ELECTRONIC BYPASS DAMPERS 

Bypass dampers are used to provide constant air delivery through the air handling unit.  This is done by bypassing excess air 

from the supply duct back to the return duct.  As a zone is satis

ed, its zone damper closes.  When this happens, the bypass 

damper opens just enough to bypass the excess air.  This will control static pressure and noise at the diffusers. 

 

The Electronic Bypass Damper is used on any size system over 5 tons.  The damper can be round  (STBP)  or rectangular 

(STCDBP)  with integrated static pressure control; and multiple dampers can be slaved together.   

SIZING ELECTRONIC BYPASS DAMPERS 

The bypass damper is to be sized for the total system CFM 

@  1500 FPM.  System  CFM  should  be  calculated  at  400 

CFM per ton. 

Example :  A 5-ton system is rated at 2000 CFM (5x400 = 

2000).  When calculated at 1500 FPM, the bypass damper 

should be 16”.  Never undersize the bypass damper. 

ROUND BYPASS DAMPER SELECTION 

The  Zonex  Systems  STBP   damper  is  used  for  round 

bypass  applications.    When  you  know  the  bypass  CFM 

requirements,  use  the  ROUND  BYPASS  SELECTION 

TABLE to con

fir

m the round damper size. 

NOTE:

  Multiple round dampers can be slaved from one 

static pressure control to provide the correct capacity.  One 

large  rectangular  bypass  damper  may  be  used  instead  of 

multiple round dampers.  See below. 

RECTANGULAR BYPASS DAMPER SELECTION 

The  Zonex  Systems  STCDBP  WxH   damper  is  used  for 

rectangular  bypass  applications.    These  dampers  are  also 

sized  for  the  total  system  CFM  rated  at  1500  FPM.  

Multiple  dampers  can  be  slaved  from  a  single  static 

pressure control. 

 

 

 

 

 

Diameter CFM

8”

560

10”

900

12”

1250

14”

1700

16”

2200

18”

2600

PART # SIZE

D

L

W

STBP08

8

8” 10” 11”

STBP10

10

10” 12” 13”

ST

BP

12

12

12” 14” 15”

STBP14

14

14” 16” 17”

STBP16

16

16” 18” 19”

STBP18

18

18” 20” 21”

ROUND BYPASS SELECTION TABLE

RECTANGULAR BYPASS DAMPERS

SELECT FROM 8 x 8 thru 48 x 48

 

D

L

W

H

D

4”

W

48” MAXIMUM WIDTH

BYPASS DAMPERS - ELECTRONIC

Содержание DigiTract 4

Страница 1: ...DigiTract 4 Two Stage Heat Cool Comfort Control System Installation Guide Part DT4UMAN Zoning Systems That s all we do Rev July 2018...

Страница 2: ...il Fuel Application 11 CAPACITY CONTROLLERS Gas Electric 11 Heat Pump 11 Capacity Control and Staging 11 ZONE DAMPERS Round 13 14 Rectangular 15 16 Installation Notes 17 BYPASS DAMPERS Barometric 17 1...

Страница 3: ...le the HVAC system off if the leaving air gets too hot in heat mode or too cold in cool mode For heat pumps this input is also used to control the auxiliary heat See Capacity Controller section on pag...

Страница 4: ...ade TREC W x H up to 5 SP Medium Pressure Dampers Round STMPD size up to 1 75 SP Rectangular STMRTD W x H up to 1 SP Heavy Duty Rectangular STCD W x H up to 1 75 SP BYPASS DAMPERS DAMPER TRANSFORMER 5...

Страница 5: ...nsor in the supply air stream as far from the coil heat exchanger as possible before the bypass takeoff Do not locate the LAT downstream of the bypass takeoff Connect W2 and Y2 of the DT4U output to u...

Страница 6: ...bypass takeoff Connect W2 from the controller to the units electric heat stage terminal designation Thermostats Heat Pump thermostats 1C 2H Note Some combination thermostats do not have an E terminal...

Страница 7: ...ring one to three TR TREC series dampers to a zone Method 2 When wiring more than Three TR TREC series dampers to a zone use a 24v AC SPNO relay Field Supplied Method 3 When using a ST series damper t...

Страница 8: ...er energizes the compressor s and indoor blower This is indicated by the corresponding Y and G LEDs illumi nating Dampers for the zones not calling for cool are powered closed and the dampers for the...

Страница 9: ...only the zone dampers 1 1 Zone damper 1 When energized power zone damper 1 closed 2 2 Zone damper 2 When energized power zone damper 2 closed 3 3 Zone damper 3 When energized power zone damper 3 clos...

Страница 10: ...ops out to the purge cycle the HVAC outputs are terminated and the initial zone damper remains open for a 4 minute delay with the other dampers closing The HVAC system fan control allows the blower to...

Страница 11: ...r terminals This transfor mer powers only the zone dampers 1 1 Zone damper 1 When energized power zone damper 1 closed 2 2 Zone damper 2 When energized power zone damper 2 closed 3 3 Zone damper 3 Whe...

Страница 12: ...LEDs on are closed B ON OFF ON OFF ON 1 Y1 Cool 1st stage cool blower on Dampers with LEDs on are closed B ON ON ON OFF ON 1 Y2 Cool 2st stage cool blower on Dampers with LEDs on are closed ON OFF OF...

Страница 13: ...e at which that heat pump is no longer ef cient When the outside temperature is less than Balance Point setpoint and there is a call for heat Y1 and Y2 air temperature and cycle the unit off when the...

Страница 14: ...ir sensor Optional for Fossil Fuel applications Sensor installation 1 Install the OAS outside of the building away from direct sun exposure and above the snow line 2 Run the sensor cable to the Digitr...

Страница 15: ...nd and one straight end for easy installation A hat section supports a synchronous 24v AC 60Hz 12VA motor and terminal board The motor is designed for continuous full stall operation Special winding a...

Страница 16: ...0 STMPD12 STMPD14 STMPD16 STMPD18 6 8 10 12 14 16 18 Nominal CFM Duct Diameter Duct Velocity FPM Damper P WC 10 12 14 16 6 8 7 9 410 660 1450 1000 110 250 160 320 750 850 1070 925 540 700 600 725 015...

Страница 17: ...off when the damper is opening or in the full opened position Since this is a spring open damper in the event of power failure the damper fails to the full open position RECTANGULAR MEDIUM PRESSURE Z...

Страница 18: ...200 1500 1800 2100 390 590 800 1000 1250 1500 1750 310 490 650 850 1000 1200 1400 250 390 510 650 6 8 10 12 14 16 18 20 8 10 12 14 16 18 20 22 24 HEIGHT IN INCHES WIDTH IN INCHES 2 1 2 5 H W 2 1 4 Par...

Страница 19: ...ough to bypass the excess air This will control static pressure and noise at the diffusers Zonex Systems offers two types of bypass dampers Barome tric and electronic Each is available in round or rec...

Страница 20: ...e certain the damper shaft is horizontal c Loosen counter weight with allen wrench d Loosen lever arm from damper shaft and allow to hang straight down e Fully close damper by grabbing damper shaft on...

Страница 21: ...ould be 16 Never undersize the bypass damper ROUND BYPASS DAMPER SELECTION The Zonex Systems STBP damper is used for round bypass applications When you know the bypass CFM requirements use the ROUND B...

Страница 22: ...0667 12000 13333 14667 16000 36 9000 10500 12000 13500 15000 16500 18000 40 10000 11667 13333 15000 16667 18333 20000 44 11000 12833 14667 16500 18333 20167 22000 48 12000 14000 16000 18000 20000 2200...

Страница 23: ...and controller are powered by a dedicated 24vac 40VA transformer 3 Do not install the bypass damper outside 4 Locate the Integrated Pressure Control IPC and air tube on the bypass damper 5 Drill hole...

Страница 24: ...ranslates to inches of W C Note 1 To open all dampers it may be necessary to remove Y outputs to unit on the zone control board and to make full cool calls on all thermostats This will modulate damper...

Страница 25: ...pplicable b Set to Cool mode c Set fan switch to AUTO mode d Set cool setpoint 4 below room temperature 14 At System Controller a Verify Y1 G and PWR LEDs are on If not cycle System Controller power s...

Страница 26: ...ip heat After 8 minutes of continuous heat call if LAT is less than 90 then W2 will energize and auxiliary heat is on 8 Turn off all thermostats except zone 1 9 At zone 1 thermostat a Verify power swi...

Страница 27: ...wiring shorted 0V dc on and w LAT installed Heating calls short cycle LAT open 5V dc on and w LAT installed Replace LAT LAT wiring open 5V dc on and w LAT installed Repair LAT wiring LAT SENSOR TEMPE...

Страница 28: ...714 898 9963 Fax 714 898 6802 PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time speci cations or designs without notice and without incurring obligations Part DT4...

Отзывы: