background image

15

❹ Maintenance

  

4.1 I  Winterizing

• 

 Winterizing is vital to prevent the condenser breaking due to freezing. This is not covered by 

the warranty.

• 

To avoid damaging the equipment with condensation, do not fully cover it.

• 

Switch off the device by pressing and holding   for 2 seconds and disconnect it or switch off the electricity supply, 

• 

Close the water input and output valves and make sure that there is no water circulating in the heat pump, 

• 

Drain the water from the condenser (risk of freezing) by unscrewing the water input and output connectors on the 

back of the heat pump, 

• 

In the case of full winterizing for the pool (complete shutdown of the filtration system, bleed the filtration circuit 

or even pool drainage): tighten the two connectors by one turn to prevent any foreign bodies from getting into the 

condenser, 

• 

In the case of winterizing for the heat pump only (shutdown of the heating only, the filtration keeps running): to not 

tighten the connectors but add 2 caps (provided) on the condenser's water inputs and outputs.

• 

We recommend that you put the aired winterizing micro cover on the heat pump.

  

4.2 I  Maintenance

• 

It is recommended that the device be general servicing at least on a yearly basis to ensure 

proper operation, maintain performance levels and prevent some potential failures. These 

operations are carried out at the user's expense, by a technician.

4.2.1 Safety instructions for appliances containing R32 refrigerant

Area check

• 

Before starting work on systems containing flammable refrigerants, safety checks must be carried out to guarantee a 

minimal ignition risk.

Work procedure

• 

The work must be carried out according to a controlled procedure in order to reduce the risks of releasing a flammable 

gas or vapour while working.

General work area

• 

All maintenance staff and other personnel working in the surrounding area must be made aware of the work carried 

out. Work conducted in enclosed areas must be avoided.

Check for the presence of refrigerant

• 

The area must be analysed using a suitable refrigerant detector before and during work so that the technician is 

informed of the presence of a potentially toxic or flammable atmosphere. Check that the leak detection equipment 

used is suitable for use with all refrigerants concerned, i.e. that it does not cause a spark, is correctly isolated or is 

entirely safe.

Check for the presence of a fire extinguisher

• 

If work must be carried out on the cooling equipment or any part associated therewith at a certain temperature, 

suitable  fire  extinguishing  means  must  be  within  reach.  Place  a  dry  chemical  fire  extinguisher  or  CO<g-

1776156949>2</g-1776156949> fire extinguisher near the work area.

No source of ignition

• 

No person carrying out work on a cooling system involving exposing the piping may use any ignition source, which 

could create a fire or explosion risk. All possible ignition sources, in particular cigarettes, must not enter within a 

sufficient perimeter of the installation, repair, removal or disposal site, in the event that refrigerant could be released 

into the surrounding space. Before starting the work, the area around the equipment must be examined to check for 

all fire or ignition risks. “No smoking” signs must be displayed.

Area ventilation

• 

Before accessing the unit in any manner whatsoever with the intention of performing any maintenance task, check 

that the area is open and well-ventilated. Suitable ventilation must be provided throughout the maintenance task to 

allow any refrigerant that could be released into the atmosphere to be safely dispersed.

Refrigeration equipment check

• 

The  manufacturer’s  recommendations  in  terms  of  care  and  maintenance  must  always  be  complied  with.  When 

replacing electric components, check that components used are of the same type and category as those recommended/

EN

Содержание Z200

Страница 1: ...H0548500_REVF 2021 02 More documents on www zodiac com Z200 Defrost Z200 PI20 Defrost PI20 Instructions for installation and use English Heat pump Translation of the original instructions in French EN...

Страница 2: ...sed for any purpose other than that for which it was designed This appliance is not intended for use by individuals including children with impaired physical sensorial or mental abilities or persons l...

Страница 3: ...on the appliance with wet hands or if the appliance is wet Before connecting the appliance to the source of supply ensure that the terminal block or supply socket to which the appliance will be conne...

Страница 4: ...designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated s...

Страница 5: ...rinciple 12 3 2 User interface presentation 12 3 3 I Operating 13 3 4 I User functions 14 Maintenance 15 4 1 I Winterizing 15 4 2 I Maintenance 15 Troubleshooting 18 5 1 I Device behaviour 18 5 2 I Er...

Страница 6: ...A Z200 PI20 B Joint x2 C Screw in connector x2 D 40 adaptation x2 E 50 reduction x2 F Condensation evacuation kit 15 G Winterizing cap x2 H Winterizing cover Heating priority I Remote control J PAC N...

Страница 7: ...cable section mm 3x2 5 3G2 5 Proof pressure bar 6 Service pressure bar 1 5 Max Discharge Suction Pressure bar 42 1 2 Max high pressure low pressure side pressure bar 42 1 2 Head loss mCE 1 1 5 1 1 5...

Страница 8: ...on valve and user interface Ventilator Technical access door Pool water intake Pool water output Evaporator Grommet for heating priority cable run Location for drilling for remote control cable run de...

Страница 9: ...und The device must not be installed In a closed and unventilated room In a location subject to high winds With the blowing towards a permanent or temporary obstacle window wall hedge awning etc less...

Страница 10: ...o make it easier to work on the device water entry valve by pass valve water exit valve water entry adjustment valve optional water exit adjustment valve optional water treatment minimum distance To e...

Страница 11: ...hnical specifications with a 30 mA dedicated differential circuit breaker circuit breaker or switch at the head of the line The electricity supply must correspond to the voltage indicated on the devic...

Страница 12: ...p power contactor coil filtration timer power contactor tripolar or bipolar for the filtration system pump motor separate cable for the heating priority function heat pump terminal see wiring diagram...

Страница 13: ...ing range sufficient to heat Cover the basin with a sheet bubble canopy canvas etc to prevent heat loss Take advantage of a period with mild outdoor temperatures on average 10 C at night your heat pum...

Страница 14: ...adually so that the filter pressure is increased by 150g 0 150 bars Open valves A C and D fully then valve E by half the air which has built up in the heat pump condenser and the filtration circuit wi...

Страница 15: ...the setpoint temperature is displayed fixed To read the water temperature it is imperative that the filtration is in operation and that the water flow indicator is fixed 3 4 2 Locking unlocking the k...

Страница 16: ...nd other personnel working in the surrounding area must be made aware of the work carried out Work conducted in enclosed areas must be avoided Check for the presence of refrigerant The area must be an...

Страница 17: ...nd intensity for the equipment being used Typically safe components are the only types on which work can be carried out in the presence of a flammable atmosphere when live The test appliance must fall...

Страница 18: ...ll a manifold in order to be able to remove the refrigerant from various locations within the system 6 Make sure that the cylinder is located on the scales before starting recovery operations 7 Start...

Страница 19: ...your heat pump cannot manage to deice its evaporator it will stop itself this means that the outdoor temperature is too low below 5 C for standard models 5 C for Defrost models The device is not worki...

Страница 20: ...temperature too high 32 C maximum Wait until the temperature falls Flow controller blocked Check the flow controller Water condenser scaled up or blocked Clean the water condenser Outside temperature...

Страница 21: ...p relay Earth KM4 Complementary relay C1 Compressor condenser M1 Compressor C2 Ventilator condenser M2 Ventilator CD Flow controller SD1 Water temperature sensor E1 High pressure switch SD2 Air temper...

Страница 22: ...KM4 Complementary relay C1 Compressor condenser M1 Compressor C2 Ventilator condenser M2 Ventilator CD Flow controller SD1 Water temperature sensor HP High pressure switch SD2 Air temperature sensor...

Страница 23: ...rty of their respective owners Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Pour plus d informations enregistrement produit et support client For more in...

Отзывы: