W-O/B: First stage heat. When energized (W1 made to R), 

energizes first-stage heat or reversing valve for HP.

G:

Blower. When energized (G made to R), 
energizes the indoor blower.

Y:

First stage cool. When energized (Y1 made to R), 
energizes first stage cooling.

R:

HVAC unit 24V power. Powers the DIGI3U board 
and zone thermostats.

C:

HVAC unit 24V power return.

B. Thermostat Terminals

– Connects up to three zone ther-

mostats. 

W:

Heat call.  When energized, requests the DIGI3U 
to run in heat mode.

W2: Used in HP STAT 1 only to energize emergency heat. 

Not used in G/E.

R:

HVAC unit 24V power.  

Y:

Compressor input.

G:

Blower Fan – When energized (G made to R), requests
the DIGI3U to turn on the indoor blower fan.

C:

HVAC unit 24V common.

C. Damper Terminals

– Connects dampers for up to three zones and

damper power supply.
TR1/TR2: 24V AC transformer terminals. This transformer powers 

only the zone dampers and size properly.

1 1: Zone damper 1. 

When energized, powers zone damper 1 closed.

2 2: Zone damper 2.  

When energized, powers zone damper 2 closed.

3 3: Zone damper 3.  

When energized, powers zone damper 3 closed.

D. Damper Status LEDs

– On when corresponding zone damper is

being powered closed.

E. Microcontroller

– Responsible for activation and control of the

unit based upon thermostat input. Occasionally software upgrades
may become available. If so, the DIGI3U software can be field
upgraded by changing this microcontroller.

F. HVAC System Status LEDs

– Indicates what the DIGI3U is

energizing on the HVAC system.
Y:

Compressor, yellow.

G:

Blower, green. On when the indoor blower is energized.

W-O/B: Heat or reversing valve, red. On when first stage heat or 

reversing valve is energized.

W2:

Heat, red. Emergency heat is energized for heat pump operation.

PWR: Power, orange. On when power at R and C and the Power 

Switch is on. Flashing when in Capacity Control cut out mode.
See Status Lights section for further information.

G. Power Switch

– When OFF, power from the HVAC unit transformer is

disconnected from the DIGI3U and thermostats. When ON, power from
the HVAC unit transformer is supplied to the DIGI3U and the zone
thermostats.

H. SS 

– Terminals for capacity control.

I. JP1 O/B Jumper 

– For heat pump application only. Place in O or B

position for proper reversing valve action.

J. JP2 HP/GE Jumper 

– Place on proper pins for desired application.

SYSTEM CONTROLLER – UNIVERSAL GE/HP

1

1

2

2

3

3

TR1

TR2

 o   o   o   o     

R  Y O/B W2 G  C

  R   Y  W   G   C

   R   Y   W   G   C

S

R

Y

G

W-O/B

W2

C

O       O       O

LED

Y

W-O/B 

W2

G

DPR1

DPR2

DPR3

GE

HP

B

POWER
SWITCH

DIGI3U

STAT 2

STAT 3

STAT 1

O

PWR

CONTROL CHIP

   O

  O

LED

S

A

B

J

G

H

I

F

E

D

C

JP2

JP1

W

COMPONENTS

A. HVAC Unit/LAT Terminals

– Connects to HVAC unit. 

Содержание DIGI3U

Страница 1: ...DIGI3U Three Zone Universal Controller for Gas Electric or Heat Pump Applications Installation Guide Part D3MAN Zoning Systems That s all we do 3 Zone Controller for the RNC Market October 2011...

Страница 2: ...the controller The resistor is used in place of the LAT for 2 zone Gas Electric installations that do not have a bypass When bypass is used the optional LAT leaving air sensor must be connected in pla...

Страница 3: ...s LAT capacity control is not applied a field supplied freeze protection and high limit device must be installed to protect equipment This should only be applied to designs in which both zones are app...

Страница 4: ...2 W WIRING GAS ELECTRIC DIGI3U S S terminals for LAT capacity control If not applied leave 1k ohm resistor in place and field supplied high and low limits should be added Transformer damper transforme...

Страница 5: ...ition for unit energizing reversing valve for cool place in B position for unit energizing reversing valve in heat JP2 Heat Pump or Gas Electric jumper is used to configure controller Factory set for...

Страница 6: ...12va per damper TR SERIES DAMPER M M 1 2 3 3 TR1 TR2 2 1 DIGI3U SYSTEM CONTROLLER ONE TO THREE TR SERIES DAMPERS Fused 24V 40VA Transformer Transformer and 2 amp fuse TR SERIES DAMPER M M 1 2 3 3 TR1...

Страница 7: ...puts to furnace and dampers After all calls are satisfied controller will initiate a 3 minute purge During this time controller will not allow any calls for heat or cool Cool Operation without LAT If...

Страница 8: ...n place to function in this mode Changeover Gas Electric While controller is operating in heat or cool if another thermostat places a call for the opposite mode a changeover sequence will begin The co...

Страница 9: ...ter all calls for cooling are satisfied Y G and all damper LEDs will go off and controller will initiate a 3 minute purge During this time controller will not allow a call for heat or cool Heat Mode w...

Страница 10: ...energized PWR Power LED orange On when DTHP4A is powered Flashing during capacity control cutout DPR Damper status LED red One per damper On when damper is closed Emergency Heat Operation To put the...

Страница 11: ...control of the unit based upon thermostat input Occasionally software upgrades may become available If so the DIGI3U software can be field upgraded by changing this microcontroller F HVAC System Statu...

Страница 12: ...on supports a synchronous 24V AC 60Hz 12VA motor and termi nal board The motor is designed for continuous full stall operation Special winding and heavy duty gearing provide for long motor life and ea...

Страница 13: ...or to bypass more than 2000 CFM use the electronic bypass RECTANGULAR ROUND BAROMETRIC BYPASS BYPASS DAMPERS BAROMETRIC AIRFLOW 1 2 4 3 1 Damper Shaft 2 Lock Nut 3 Lever Arm 4 Counter Weight BAROMETR...

Страница 14: ...Damper incorrectly wired Correct damper wiring Emergency Heat does not Work STAT 1 must make heat call in Emergency Heat Verify heat call STAT 2 and STAT 3 can make Emergency heat call after STAT 1 V...

Страница 15: ...on and blower fan is running 15 Verify air is being delivered to zone 1 and not to any of the other zones 16 At zone 1 verify air is coming out of the register diffuser 17 At next zone a Verify air is...

Страница 16: ...9963 Fax 714 898 6802 Visit our Web Site http www zonexsystems com PATENTED PRODUCT Zonex Systems reserves the right to discontinue or change at any time specifications or designs without notice and w...

Отзывы: