background image

6

© Copyright 2022 Zoeller

®

 Co. All rights reserved.

T3 

T2 

T1 

L3 

L2 

L1 

POWER CABLE 

(N/C) 

THERMAL SENSOR 

330K OHMS RESISTANCE

SEAL FAILURE PROBES

3 PHASE MOTOR 

PANEL. 

INDUCTION CIRCUIT IN THE CONTROL 

LEADS MUST BE CONNECTED TO  

SEAL FAILURE MOISTURE SENSOR 

STARTER COIL 

CONNECTED IN SERIES WITH 

RECOMMENDED THERMAL SENSOR 

3ø VAC 

SENSOR CABLE 

BLACK 

WHITE 

ORANGE 

RED 

GREEN 

230 VAC 1ø

FROM CONTACTOR

RELAY

START

1

2

5

BLACK

CAPACITORS

START

RUN CAPACITOR

WHITE

BLACK

RED

WHITE

MAIN

PUMP

START

4

5

1

L1

L2

C-1

C-2

C-3

GREEN

Three Phase Installation

Three phase pumps are nonautomatic. To operate automatically, a control panel 

is required. Follow the instructions provided with the panel to wire the system.

Before installing a pump, check the pump rotation to insure that wiring has been 

connected properly to power source, and that the green lead of power cord (See 

wiring diagram), is connected to a valid ground, Momentarily energize the pump, 

observing the directions of kick back due to starting torque. Rotation is correct 

if kick back is in the opposite direction of rotation arrow on the pump casing. 

If rotation is not correct, switching of any two power leads other than ground, 

should provide the proper rotation.

The above wiring diagram shows a typical hookup for a 230 volt, 3 phase pump, 

two variable level float switches, and a magnetic starter.  It is not intended that 

this diagram cover all applications.  See wiring diagram supplied with specific 

electrical controllers and panels.

NOTE 1:

 Optional sensor cable includes 5 leads; 2 leads for thermal sensor, 2 leads 

for moisture sensor, and a green ground lead. If one sensor only is specified, both 

sensors are provided and must be hooked up to validate warranty. The sensors 

must be specified at time of initial pump order and are not available for field 

installation. Sensor wire colors are as shown.

TYPICAL 3-PHASE  WIRING DIAGRAM

Refer to Sensor and Control Panel sections on page 5.

ZEPA0036

ZEPA0038E

Single Phase Installation

All single phase models require start capacitor, run capacitor and relay in the circuit to start and operate properly. These components can be purchased separately 

or prewired in Zoeller control panel. For components purchased separately used the diagram for installation and hookup.

Single phase models are nonautomatic. To operate automatically a control panel  must be added to the power circuit. Follow the instructions provided with the panel.

ZEPA0041

ZEPA0040

WIRING DIAGRAM

1

2

5

L2

T2

T1

L1

RELAY

START

MOTOR

BLACK

START CAPACITORS

WHITE

230 VAC 1Ø

RUN CAPACITOR

4

WHITE

RED

BLACK

PUMP

START

5

MAIN

1

C-1

C-2

C-3

GREEN

(460-552MF, 125 VOLTS)

(30MF, 440 VOLTS)

COMPONENT LAYOUT

WIRING DIAGRAM 

ZEPA0043

COMPONENT LAYOUT

ZEPA0042

 5 BHP MODEL X6220

7-1/2 BHP MODEL X6221

C-4

MAIN

START

PUMP

RED

BLACK

C-3

RUN CAPACITORS

C-1

C-2

START

CAPACITORS

BLACK

5

2

1

5 1

4

START

RELAY

FROM CONTACTOR

230 VAC 1ø

WHITE

L1

L2

WHITE

GREEN

WHITE

START CAPACITORS

RUN CAPACITORS

RELAY

START

C-1

C-2

C-4

C-3

4

230 VAC 1Ø

BLACK

RED

WHITE

PUMP

MAIN

START

BLACK

L1

T1

T2

L2

1

5

2

5

1

GREEN

(20MF, 370 VOLTS)

(590-708MF, 110-125 VOLTS)

OL

OL

OL

STARTER

MAGNETIC

IS REQUIRED

CIRCUIT TRANSFORMER

3 PHASE A CONTROL

NOTE - FOR 460 VOLT

FLOAT SWITCH

"OFF"

FLOAT SWITCH

"ON"

L3

L2

L1

2

3

MOTOR

PUMP

T3

T2

T1

OL

M

230 VOLTS, 60 HZ., 3 PH

TYPICAL WIRING DIAGRAM

NOTES:

1. “

◊” DENOTES A TERMINAL ON    

 

MOTOR START RELAY ASSEMBLY.

2. “

Ο

” DENOTES MOTOR TERMINAL. 

3.  MOTOR EQUIPPED WITH MOISTURE  

 

PROBES AND THERMAL SENSORS.  

 

REFER TO 3 PHASE WIRING DIA 

GRAM    

BELOW.

NOTES:

1. “

◊” DENOTES A TERMINAL ON    

 

MOTOR  START RELAY ASSEMBLY.

2. “

Ο

” DENOTES MOTOR TERMINAL. 

3.  MOTOR  EQUIPPED WITH MOISTURE  

 

PROBES AND THERMAL SENSORS.  

 

REFER TO 3 PHASE WIRING DIAGRAM  

 BELOW.

Содержание EX6220

Страница 1: ...w the steps and procedures listed on ZM1074 for a proper start up and warranty protection Many items contained within when followed correctly will not only ensure a long and problem free life for the pump but also save time and money during installation Should further assistance be necessary please call our Technical Service Department at 1 800 928 PUMP 7867 Safety Instructions CAUTION TO AVOID SE...

Страница 2: ...ctured at Zoeller Engineered Product s option provided however that by so doing we shall not be obligated to replace an entire assembly the entire mechanism or the complete unit Major components and controls not manufacturedbythecompanyarecoveredbytheoriginalmanufacturerwarranty in lieu of this warranty This warranty shall not apply to any product or part of a product including pumps controls lift...

Страница 3: ...oper grounding to help protect you against the possibility of electrical shock 3 Makecertainthatthecontrolboxis within thereach ofthepump s power supply cord DO NOT USE AN EXTENSION CORD Extension cords that are too long or too light do not deliver sufficient voltage to the pump motor But more important they could present a safety hazard if the insulation were to become damaged or the connection e...

Страница 4: ... valve is installed drill a 3 16 diameter hole in the discharge pipe below the check valve even with the top of the pump NOTE The hole must be below the basin cover and cleaned periodically Water stream will be visible from this hole during pump run periods Also a vent hole is drilled in the pump housing Be sure that this hole is cleared during any servicing 7 Vent gases and odors to the atmospher...

Страница 5: ... sensors are normally closed and mounted adjacent to the motor windings If internal temperatures exceed a maximum limit the pump will deac tivate when the red and orange wires are connected in series to the control coil of the motor starter circuit The pump is able to restart once the motor cools down Continued deactivation of this circuit requires the attention from maintenance personnel 2 The bl...

Страница 6: ...ecified at time of initial pump order and are not available for field installation Sensor wire colors are as shown TYPICAL 3 PHASE WIRING DIAGRAM RefertoSensorandControlPanelsectionsonpage5 ZEPA0036 ZEPA0038E Single Phase Installation All single phase models require start capacitor run capacitor and relay in the circuit to start and operate properly These components can be purchased separately or ...

Страница 7: ...t function Valves Dischargevalvesshouldbeplacedinthefullyopenposition Systems shouldnotbeoperatedforextendedperiodsoftimewiththedischarge valves partially closed due to damaging the valve SHUTDOWN PROCEDURES If a system is shutdown for more than six months the following is recommended Pumps If pit is to remain dry then the pump can remain in the pit With the pumpinthepit itshouldbeoperatedforfivem...

Страница 8: ...rect Voltage Unbalanced power source Incorrect motor rotation Negative or low head Excessive water temperature Impeller or seal mechanically bound Defective capacitor or relay Motor shorted Lost one line in a Three Phase unit C Pumps starts and stops too often Check valve stuck open Level controls out of adjustment Temperature sensor tripping Thermal overload switch out of adjustment or defective ...

Отзывы: