14
1. If no heating system, go to step 12.
2. At System Controller:
a. Turn power switch on.
b. Verify at this time the PWR light is on only.
3. Turn off all thermostats except zone 1.
4. At zone 1 thermostat
a. Set power switch on.
b. Set to Heat mode.
c. Set Fan switch Auto mode.
d. Set Heat set point several degrees above room temperature.
5. At System Controller:
a. Verify W, G and PWR lights are on.
b. Verify DPR1 light is off and DPR2 and 3 LEDs are on.
6. At HVAC unit, verify furnace is on and blower fan is running. If the G
light on System Controller is not on, the blower fan is controlled by
the furnace; and there will be a delay before it turns on.
7. At zone 1, verify air is coming out of register/diffuser.
8. At next zone:
a. Verify air is not coming out of register/diffuser
b. At thermostat:
b-1 Set power switch on.
b-2 Set to Heat mode.
b-3 Set Fan switch to Auto mode
b-4 Set heat setpoint several degrees above room temperature.
c. Verify air is now coming out the register/diffuser.
9. At the previous zone, turn thermostat off and verify air stops coming
out of the register/diffuser.
10. Repeat steps 8 and 9 for the last zone 3.
11. Turn off all thermostats except zone 1.
12. At zone 1 thermostat:
a. Set power switch on.
b. Set to Cool mode
c. Set Fan switch to Auto mode.
d. Set cool setpoint several degrees below room temperature.
13. At System Controller:
a. Verify Y, G and PWR lights are on. If not, cycle the System
Controller power switch OFF and then ON; then recheck.
b. Verify DPR 1 light is off and DPR 2 through DPR 3 lights are on.
14. At HVAC unit, verify air conditioner is on and blower fan is running.
15. Verify air is being delivered to zone 1 and not to any of the other
zones.
16. At zone 1, verify air is coming out of the register/diffuser.
17. At next zone:
a. Verify air is not coming out of the register/diffuser.
b. At thermostat:
b-1 Set power switch on.
b-2 Set to Cool mode.
b-3 Set Fan switch to Auto mode.
b-4 Set cool setpoint several degrees below room temperature.
c. Verify air is now coming out of the register/diffuser.
18. At previous zone, turn thermostat off and verify that air stops
coming out of the diffuser.
19. Repeat steps 17 and 18 for the remaining 2 zones.
Test Complete.
STARTUP TEST, GAS/ELECTRIC MODE DIGI3U
(Verify Jumper JP2 is in the G/E mode on the Controller)
2. Make a Heat call from STAT 1 only.
3. Verify DPR1 LED is off and DPR2 & DPR3 LEDs are illuminated.
4. Check dampers for proper open and close position.
5. Verify controller energizes the compressor and indoor fan.
Y and G LEDs are illuminated for “O” mode.
Y, G and O/B LEDs are illuminated for “B” mode.
6. Verify after 4 minutes of run time, Y, G, and W2 LEDs are illuminated
and the auxiliary heat is energized on the controller.
7. Repeat this process for zones 2 and 3.
8. Make a Cool call on STAT1.
9. Verify DPR1 LED is off and DPR2 & DPR3 LEDs are illuminated.
10. Check dampers for proper open and close position.
11. Verify controller energizes the compressor, rev valve (“O” mode)
and indoor fan.
Y, G and O/B LEDs are illuminated for “O” mode.
Y and G LEDs are illuminated for “B” mode.
12. Repeat this process for zones 2 and 3.
STARTUP TEST, HEAT PUMP MODE DIGI3U
(Verify jumper JP2 is in the HP position on the controller and the LAT sensor is connected to the S S terminals.)
1. Temporarily remove the LAT from the supply air stream.
13. Re-install the LAT into the supply air stream.