background image

STATUS LEDs

     Y1         Y2         G          W1       W2       PWR      DPR          MODE          FUNCTION

   OFF      OFF       OFF      OFF      OFF      OFF      OFF               Off             Power off
   OFF      OFF       OFF      OFF      OFF       ON       OFF              On             Power on, blower off, all zone dampers open

      OFF      OFF       ON       OFF      OFF       ON           0               Vent            Blower on, compressor(s) off, all zone dampers open
      OFF      OFF       OFF      OFF      OFF       ON           1               Purge          Blower off, compressor(s) off, Dampers with LEDs on are closed
       ON      OFF        ON      OFF       OFF       ON           1            Y1 Cool         1st stage cool, blower on. Dampers with LEDs on are closed
      ON        ON        ON      OFF       OFF       ON           1            Y2 Cool          2st stage cool, blower on. Dampers with LEDs on are closed

      OFF      OFF      OFF      ON       OFF       ON           1            W1 Heat         1st stage heat, blower on. Dampers with LEDs on are closed

      OFF      OFF      OFF      ON       ON       ON           1            W2 Heat          2st stage heat, blower on. Dampers with LEDs on are closed

      OFF      OFF       ON        ON      ON       SFL           1               Cap cut out       Blower on, all compressors off. Dampers w/LED on are closed
       ON       OFF       ON        OFF      OFF       FFL           1               Stage 2 cut out       Compressor 1 on, blower on, damper w/LED on are closed

STATUS LED LEGEND

FFL

 = Fast Flash 

SFL

 = Slow Flash 

1

 = One or more damper LEDs on 

0

 = All dampers LEDs are off

6

SYSTEM CONTROLLER – GAS/ELECTRIC 

OPERATION

SYSTEM CONTROLLER - GAS/ELECTRIC

The DigiTract Controller is the heart of the DigiTract zoning 

system. It is an auto changeover, home run system with built 

in staging and capacity controller. The function of the 

system controller is to receive calls from the zone thermo-

stats, operate the HVAC system in either heat or cool mode 

and close the damper(s) of zones not calling for the operat-

ing mode. The mode of operation is determined by the first 

call received. If the thermostats are calling for opposite 

modes, a changeover sequence will start. Based on the 

Time Setpoint setting, a changeover will occur after time 

delay. Changeover will continue as long as there are oppos-

ing calls. The built in Capacity Contoller maintains the 

supply air temperature within an operation range to prevent 

freeze ups and overheating.  

For Heat Pumps, the System Controller will also control the 

auxiliary heat.

The Digitract 4 controller is not to be subjected to tempera-

tures below 33°F or above 160°F. The controllers must not be 

installed in atmospheres that could create condensation or 

corrosion. Warranty is voided on controllers that fail due to 

moisture or corrosion evidenced on the circuit board. The 

operating voltage range on the Digitract 4 controllers is 24 

vac to 28 vac.

NOTE: For Heat Pumps systems using gas electric inputs

 (“O” or “B” reversing valve circuits) use gas electric setup.

The System Controller will initially run in the mode request-

ed by the first calling zone thermostat.

Cool mode

 - When running in the cool mode, the System 

Controller energizes the compressor(s) and indoor blower. 

This is indicated by the corresponding Y and G LEDs illumi-

nating. Dampers for the zones not calling for cool are 

powered closed and the dampers for the zones calling for 

cool are left open. This is indicated by the DPR LEDs. If the 

DPR LED is illuminated on the damper terminal strip and the 

damper terminal board, the corresponding damper is 

closed. The system will continue to run in the cool mode 

until all calls are satisfied or changeover occurs. When all 

calls are satisfied or prior to changeover, the system will go 

into a purge mode.

Heat mode

 - When running in the heat mode, the System 

Controller energizes the heat stage(s), indicated by the W 

LEDs illuminating. Dampers for the zones not calling for 

heat are powered closed and the dampers for the zones 

calling for heat are left open. This is indicated by the DPR 

LEDs. If the DPR LED is illuminated on the damper terminal 

strip and the damper terminal board, the corresponding 

damper is closed. The system will continue to run in the heat 

mode  until  all  calls  are  satisfied  or  changeover  occurs. 

When  all  calls  are  satisfied  or  prior  to  changeover,  the 

system will go into a purge mode.

Changeover

 - 

While the system is operating in one 

mode, and the System Controller recives a call for the oppo-

site mode, the System Controller will continue to run in the 

current mode until the changeover TIME limit has been 

reached,  or  all  current  calls  have  been  satisfied.  Now  the 

System Controller will go into a purge mode for 4 minutes, 

then changeover to the new mode.

Purge mode

 - Purge mode is initiated after the last calling 

zone  is  satisfied,  or  when  the  controller  goes  into  a  forced 

changeover. All HVAC output LEDs on the controller go off 

during this cycle. When the last calling zone thermostat 

satisfies, the Digitract controller goes into a 4 minute purge 

cycle. During this time delay all outputs to the HVAC system 

and dampers are terminated. All dampers go to a full open 

position and the HVAC system fan delay runs the blower for a 

time. This time delay with no control outputs allows the supply 

duct to return to ambient temperature before the next call is 

initiated.

When the controller goes into a force mode changeover, and 

the initial call drops out to the purge cycle, the HVAC outputs 

are terminated, and the initial zone damper remains open for 

a 4 minute delay with the other dampers closing. The HVAC 

system fan control allows the blower to run for a time, and the 

initial calling zone supply duct returns to ambient tempera-

ture.

Ventilation 

- When no zones are calling, all zone dampers 

are open. During this time, if any thermostat has the fan switch 

ON then the indoor blower is energized (G made to R)  and G 

LED is on. This provides ventilation to all zones.

Содержание DigiTract 4

Страница 1: ...DigiTract 4 Two Stage Heat Cool Comfort Control System Installation Guide Part DT4UMAN Zoning Systems That s all we do Rev July 2018...

Страница 2: ...il Fuel Application 11 CAPACITY CONTROLLERS Gas Electric 11 Heat Pump 11 Capacity Control and Staging 11 ZONE DAMPERS Round 13 14 Rectangular 15 16 Installation Notes 17 BYPASS DAMPERS Barometric 17 1...

Страница 3: ...le the HVAC system off if the leaving air gets too hot in heat mode or too cold in cool mode For heat pumps this input is also used to control the auxiliary heat See Capacity Controller section on pag...

Страница 4: ...ade TREC W x H up to 5 SP Medium Pressure Dampers Round STMPD size up to 1 75 SP Rectangular STMRTD W x H up to 1 SP Heavy Duty Rectangular STCD W x H up to 1 75 SP BYPASS DAMPERS DAMPER TRANSFORMER 5...

Страница 5: ...nsor in the supply air stream as far from the coil heat exchanger as possible before the bypass takeoff Do not locate the LAT downstream of the bypass takeoff Connect W2 and Y2 of the DT4U output to u...

Страница 6: ...bypass takeoff Connect W2 from the controller to the units electric heat stage terminal designation Thermostats Heat Pump thermostats 1C 2H Note Some combination thermostats do not have an E terminal...

Страница 7: ...ring one to three TR TREC series dampers to a zone Method 2 When wiring more than Three TR TREC series dampers to a zone use a 24v AC SPNO relay Field Supplied Method 3 When using a ST series damper t...

Страница 8: ...er energizes the compressor s and indoor blower This is indicated by the corresponding Y and G LEDs illumi nating Dampers for the zones not calling for cool are powered closed and the dampers for the...

Страница 9: ...only the zone dampers 1 1 Zone damper 1 When energized power zone damper 1 closed 2 2 Zone damper 2 When energized power zone damper 2 closed 3 3 Zone damper 3 When energized power zone damper 3 clos...

Страница 10: ...ops out to the purge cycle the HVAC outputs are terminated and the initial zone damper remains open for a 4 minute delay with the other dampers closing The HVAC system fan control allows the blower to...

Страница 11: ...r terminals This transfor mer powers only the zone dampers 1 1 Zone damper 1 When energized power zone damper 1 closed 2 2 Zone damper 2 When energized power zone damper 2 closed 3 3 Zone damper 3 Whe...

Страница 12: ...LEDs on are closed B ON OFF ON OFF ON 1 Y1 Cool 1st stage cool blower on Dampers with LEDs on are closed B ON ON ON OFF ON 1 Y2 Cool 2st stage cool blower on Dampers with LEDs on are closed ON OFF OF...

Страница 13: ...e at which that heat pump is no longer ef cient When the outside temperature is less than Balance Point setpoint and there is a call for heat Y1 and Y2 air temperature and cycle the unit off when the...

Страница 14: ...ir sensor Optional for Fossil Fuel applications Sensor installation 1 Install the OAS outside of the building away from direct sun exposure and above the snow line 2 Run the sensor cable to the Digitr...

Страница 15: ...nd and one straight end for easy installation A hat section supports a synchronous 24v AC 60Hz 12VA motor and terminal board The motor is designed for continuous full stall operation Special winding a...

Страница 16: ...0 STMPD12 STMPD14 STMPD16 STMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 1000 110 250 160 320 750 850 1070 925 540 700 600 725 015...

Страница 17: ...off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RECTANGULAR MEDIUM PRESSURE Z...

Страница 18: ...200 1500 1800 2100 390 590 800 1000 1250 1500 1750 310 490 650 850 1000 1200 1400 250 390 510 650 6 8 10 12 14 16 18 20 8 10 12 14 16 18 20 22 24 HEIGHT IN INCHES WIDTH IN INCHES 2 1 2 5 H W 2 1 4 Par...

Страница 19: ...ough to bypass the excess air This will control static pressure and noise at the diffusers Zonex Systems offers two types of bypass dampers Barome tric and electronic Each is available in round or rec...

Страница 20: ...e certain the damper shaft is horizontal c Loosen counter weight with allen wrench d Loosen lever arm from damper shaft and allow to hang straight down e Fully close damper by grabbing damper shaft on...

Страница 21: ...ould be 16 Never undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STBP damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND B...

Страница 22: ...0667 12000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 2200...

Страница 23: ...and controller are powered by a dedicated 24vac 40VA transformer 3 Do not install the bypass damper outside 4 Locate the Integrated Pressure Control IPC and air tube on the bypass damper 5 Drill hole...

Страница 24: ...ranslates to inches of W C Note 1 To open all dampers it may be necessary to remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats This will modulate damper...

Страница 25: ...pplicable b Set to Cool mode c Set fan switch to AUTO mode d Set cool setpoint 4 below room temperature 14 At System Controller a Verify Y1 G and PWR LEDs are on If not cycle System Controller power s...

Страница 26: ...ip heat After 8 minutes of continuous heat call if LAT is less than 90 then W2 will energize and auxiliary heat is on 8 Turn off all thermostats except zone 1 9 At zone 1 thermostat a Verify power swi...

Страница 27: ...wiring shorted 0V dc on and w LAT installed Heating calls short cycle LAT open 5V dc on and w LAT installed Replace LAT LAT wiring open 5V dc on and w LAT installed Repair LAT wiring LAT SENSOR TEMPE...

Страница 28: ...714 898 9963 Fax 714 898 6802 PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time speci cations or designs without notice and without incurring obligations Part DT4...

Отзывы: