background image

7

© Copyright 2022 Zoeller

®

 Co. All rights reserved.

Operation

GENERAL

Zoeller pumps are lubricated and tested at the factory prior to shipment and 

require minimum pre-start-up maintenance.
Maximum liquid temperature of a continuous operating pump liquid for this model 

pump must not exceed 104 °F (40 °C). For longest service life all pumps should be totally 

submerged on long pumping cycles. Maximum submerged depth is 50'.
These units are not designed to handle liquids other than water or sewage. If 

pump is used in water contaminated with heavy, viscous, or abrasive materials, 

the warranty will be voided.

NAMEPLATE DATA

The nameplate, located on the top of pump, indicates specific information about 

the construction of the pump. The model number, date code, and serial number  

information should be recorded on the front page in the “Owner’s Information” 

section of this manual.

   

 

If the pump is repaired in the field, its explosion

   

 

proof rating may be voided.

SHORT TERM STORAGE

If pump is to be stored, the following is advised:
•  Store pump inside whenever possible or cover with some type of protective covering.

•  Tape or seal in plastic bag the terminal ends of wire leads.

•  Pump is to be stored in an upright position. Seal leaks that occur in storage 

to a pump laying on its side will not be repaired under warranty.

•  The impeller should be rotated every six months in order to keep the seals 

lubricated and not develop a permanent set.

If panel is to be stored, the following is advised:
•  Store the panel inside whenever possible and leave in the shipping box.

•  All openings shall be sealed.

•  Store in an upright position.

•  Do not stack anything on top of panel.

START-UP PROCEDURE

Before placing the equipment into operation the following should be checked:
•  Correct pump rotation (3 Phase units only).

•  Clean pit.

•  Panel dry, securely installed and properly sealed.

•  Floats positioned properly.

•  Discharge valves open.

•  3/16” vent hole drilled in pipe between check valve and pump.

Once the above has been verified proceed with the following checks:

•  Pump power cables properly connected to panel.

•  Float cables properly connected in an intrinsically safe panel.

•  Conduit connections to panel are properly sealed.

•  Thermal overload adjustments made in the panel.

•  After installing the pump into the containment area, with adequate submer-

gence, open the discharge valve fully. Start the unit using manual controls. 

If flow is appreciably less than rated performance, pump may be air locked. 

To expel trapped air, jog the unit several times, using the manual controls.

•  Have a qualified electrician take voltage and current measurements on the 

black wire of single phase or all three power wires of three phase with the 

pump running. Record these readings in the space provided in the 

“Owner’s 

Information” 

section on page 1 of this manual for future reference. 

After the preoperational functional test has been completed, system is ready for 

operation. Zoeller requires completing a Start-up Report (ZM1074) whenever a 

system is started for the first time or after a system has had a significant change 

take place (i.e. pump replacement, overhaul, etc..). A copy of the Start-up Report 

should remain with the system for future reference.

ADJUSTMENT PROCEDURE

Pumps:  No adjustments are required other than assuring correct rotation.

Panels:  The thermal overloads in the panel  must be set to the F.L.A. rating 

on the pump nameplate (or refer to pump data sheet).

Floats:  

Refer to the system drawing for desired location of each float function.

Valves:  Discharge valves should be placed in the fully open position. Systems 

should not be operated for extended periods of time with the discharge 

valves partially closed due to damaging the valve.

SHUTDOWN PROCEDURES

If a system is shutdown for more than six months, the following is recommended:
Pumps:  If pit is to remain dry, then the pump can remain in the pit. With the 

pump in the pit, it should be operated for five minutes once every three 

months. If the pit is to remain wet, the pump should be removed and 

stored as noted above.

Panels:  The panel should have all openings sealed to prevent moisture and dust 

from entering the enclosure. Prior to restarting system, the panel should 

be inspected for presence of moisture and any loose connections.

Valves:  Consult the valve/actuator supplier for information concerning these 

systems components.

Maintenance

  Repair and service must be performed by a firm approved by 

Zoeller Company. The firm must be certified to work on explosion proof motors 

if motor housing, adapter or cord cap is repaired. Contact Zoeller Technical 

Service Department regarding warranty issues.

    

 

If repair to the motor housing, adapter or cord cap is

disassembled or repaired by a firm not certified to work on explosion proof mo

-

tors, the explosion proof rating is void and the cCSAus approval tag 

MUST BE 

REMOVED FROM THE PUMP.SAFETY PROCEDURES.

SAFETY PROCEDURES

 For your protection, always disconnect pump and panel from its 

power source before handling.

 Never enter the basin until it has been properly vented and 

tested. Any person entering a basin should be wearing a harness with safety rope 

extending to the surface so that they can be pulled out in case of asphyxiation. 

Sewage water gives off methane and hydrogen sulfide gases, both of which 

can be highly poisonous.
Installation and checking of electrical circuits and hardware should be performed 

by a qualified electrician.

Pump is never to be lifted by power cord.

 Unit must be flushed and disinfected, inside and out, prior to 

servicing.

GENERAL SYSTEM INSPECTION

Before the system is placed into operation, a system Start-up Report should be 

conducted by a qualified technician.

 Wiring and grounding must be in accordance with the national 

electrical code and all applicable local codes and ordinances.

LUBRICATION PROCEDURES

No lubrication is required.

If pumps are to be stored for more than six months, refer to short term storage 

procedure in the Operation section.

PREVENTIVE MAINTENANCE

Preventive maintenance is recommended to ensure a long service life from the 

product. Provided is a suggested maintenance schedule.

Every month:

•  Check for proper and unobstructed float operation.

•  Listen for proper check valve operation.

•  Duplex Units - Check for even operating times. Uneven times indicate a  

  defective unit, float switch or control.

•  Inspect the panel for any presence of moisture in enclosure, loose connections, and 

general component condition. check out location and  condition of float switches.

Every year:

•  In addition to the monthly checks, the basin should be inspected and cleaned. 

Any defective components should be replaced. Inspect and remove any sand, 

debris, or mud present in the pump basin assembly.

Every two years:

 •  Inspect power cables for damage or wear. Replace immediately if damage or 

wear is detected, 

•  Inspect impeller for damage or wear. Replace as required by a Zoeller  

 

  Authorized Service Station.

DOUBLE SEAL PUMPS

•  Double seal pumps offer extra protection. During every inspection of the unit, 

check the control panel seal failure for a warning. Whenever the seal leak is 

activated, indicating that the lower seal has failed, the pump should be removed 

and serviced in order to avoid damage to the motor.

Содержание EX6220

Страница 1: ...w the steps and procedures listed on ZM1074 for a proper start up and warranty protection Many items contained within when followed correctly will not only ensure a long and problem free life for the pump but also save time and money during installation Should further assistance be necessary please call our Technical Service Department at 1 800 928 PUMP 7867 Safety Instructions CAUTION TO AVOID SE...

Страница 2: ...ctured at Zoeller Engineered Product s option provided however that by so doing we shall not be obligated to replace an entire assembly the entire mechanism or the complete unit Major components and controls not manufacturedbythecompanyarecoveredbytheoriginalmanufacturerwarranty in lieu of this warranty This warranty shall not apply to any product or part of a product including pumps controls lift...

Страница 3: ...oper grounding to help protect you against the possibility of electrical shock 3 Makecertainthatthecontrolboxis within thereach ofthepump s power supply cord DO NOT USE AN EXTENSION CORD Extension cords that are too long or too light do not deliver sufficient voltage to the pump motor But more important they could present a safety hazard if the insulation were to become damaged or the connection e...

Страница 4: ... valve is installed drill a 3 16 diameter hole in the discharge pipe below the check valve even with the top of the pump NOTE The hole must be below the basin cover and cleaned periodically Water stream will be visible from this hole during pump run periods Also a vent hole is drilled in the pump housing Be sure that this hole is cleared during any servicing 7 Vent gases and odors to the atmospher...

Страница 5: ... sensors are normally closed and mounted adjacent to the motor windings If internal temperatures exceed a maximum limit the pump will deac tivate when the red and orange wires are connected in series to the control coil of the motor starter circuit The pump is able to restart once the motor cools down Continued deactivation of this circuit requires the attention from maintenance personnel 2 The bl...

Страница 6: ...ecified at time of initial pump order and are not available for field installation Sensor wire colors are as shown TYPICAL 3 PHASE WIRING DIAGRAM RefertoSensorandControlPanelsectionsonpage5 ZEPA0036 ZEPA0038E Single Phase Installation All single phase models require start capacitor run capacitor and relay in the circuit to start and operate properly These components can be purchased separately or ...

Страница 7: ...t function Valves Dischargevalvesshouldbeplacedinthefullyopenposition Systems shouldnotbeoperatedforextendedperiodsoftimewiththedischarge valves partially closed due to damaging the valve SHUTDOWN PROCEDURES If a system is shutdown for more than six months the following is recommended Pumps If pit is to remain dry then the pump can remain in the pit With the pumpinthepit itshouldbeoperatedforfivem...

Страница 8: ...rect Voltage Unbalanced power source Incorrect motor rotation Negative or low head Excessive water temperature Impeller or seal mechanically bound Defective capacitor or relay Motor shorted Lost one line in a Three Phase unit C Pumps starts and stops too often Check valve stuck open Level controls out of adjustment Temperature sensor tripping Thermal overload switch out of adjustment or defective ...

Отзывы: