11 

 

Display 

Designation 

Cause 

Solution 

Reset 

 

 

(alternating with 

Water flow-
rate sensor 

fault 

(ST4) 

Sensor defective or 

disconnected 

(terminals 4-5 of the 

plate B1) 

Replace or 

reconnect the 

sensor 

Switch the power 

supply off and then 

back on again or 

automatic if the 

fault disappears. 

 

Refrigerant 

circuit 

pressure 

fault 

High or low pressure 

fault tripped while 

fault “ESt4”   

Cancel the fault 

“ESt4” 

Automatic 

 (if less than 4 

“dbP”  or  “dHP” 

faults per hour) or 

press 

 if “ESt4” 

flashes 

 

Defrost cycle 

time 

exceeded 

Defrost cycle too 

long (> 1 hour): 

- excessive ice 

formation on the 

evaporator (low 

temperature with  

evaporator  blocked 

or no ventilation 

during the defrost 

cycle). 

- incorrect ST3 

sensor value (see 

§2.1.3) 

Cancel the fault, 

then check that the 

defrost cycle 

operates correctly. 

In case of repeated 

fault: contact an 

approved 

technician to check 

for the presence of 

an adequate 

quantity of 

refrigerant gas in 

the appliance. 

Switch the power 

supply off or press 

 if “dtd” flashes 

(case after stand-by 

following regulator 

start up by pressing 

 

EEPROM 

fault 

(micro-

processor) 

The parameters data 

in the controller chips 

are damaged 

Change the 

regulator  

Switch the power 

supply off and then 

back on again 

 

2.1.3 Display the values of sensors ST1-ST2-ST3 and ST4  

 

 enter into the parameter: press 3 seconds on 

 => 

 

 press on 

 

 to view the value, and return by pressing again on 

 display 

 => 

 => 

 by pressing 

 quit: press 3 seconds on 

 or automatic after a time period of 70 seconds without touching the 

regulator. 

 

 

 

2.2 Malfunctions of the appliance 

2.2.1 The appliance does not work 

 

Causes 

Verification / solution 

No display 

Check the supply voltage and the fuse 

The pool temperature is above the temperature 
setpoint. 

Increase the temperature setpoint. 

A message is on the screen. 

Check the meaning of message §2.1 

 
 
 
 
 

- the

 

 

key is disabled in this menu.

Содержание PF 6M-8M-11M-13M-15M

Страница 1: ...Installation instructions PF 6M 8M 11M 13M 15M Heat pump for swimming pools R f N C 014 A EN Ver 12 2010...

Страница 2: ...0 2 1 Statuses and faults of the regulator 10 2 1 1 Statuses 10 2 1 2 Faults 10 2 1 3 Display the values of sensors ST1 ST2 ST3 and ST4 11 2 2 Malfunctions of the appliance 11 2 2 1 The appliance does...

Страница 3: ...ing If the appliance has been tipped over express reserves in writing to the transporter Elimination or shunting of one of the safety leads automatically to the cancellation of the guarantee as for th...

Страница 4: ...1 with an ambient air of 15 C and a pool water of 26 C humidity 70 in compliance with the French NF 414 standard unit protection class IP 24 refrigerant gas R410A refrigerant charge see product name...

Страница 5: ...4 3 Installing the appliance installed the 5 anti vibration studs supplied see 1 1 2 put onto a stable solid concrete slab type and level surface preserve from risks of flooding due to condensation p...

Страница 6: ...5 1 1 Condensation drainage Caution your appliance can drain several litres of water per day and you are strongly advised to connect the drainage to the sewer connect a 18 interior pipe not supplied...

Страница 7: ...ing function Objective to keep the pool water at the required temperature independent of the filtering time the heat pump triggers the operation of the filter every hour the pool temperature required...

Страница 8: ...ing output terminals 16 17 heat pump B1 regulation electronic card see placing dimensions and description in the appendix Never power the filter pump motor directly through terminals 16 17 located on...

Страница 9: ...pressure to 150 g 0 150 bar open valves 2 3 and 4 completely then half open valve 5 see 1 4 4 the air accumulated in the heat pump condenser unit and in the filter circuit is then evacuated If valves...

Страница 10: ...by mode by pressing and holding for 3 seconds on then appears on the screen for 5 seconds before a small red dot appears open the valve 1 close valves 2 and 3 and open valves 4 and 5 if present ensur...

Страница 11: ...ect the sensor Switch the power supply off or press if dSA flashes Defrost sensor fault ST3 Sensor defective or disconnected terminals 4 6 of the plate B1 Replace or reconnect the sensor Switch the po...

Страница 12: ...an approved technician to check for the presence of an adequate quantity of refrigerant gas in the appliance Switch the power supply off or press if dtd flashes case after stand by following regulator...

Страница 13: ...if the outside temperature is lower than 12 C The evaporator is fouled Clean the evaporator 2 2 4 The heat pump trips out or attempts to start itself from time to time Causes Verification solution Th...

Страница 14: ...es Shipping expenses for the repaired or replaced Products delivered to the client will be borne by us excluding any labour costs travel and or accommodation expenses incurred as the result of repairs...

Страница 15: ...l installer excluding installation via retrofit kit for a period of two years starting from the date mentioned on the invoice as issued by our Client to the end User Users are also required to have an...

Страница 16: ...itrogen brazing etc all brazing work must be carried out by a qualified brazer welder in the case of units filled with R410A refer to the specific indications in the installation instructions this uni...

Страница 17: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 18: ...1 Electric diagram PF 6M 8M...

Страница 19: ...2 PF 11M 13M 15M...

Страница 20: ...Water flow adjusting probe NTC Regulation electronic card Pump control Fuse 3 15A T 250V 5 20 Fan capacitor Compressor capacitor Fan connector Fan Compressor Soft starter Black Blue Brown Grey White...

Страница 21: ...English Base Front pannel cowl Technical door Back pannel Post Grid Regulator 1 water pool inlet 1 water pool outlet Evaporator Stuffing box B1 regulation electronic card Fuse F1 Supply terminal boar...

Страница 22: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 23: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 24: ...023 49180 Saint Barth l my d Anjou cedex France www zodiac poolcare com Innovative pool products and services Produits et services innovants pour la piscine Votre installateur Your installer Plaque si...

Отзывы: