❹ Troubleshooting

• 

If a problem occurs, before you contact your retailer, please carry out these few simple checks 

using the following tables. 

• 

If the problem continues, contact your retailer.

• 

: Actions to be performed by a qualified technician only

  

4.1 I  Appliance behaviour

The appliance 

does not start 

heating straight 

away

• 

When the setpoint temperature is reached, the heat pump stops heating: the water temperature 

is higher than or equal to the setpoint temperature.

• 

When the water flow rate is zero or is not enough, the heat pump stops: check that the water is 

circulating correctly in the heat pump (see § ‘’2.2 I  User interface presentation’’) and that the 

hydraulic connections are correct.

• 

The heat pump stops when the outdoor temperature falls below -12 °C.

• 

It may be that the heat pump has detected an operating fault (see § ‘’4.2 I  Error code display’’). 

• 

If you have checked these points and the problem persists: contact your retailer.

The appliance 

is discharging 

water 

• 

Often  called  condensates.  This  water  is  the  moisture  contained  in  the  air  which  condenses 

on contact with certain cold mechanisms in the heat pump, especially on the evaporator. The 

damper the air, the more condensates your heat pump will produce (your appliance may drain 

several litres of water per day). This water is retrieved by the base of the heat pump and drained 

by the condensate drainage elbow (see § ‘’1.2 I  Hydraulic connections’’). 

•  To check that the water is not coming from a leak in the pool circuit on the heat pump, shut 

down the heat pump and run the filtration pump for the water to circulate in the heat pump. If 

the water continues to flow through the condensate drainage lines, there is a water leak in the 

heat pump; contact your retailer.

The evaporator is 

iced over

•  Your heat pump will soon switch to its defrost cycle to melt the ice.

• 

If your heat pump cannot manage to defrost its evaporator, it will stop itself; this means that the 

outdoor temperature is too low (below -12 °C).

The appliance is 

"smoking"

• 

The machine has come to the end of the defrost cycle; water has changed to gaseous state and 

passes through the grid.

• 

If your heat pump is not in its defrost cycle, this is not normal. Switch off and disconnect the 

heat pump immediately and contact your retailer.

The appliance is 

not working

• 

 If there is no display, check the supply voltage and the F2 fuse.

• 

When the setpoint temperature is reached, the heat pump stops heating: the water temperature 

is higher than or equal to the setpoint temperature.

• 

When the water flow rate is zero or is not enough, the heat pump stops: check that the water is 

circulating correctly in the heat pump (see § ‘’2.2 I  User interface presentation’’).

•  The heat pump stops when the outdoor temperature falls below

 

-12 °C or rises above +40 °C.

• 

It may be that the heat pump has detected an operating fault (see § ‘’4.2 I  Error code display’’). 

The appliance 

is working 

but the water 

temperature 

does not increase

• 

Check that the automatic water filling controller (see diagram in § «2.3 I Operation») is not 

stuck in the open position: this will keep supplying cold water into the pool and will prevent the 

temperature from rising.

•  There is too much heat loss. Install a heat insulated cover on your pool.

•  The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean 

it to restore its performances (see § ‘’3.2 I  Maintenance’’).

• 

Check that the external environment is not hindering the heat pump (see § ‘’❶ Installation’’).

• 

 Check that the heat pump is the right size for this pool and its environment.

The fan is 

running but 

the compressor 

stops from time 

to time with no 

error message

•  If the outdoor temperature is low, the heat pump performs defrost cycles under normal 

operation.

•  The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean 

it to restore its performances (see § ‘’3.2 I  Maintenance’’).

The appliance 

trips the circuit 

breaker

• 

 

Check that the circuit breaker is correctly dimensioned and that the cable section used is 

appropriate

 (see § ‘’5.2 I  Technical specifications’’).

• 

 The supply voltage is too low: contact your electricity supplier.

EN

Содержание iAquaLink Z400iQ

Страница 1: ...H0638700_REVI 2021 06 More documents on www zodiac com Z400iQ EN Instructions for installation and use English Heat pump Translation of the original instructions in French...

Страница 2: ......

Страница 3: ...r instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance This appliance can be used by ch...

Страница 4: ...orm maintenance or servicing operations on the appliance with wet hands or if the appliance is wet Before connecting the appliance to the source of supply ensure that the terminal block or supply sock...

Страница 5: ...h the consequent risk of severe burns TROUBLESHOOTING All soldering work must be carried out by a someone qualified to do so Replacement pipes must always be made of copper in compliance with standard...

Страница 6: ...working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer it in doubt The reco...

Страница 7: ...14 Maintenance 15 3 1 I Winterizing 15 3 2 I Maintenance 15 Troubleshooting 18 4 1 I Appliance behaviour 18 4 2 I Error code display 19 4 3 I Lighting of LEDs on the printed circuit board 20 4 4 I Wir...

Страница 8: ...grated under its base height adjustable on a stable solid and level surface This surface must be able to bear the weight voir 5 2 I Technical specifications of the appliance in particular in the case...

Страница 9: ...ns Install 50 cm of flexible PVC pipe at the heat pump water inlet and outlet to absorb vibrations Increase the filtration time by 50 and activate silence mode The heat pump will run for longer with l...

Страница 10: ...valve by pass valve water outlet valve water inlet adjustment valve optional water outlet adjustment valve optional water treatment minimum distance To evacuate the condensates fit a 18 pipe on the g...

Страница 11: ...curve rating to be defined according to the table 5 2 I Technical specifications with a suitable dedicated differential protection device circuit breaker or switch Additional protection may be requir...

Страница 12: ...isk of interference using a collar inside the appliance just after the glands 1 5 1 Heating priority option This function helps to keep the water temperature constant by checking the water temperature...

Страница 13: ...will have enough operating range to heat up Cover the pool with a sheet bubble canopy canvas etc to prevent heat loss The heat pump will be even more efficient if it operates during the warmest hours...

Страница 14: ...see 4 2 I Error code display Off Stopped Device off or not connected to the power supply 2 3 I Operation Check that there are no tools or other foreign objects in the machine The panel that provides...

Страница 15: ...the temperature setpoint is displayed and flashes Press to increase the temperature by 0 5 C Press to reduce the temperature by 0 5 C Press to confirm the desired setpoint temperature The settings scr...

Страница 16: ...the setpoint temperature to at least 2 degrees below the measured water temperature 2 5 I Connection to the iAquaLink app The Z400iQ heat pump may be controlled by remote from a smartphone or tablet v...

Страница 17: ...operations are carried out at the user s expense by a qualified technician 3 2 1 Safety instructions concerning appliances containing R32 refrigerant Z400iQ MD4 MD5 TD7 TD8 TD9 models Area check Prio...

Страница 18: ...all include damage to cables excessive number of connections terminals not made to original specification damage to seals incorrect fitting of glands etc Ensure that the apparatus is mounted securely...

Страница 19: ...is available if required for handling refrigerant cylinders all personal protective equipment is available and being used correctly the recovery process is supervised at all times by a competent perso...

Страница 20: ...low below 12 C The appliance is smoking The machine has come to the end of the defrost cycle water has changed to gaseous state and passes through the grid If your heat pump is not in its defrost cycl...

Страница 21: ...ng red LED press Cooling circuit high pressure fault Exchanger clogged with dirt Clean the water exchanger Steady red LED automatic Flashing red LED press Insufficient water flow Increase flow using t...

Страница 22: ...s Condenser protection ST1 sensor temperature too low Wait until the water temperature rises above 35 C or switch to Hot mode if the appliance is in Cooling mode Automatic 4 3 I Lighting of LEDs on th...

Страница 23: ...teristics 5 1 I Description In the appliance s box A Z400iQ B Winterizing cap x2 C 50 connector to be glued x2 D Winterizing cover Heating priority E PAC NET cleaning product supplied available as an...

Страница 24: ...A Boost 64 65 66 68 64 65 64 66 Silence 61 63 63 66 61 62 62 63 Frequency band GHz 2 412 2 484 Emitted power dBm 20 Type of refrigerant R32 R410A R32 R410A R32 R410A R32 Refrigerant amount kg 0 87 1 0...

Страница 25: ...1030 1145 B 450 480 C 479 509 D 880 1027 Overall dimensions in mm Front Side Rear Base Front panel Grid User interface Appliance status LEDs Side panel Technical access door Technical access door Poo...

Страница 26: ...Sch mas lectriques Wiring diagrams Schaltplan Elektrischschema Esquema el ctrico Esquema el ctrico Schema elettrico 1 Z400iQ MD4 MD5...

Страница 27: ...2 Z400iQ MD7...

Страница 28: ...3 Z400iQ MD8...

Страница 29: ...4 Z400iQ MD9...

Страница 30: ...5 Z400iQ TD7 TD8 TD9...

Страница 31: ...ature sensor Fl ssigkeitstemperatur f hler Temperatuursensor vloeistof ST5 Sonde temp rature refoulement Compressor discharge temperature Temperaturf hler an Druckseite Temperatuursensor perszijde LP...

Страница 32: ...ra de l quido Sonda temperatura liquida ST5 Sonda de temperatura de descarga Sonda temperatura retorno Sonda temperatura di mandata LP Presostato de baja presi n Pressostato baixa press o Pressostato...

Страница 33: ...eil Appliance model Num ro de s rie Serial number EUROPE ZPCE ZA La Balme 31450 Belberaud S A S U au capital de 1 267 140 SIRET 395 068 679 00046 RCS TOULOUSE AUSTRALIA Zodiac Group Australia Pty Ltd...

Отзывы: