2. Troubleshooting 

2.1 Statuses and faults of the regulator 

2.1.1 Statuses  

 

  

 

Display 

Cause 

Solution 

Reset 

 

1 - filtration pump off 

2 – water flow in the 

appliance not enough, 

3- flow switch defective 

or disconnected.  

1- clean the filter and start the filtering

 

2- check the adjustment of the valves

3- test the continuity of the flow switch 

and the connection of terminals 7 and 

8 of card B1  

Automatic 
after timer 

 

(alternating with 

Outside temperature too 
low (ST2 < to + 5 °C) for 

probe reading, see 

§2.1.3 

Wait for the outside temperature to 

increase naturally 

Automatic 

 

2.1.2 Faults 

 

 

 

Display 

Designation 

Cause 

Solution 

Reset 

 

Control 

sensor fault 

(ST1) 

Sensor defective or 

disconnected 

(terminals 2-3 of the 

plate B1) 

Replace or reconnect 

the sensor 

Switch the power 

supply off or press 

 if “dSr” flashes 

 

 

Antifreeze 

sensor fault 

(ST2) 

Sensor defective or 

disconnected 

(terminals 1-3 of the 

plate B1) 

Replace or reconnect 

the sensor 

Switch the power 

supply off or press 

 if  “dSA” flashes 

 

Defrost 

sensor fault 

(ST3) 

Sensor defective or 

disconnected 

(terminals 4-6 of the 

plate B1) 

Replace or reconnect 

the sensor 

Switch the power 

supply off or press 

 if  “dSd” flashes 

 

Refrigerant 

circuit low 

pressure 

fault 

Insufficient 

refrigerant (if the fault 

persists after 

clearing) 

Contact an approved 

technician to detect 

the leak and top up 

the refrigerant 

Automatic 

 (if less than 4 “dbP”  

or  “dHP” faults per 

hour) or press 

 if  

“dbP” flashes 

 

Refrigerant 

circuit high 

pressure 

fault 

1- emulsion of air 

and water passed in 

the appliance, 

2- bad water flow, 

3- exchanger fouled  

4- flow controller 

jammed shut  

1 - check the pool 

hydraulic circuit  

2 - check the flow  

rate controler 

3 - if the fault persists, 

contact an approved 

technician 

Automatic 

 (if less than 4 “dbP”  

or  “dHP” faults per 

hour) or press 

 if  

“dHP” flashes 

 
 
 
 
 
 

The indicator 

 

 

 

remains on for 2 minutes after one of the messages indicated above. 

 

The fault  

alternating with the pool water temperature, does not block operation 

of the heat pump. 

The indicator  

 

 

remains on for 2 minutes after the message 

 or 

 

Содержание PF 6M-8M-11M-13M-15M

Страница 1: ...Installation instructions PF 6M 8M 11M 13M 15M Heat pump for swimming pools R f N C 014 A EN Ver 12 2010...

Страница 2: ...0 2 1 Statuses and faults of the regulator 10 2 1 1 Statuses 10 2 1 2 Faults 10 2 1 3 Display the values of sensors ST1 ST2 ST3 and ST4 11 2 2 Malfunctions of the appliance 11 2 2 1 The appliance does...

Страница 3: ...ing If the appliance has been tipped over express reserves in writing to the transporter Elimination or shunting of one of the safety leads automatically to the cancellation of the guarantee as for th...

Страница 4: ...1 with an ambient air of 15 C and a pool water of 26 C humidity 70 in compliance with the French NF 414 standard unit protection class IP 24 refrigerant gas R410A refrigerant charge see product name...

Страница 5: ...4 3 Installing the appliance installed the 5 anti vibration studs supplied see 1 1 2 put onto a stable solid concrete slab type and level surface preserve from risks of flooding due to condensation p...

Страница 6: ...5 1 1 Condensation drainage Caution your appliance can drain several litres of water per day and you are strongly advised to connect the drainage to the sewer connect a 18 interior pipe not supplied...

Страница 7: ...ing function Objective to keep the pool water at the required temperature independent of the filtering time the heat pump triggers the operation of the filter every hour the pool temperature required...

Страница 8: ...ing output terminals 16 17 heat pump B1 regulation electronic card see placing dimensions and description in the appendix Never power the filter pump motor directly through terminals 16 17 located on...

Страница 9: ...pressure to 150 g 0 150 bar open valves 2 3 and 4 completely then half open valve 5 see 1 4 4 the air accumulated in the heat pump condenser unit and in the filter circuit is then evacuated If valves...

Страница 10: ...by mode by pressing and holding for 3 seconds on then appears on the screen for 5 seconds before a small red dot appears open the valve 1 close valves 2 and 3 and open valves 4 and 5 if present ensur...

Страница 11: ...ect the sensor Switch the power supply off or press if dSA flashes Defrost sensor fault ST3 Sensor defective or disconnected terminals 4 6 of the plate B1 Replace or reconnect the sensor Switch the po...

Страница 12: ...an approved technician to check for the presence of an adequate quantity of refrigerant gas in the appliance Switch the power supply off or press if dtd flashes case after stand by following regulator...

Страница 13: ...if the outside temperature is lower than 12 C The evaporator is fouled Clean the evaporator 2 2 4 The heat pump trips out or attempts to start itself from time to time Causes Verification solution Th...

Страница 14: ...es Shipping expenses for the repaired or replaced Products delivered to the client will be borne by us excluding any labour costs travel and or accommodation expenses incurred as the result of repairs...

Страница 15: ...l installer excluding installation via retrofit kit for a period of two years starting from the date mentioned on the invoice as issued by our Client to the end User Users are also required to have an...

Страница 16: ...itrogen brazing etc all brazing work must be carried out by a qualified brazer welder in the case of units filled with R410A refer to the specific indications in the installation instructions this uni...

Страница 17: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 18: ...1 Electric diagram PF 6M 8M...

Страница 19: ...2 PF 11M 13M 15M...

Страница 20: ...Water flow adjusting probe NTC Regulation electronic card Pump control Fuse 3 15A T 250V 5 20 Fan capacitor Compressor capacitor Fan connector Fan Compressor Soft starter Black Blue Brown Grey White...

Страница 21: ...English Base Front pannel cowl Technical door Back pannel Post Grid Regulator 1 water pool inlet 1 water pool outlet Evaporator Stuffing box B1 regulation electronic card Fuse F1 Supply terminal boar...

Страница 22: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 23: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 24: ...023 49180 Saint Barth l my d Anjou cedex France www zodiac poolcare com Innovative pool products and services Produits et services innovants pour la piscine Votre installateur Your installer Plaque si...

Отзывы: