SYSTEM CONTROLLER OPERATIONS – DIGI3U

GAS/ELECTRIC OPERATION

Gas Electric Operation Cool with LAT: 

Remove the factory installed

1K ohm resistor and install LAT sensor wired to SS terminals of DIGI3U
controller.

When any thermostat calls for cool, Y and G LEDs will illuminate, indi-
cating outputs to unit are energized and unit is running. Damper LEDs
for non-calling zones are illuminated, indicating that dampers are
closed. When all calls are satisfied, Y, G and damper LEDs will go off, de-
energizing unit and opening all dampers.

When the leaving air temperature drops below 45°, Y will de-energize
and G will remain on for 3 minutes. After 3 minutes, if the leaving air
temperature has risen above 45° cutout limit, Y will energize and
cooling will restart.   

After all calls are satisfied, a 3-minute purge will be initiated by controller.
During this time the controller will not allow any calls for heat or cool.

Heat Operation with LAT: 

When any thermostat places a call for

heat, the W LED will illuminate and output to furnace will be energized.
Damper LEDs for non-calling zones will illuminate, indicating that
dampers are powered closed.

If leaving air rises above 145°, W will de-energize and gas valve/electric
heat will shut off.  After 3 minutes, if leaving air temperature is less than
145°, then W LED will illuminate and heat will restart.  When all calls
for heat are satisfied, W and damper LEDs will go off, de-energizing out-
puts to furnace and dampers.  

After all calls are satisfied, controller will initiate a 3-minute purge.
During this time controller will not allow any calls for heat or cool.

Cool Operation without LAT: 

If not using the LAT capacity control, a

field supplied high and low limit device will need to be applied to sys-
tem to protect equipment.  

When any thermostat places a call for cooling, the power LED will flash
and all dampers will remain open. After 3 minutes, Y and G LEDs will
illuminate and energize condensing unit and fan. Damper LEDs for non-
calling zones will illuminate, indicating that dampers are closed.  

After initial call for cooling or low limit cutout, all cooling calls will
initiate a 3-minute fan purge cycle. When all calls are satisfied, Y, G
and damper LEDs will go off and controller will initiate a 3-minute
time delay. During this time delay, controller will not allow a call for heat
or cool.

Heat Operation without LAT:

When a call for Heat is sent to the

controller, a 3-minute time delay is initiated. This time delay is indicated
by a flashing power LED.

When the 3-minute time delay is complete, the power LED is illuminated
constant and the controller will then energize the Heat output including
the corresponding damper signals.

A field supplied high and low limit device is required to provide HVAC
system protection.

Configure the DIGI3U for GE operation.

Jumper JP2 must be placed in GE position on controller.  This will allow controller to control gas fur-

naces and electric heat air handlers and cooling condensers.

FOR APPLICATIONS

WITHOUT

LAT CAPACITY CONTROLLER

FOR APPLICATIONS USING THE LAT SENSOR

Содержание DIGI3U

Страница 1: ...DIGI3U Three Zone Universal Controller for Gas Electric or Heat Pump Applications Installation Guide Part D3MAN Zoning Systems That s all we do 3 Zone Controller for the RNC Market October 2011...

Страница 2: ...the controller The resistor is used in place of the LAT for 2 zone Gas Electric installations that do not have a bypass When bypass is used the optional LAT leaving air sensor must be connected in pla...

Страница 3: ...s LAT capacity control is not applied a field supplied freeze protection and high limit device must be installed to protect equipment This should only be applied to designs in which both zones are app...

Страница 4: ...2 W WIRING GAS ELECTRIC DIGI3U S S terminals for LAT capacity control If not applied leave 1k ohm resistor in place and field supplied high and low limits should be added Transformer damper transforme...

Страница 5: ...ition for unit energizing reversing valve for cool place in B position for unit energizing reversing valve in heat JP2 Heat Pump or Gas Electric jumper is used to configure controller Factory set for...

Страница 6: ...12va per damper TR SERIES DAMPER M M 1 2 3 3 TR1 TR2 2 1 DIGI3U SYSTEM CONTROLLER ONE TO THREE TR SERIES DAMPERS Fused 24V 40VA Transformer Transformer and 2 amp fuse TR SERIES DAMPER M M 1 2 3 3 TR1...

Страница 7: ...puts to furnace and dampers After all calls are satisfied controller will initiate a 3 minute purge During this time controller will not allow any calls for heat or cool Cool Operation without LAT If...

Страница 8: ...n place to function in this mode Changeover Gas Electric While controller is operating in heat or cool if another thermostat places a call for the opposite mode a changeover sequence will begin The co...

Страница 9: ...ter all calls for cooling are satisfied Y G and all damper LEDs will go off and controller will initiate a 3 minute purge During this time controller will not allow a call for heat or cool Heat Mode w...

Страница 10: ...energized PWR Power LED orange On when DTHP4A is powered Flashing during capacity control cutout DPR Damper status LED red One per damper On when damper is closed Emergency Heat Operation To put the...

Страница 11: ...control of the unit based upon thermostat input Occasionally software upgrades may become available If so the DIGI3U software can be field upgraded by changing this microcontroller F HVAC System Statu...

Страница 12: ...on supports a synchronous 24V AC 60Hz 12VA motor and termi nal board The motor is designed for continuous full stall operation Special winding and heavy duty gearing provide for long motor life and ea...

Страница 13: ...or to bypass more than 2000 CFM use the electronic bypass RECTANGULAR ROUND BAROMETRIC BYPASS BYPASS DAMPERS BAROMETRIC AIRFLOW 1 2 4 3 1 Damper Shaft 2 Lock Nut 3 Lever Arm 4 Counter Weight BAROMETR...

Страница 14: ...Damper incorrectly wired Correct damper wiring Emergency Heat does not Work STAT 1 must make heat call in Emergency Heat Verify heat call STAT 2 and STAT 3 can make Emergency heat call after STAT 1 V...