 

Y2 will energize, indicated by the Y2 LED. Y2 will cycle off 

when LAT is HI minus 5° (120 - 5 = 115) or when all heat calls 

are satisfied.

Fossil Fuel Operation

 - For Fossil Fuel Operation, FF jumper 

must be placed in the FF position.

For  greater  efficiency  and  comfort,  an  Outdoor Air  Sensor, 

Part # FOAS, should be used in the Fossil Fuel application. 

The FOAS is used to lock out compressor operation when 

outside air temperature has dropped below Balance Point 

setpoint, the temperature at which that heat pump is no 

longer efficient. When the outside temperature is less than 

Balance Point setpoint and there is a call for heat, Y1 and Y2

air temperature and cycle the unit off when the air is out of 

operating range and, after a minimum 4 minute time delay, 

turn the unit back on when the air temperature has returned 

within operating range. Additionally, for heat pump the 

Capacity Controller will turn on the heat pump auxiliary heat 

if the coil leaving air temperature is not hot enough in heat 

mode.

the O/B output will be energized simultaneously with the Y1 

indicated by the O/B LED. After 8 minutes of continuous Y1 

run time, LAT (leaving air temperature) will be checked. if LAT 

is greater than low limit (LO) plus 12° (LO of 45° + 12° = 57°), 

then Y2 will energize and Y2 LED will illuminate. Y2 will cycle 

off when LAT drops below 5° plus low limit (45° + 5° = 50° ). 

Y2 and G will de-energize when all calls are satisfied, and the 

controller will go into a 4 minute purge cycle

.

W2 Heat Operations

 - After W1 has operated continuously 

for 4 minutes and LAT is less than High Limit minus 25° (if HI 

of 145° - 25° = 120°), then W2 will energize by the W2 LED. If 

LAT rises to High Limit minus 5°, then W2 will de-energize 

indicted by W2 LED off and PWR LED flashing quickly. If all 

heat calls are satisfied both W1 and W2 will de-energize and 

controller will go into a 4 minute purge cycle.

will be locked out; and W2 will energize indicated by W2 LED 

illuminating. The HI limit will be reset automatically to 135° to 

provide HI limit protection for furnace. Calls for heat are 

recognized from all thermostats; dampers for zones calling 

for heat will open, indicated by DPR LEDs off, while zones not 

calling will close, indicated by illuminated DPR LEDs. The 

Balance Point setpoint is adjustable from 25° to 41° by 

moving Balance Point potentiometer to desired setpoint. 

Refer to page 9 for potentiometer location (J) on DT4U.

 Applications without FOAS will stage on time and tempera-

ture. With the Fossil fuel jumper in the FF position, after 8 

minutes of continuous heat operation, if leaving air is less 

than 90°, then W2 will energize. Y1 and Y2 will de-energize 

indicated by LEDs off; W2 LED will illuminate and furnace will 

start. The HI limit will reset automatically to 135° to protect 

furnace heat exchanger. DPR LED for calling zones will be off, 

while DPR LEDs for non-calling zones will illuminate. All 

thermostats are able to make calls for heat.

Auxiliary Heat (Electric Strip Heat)

 - After 8 minutes of contin-

uous operation the leaving air temperature is checked. If LAT 

is below 90° W2 will energize and W2 LED will illuminate. W2 

will cycle off above 100°, or when all calls are satisfied.

COOLING OPERATION

HEAT OPERATION - GAS/ELECTRIC

HEAT OPERATION - HEAT PUMP

Содержание DigiTract 4

Страница 1: ...DigiTract 4 Two Stage Heat Cool Comfort Control System Installation Guide Part DT4UMAN Zoning Systems That s all we do Rev July 2018...

Страница 2: ...il Fuel Application 11 CAPACITY CONTROLLERS Gas Electric 11 Heat Pump 11 Capacity Control and Staging 11 ZONE DAMPERS Round 13 14 Rectangular 15 16 Installation Notes 17 BYPASS DAMPERS Barometric 17 1...

Страница 3: ...le the HVAC system off if the leaving air gets too hot in heat mode or too cold in cool mode For heat pumps this input is also used to control the auxiliary heat See Capacity Controller section on pag...

Страница 4: ...ade TREC W x H up to 5 SP Medium Pressure Dampers Round STMPD size up to 1 75 SP Rectangular STMRTD W x H up to 1 SP Heavy Duty Rectangular STCD W x H up to 1 75 SP BYPASS DAMPERS DAMPER TRANSFORMER 5...

Страница 5: ...nsor in the supply air stream as far from the coil heat exchanger as possible before the bypass takeoff Do not locate the LAT downstream of the bypass takeoff Connect W2 and Y2 of the DT4U output to u...

Страница 6: ...bypass takeoff Connect W2 from the controller to the units electric heat stage terminal designation Thermostats Heat Pump thermostats 1C 2H Note Some combination thermostats do not have an E terminal...

Страница 7: ...ring one to three TR TREC series dampers to a zone Method 2 When wiring more than Three TR TREC series dampers to a zone use a 24v AC SPNO relay Field Supplied Method 3 When using a ST series damper t...

Страница 8: ...er energizes the compressor s and indoor blower This is indicated by the corresponding Y and G LEDs illumi nating Dampers for the zones not calling for cool are powered closed and the dampers for the...

Страница 9: ...only the zone dampers 1 1 Zone damper 1 When energized power zone damper 1 closed 2 2 Zone damper 2 When energized power zone damper 2 closed 3 3 Zone damper 3 When energized power zone damper 3 clos...

Страница 10: ...ops out to the purge cycle the HVAC outputs are terminated and the initial zone damper remains open for a 4 minute delay with the other dampers closing The HVAC system fan control allows the blower to...

Страница 11: ...r terminals This transfor mer powers only the zone dampers 1 1 Zone damper 1 When energized power zone damper 1 closed 2 2 Zone damper 2 When energized power zone damper 2 closed 3 3 Zone damper 3 Whe...

Страница 12: ...LEDs on are closed B ON OFF ON OFF ON 1 Y1 Cool 1st stage cool blower on Dampers with LEDs on are closed B ON ON ON OFF ON 1 Y2 Cool 2st stage cool blower on Dampers with LEDs on are closed ON OFF OF...

Страница 13: ...e at which that heat pump is no longer ef cient When the outside temperature is less than Balance Point setpoint and there is a call for heat Y1 and Y2 air temperature and cycle the unit off when the...

Страница 14: ...ir sensor Optional for Fossil Fuel applications Sensor installation 1 Install the OAS outside of the building away from direct sun exposure and above the snow line 2 Run the sensor cable to the Digitr...

Страница 15: ...nd and one straight end for easy installation A hat section supports a synchronous 24v AC 60Hz 12VA motor and terminal board The motor is designed for continuous full stall operation Special winding a...

Страница 16: ...0 STMPD12 STMPD14 STMPD16 STMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 1000 110 250 160 320 750 850 1070 925 540 700 600 725 015...

Страница 17: ...off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RECTANGULAR MEDIUM PRESSURE Z...

Страница 18: ...200 1500 1800 2100 390 590 800 1000 1250 1500 1750 310 490 650 850 1000 1200 1400 250 390 510 650 6 8 10 12 14 16 18 20 8 10 12 14 16 18 20 22 24 HEIGHT IN INCHES WIDTH IN INCHES 2 1 2 5 H W 2 1 4 Par...

Страница 19: ...ough to bypass the excess air This will control static pressure and noise at the diffusers Zonex Systems offers two types of bypass dampers Barome tric and electronic Each is available in round or rec...

Страница 20: ...e certain the damper shaft is horizontal c Loosen counter weight with allen wrench d Loosen lever arm from damper shaft and allow to hang straight down e Fully close damper by grabbing damper shaft on...

Страница 21: ...ould be 16 Never undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STBP damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND B...

Страница 22: ...0667 12000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 2200...

Страница 23: ...and controller are powered by a dedicated 24vac 40VA transformer 3 Do not install the bypass damper outside 4 Locate the Integrated Pressure Control IPC and air tube on the bypass damper 5 Drill hole...

Страница 24: ...ranslates to inches of W C Note 1 To open all dampers it may be necessary to remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats This will modulate damper...

Страница 25: ...pplicable b Set to Cool mode c Set fan switch to AUTO mode d Set cool setpoint 4 below room temperature 14 At System Controller a Verify Y1 G and PWR LEDs are on If not cycle System Controller power s...

Страница 26: ...ip heat After 8 minutes of continuous heat call if LAT is less than 90 then W2 will energize and auxiliary heat is on 8 Turn off all thermostats except zone 1 9 At zone 1 thermostat a Verify power swi...

Страница 27: ...wiring shorted 0V dc on and w LAT installed Heating calls short cycle LAT open 5V dc on and w LAT installed Replace LAT LAT wiring open 5V dc on and w LAT installed Repair LAT wiring LAT SENSOR TEMPE...

Страница 28: ...714 898 9963 Fax 714 898 6802 PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time speci cations or designs without notice and without incurring obligations Part DT4...

Отзывы: