background image

4

it is recommended good practice that all refrigerants are removed safely.

• When transferring refrigerant into cylinders, ensure that only appropriate 

refrigerant recovery cylinders are employed. Ensure that the correct number of 

cylinders for holding the total system charge is available. All cylinders to be used 

are designated for the recovered refrigerant and labelled for that refrigerant (i.e. 

special cylinders for the recovery of refrigerant). Cylinders shall be complete with 

pressure-relief valve and associated shut-off valves in good working order. Empty 

recovery cylinders are evacuated and. if possible. cooled before recovery occurs.

• 

The recovery equipment shall be in good working order with a set of instructions 

concerning the equipment that is at hand and shall be suitable for the recovery 

of all appropriate refrigerants including, when applicable, flammable refrigerants. 

In  addition,  a  set  of  calibrated  weighing  scales  shall  be  available  and  in  good 

working order. Hoses shall be complete with leak-free disconnect couplings and in 

good condition. Before using the recovery machine, check that it is in satisfactory 

working order, has been properly maintained and that any associated electrical 

components are sealed to prevent ignition in the event of a refrigerant release. 

Consult manufacturer it in doubt.

• The recovered refrigerant shall be returned to the refrigerant supplier in the 

correct recovery cylinder, and the relevant waste transfer note arranged. Do not 

mix refrigerants in recovery units and especially not in cylinders.

• If compressors or compressor oils are to be removed. ensure that they have been 

evacuated to an acceptable level to make certain that flammable refrigerant does 

not remain within the lubricant. The evacuation process shall be carried out prior to 

returning the compressor to the suppliers. Only electric heating to the compressor 

body shall be employed to accelerate this process. When all is drained from a 

system, it shall be carried out safely.

Recycling

This  symbol  is  required  by  European  Community  Directive  2012/19/UE  on  WEEE  (Waste  Electrical  and 

Electronic  Equipment)  and  means  that  your  appliance  must  not  be  thrown  into  a  normal  bin.  It  will  be 

selectively collected for the purpose of reuse, recycling or transformation. Any substances it may contain 

which are potentially dangerous to the environment shall be eliminated or neutralised. Request information 

on recycling procedures from your retailer.

EN

Содержание iAquaLink Z400iQ

Страница 1: ...H0638700_REVI 2021 06 More documents on www zodiac com Z400iQ EN Instructions for installation and use English Heat pump Translation of the original instructions in French...

Страница 2: ......

Страница 3: ...r instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance This appliance can be used by ch...

Страница 4: ...orm maintenance or servicing operations on the appliance with wet hands or if the appliance is wet Before connecting the appliance to the source of supply ensure that the terminal block or supply sock...

Страница 5: ...h the consequent risk of severe burns TROUBLESHOOTING All soldering work must be carried out by a someone qualified to do so Replacement pipes must always be made of copper in compliance with standard...

Страница 6: ...working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer it in doubt The reco...

Страница 7: ...14 Maintenance 15 3 1 I Winterizing 15 3 2 I Maintenance 15 Troubleshooting 18 4 1 I Appliance behaviour 18 4 2 I Error code display 19 4 3 I Lighting of LEDs on the printed circuit board 20 4 4 I Wir...

Страница 8: ...grated under its base height adjustable on a stable solid and level surface This surface must be able to bear the weight voir 5 2 I Technical specifications of the appliance in particular in the case...

Страница 9: ...ns Install 50 cm of flexible PVC pipe at the heat pump water inlet and outlet to absorb vibrations Increase the filtration time by 50 and activate silence mode The heat pump will run for longer with l...

Страница 10: ...valve by pass valve water outlet valve water inlet adjustment valve optional water outlet adjustment valve optional water treatment minimum distance To evacuate the condensates fit a 18 pipe on the g...

Страница 11: ...curve rating to be defined according to the table 5 2 I Technical specifications with a suitable dedicated differential protection device circuit breaker or switch Additional protection may be requir...

Страница 12: ...isk of interference using a collar inside the appliance just after the glands 1 5 1 Heating priority option This function helps to keep the water temperature constant by checking the water temperature...

Страница 13: ...will have enough operating range to heat up Cover the pool with a sheet bubble canopy canvas etc to prevent heat loss The heat pump will be even more efficient if it operates during the warmest hours...

Страница 14: ...see 4 2 I Error code display Off Stopped Device off or not connected to the power supply 2 3 I Operation Check that there are no tools or other foreign objects in the machine The panel that provides...

Страница 15: ...the temperature setpoint is displayed and flashes Press to increase the temperature by 0 5 C Press to reduce the temperature by 0 5 C Press to confirm the desired setpoint temperature The settings scr...

Страница 16: ...the setpoint temperature to at least 2 degrees below the measured water temperature 2 5 I Connection to the iAquaLink app The Z400iQ heat pump may be controlled by remote from a smartphone or tablet v...

Страница 17: ...operations are carried out at the user s expense by a qualified technician 3 2 1 Safety instructions concerning appliances containing R32 refrigerant Z400iQ MD4 MD5 TD7 TD8 TD9 models Area check Prio...

Страница 18: ...all include damage to cables excessive number of connections terminals not made to original specification damage to seals incorrect fitting of glands etc Ensure that the apparatus is mounted securely...

Страница 19: ...is available if required for handling refrigerant cylinders all personal protective equipment is available and being used correctly the recovery process is supervised at all times by a competent perso...

Страница 20: ...low below 12 C The appliance is smoking The machine has come to the end of the defrost cycle water has changed to gaseous state and passes through the grid If your heat pump is not in its defrost cycl...

Страница 21: ...ng red LED press Cooling circuit high pressure fault Exchanger clogged with dirt Clean the water exchanger Steady red LED automatic Flashing red LED press Insufficient water flow Increase flow using t...

Страница 22: ...s Condenser protection ST1 sensor temperature too low Wait until the water temperature rises above 35 C or switch to Hot mode if the appliance is in Cooling mode Automatic 4 3 I Lighting of LEDs on th...

Страница 23: ...teristics 5 1 I Description In the appliance s box A Z400iQ B Winterizing cap x2 C 50 connector to be glued x2 D Winterizing cover Heating priority E PAC NET cleaning product supplied available as an...

Страница 24: ...A Boost 64 65 66 68 64 65 64 66 Silence 61 63 63 66 61 62 62 63 Frequency band GHz 2 412 2 484 Emitted power dBm 20 Type of refrigerant R32 R410A R32 R410A R32 R410A R32 Refrigerant amount kg 0 87 1 0...

Страница 25: ...1030 1145 B 450 480 C 479 509 D 880 1027 Overall dimensions in mm Front Side Rear Base Front panel Grid User interface Appliance status LEDs Side panel Technical access door Technical access door Poo...

Страница 26: ...Sch mas lectriques Wiring diagrams Schaltplan Elektrischschema Esquema el ctrico Esquema el ctrico Schema elettrico 1 Z400iQ MD4 MD5...

Страница 27: ...2 Z400iQ MD7...

Страница 28: ...3 Z400iQ MD8...

Страница 29: ...4 Z400iQ MD9...

Страница 30: ...5 Z400iQ TD7 TD8 TD9...

Страница 31: ...ature sensor Fl ssigkeitstemperatur f hler Temperatuursensor vloeistof ST5 Sonde temp rature refoulement Compressor discharge temperature Temperaturf hler an Druckseite Temperatuursensor perszijde LP...

Страница 32: ...ra de l quido Sonda temperatura liquida ST5 Sonda de temperatura de descarga Sonda temperatura retorno Sonda temperatura di mandata LP Presostato de baja presi n Pressostato baixa press o Pressostato...

Страница 33: ...eil Appliance model Num ro de s rie Serial number EUROPE ZPCE ZA La Balme 31450 Belberaud S A S U au capital de 1 267 140 SIRET 395 068 679 00046 RCS TOULOUSE AUSTRALIA Zodiac Group Australia Pty Ltd...

Отзывы: