2.2.2 The appliance operates but the water temperature does not rise 

 

Causes 

Verification / solution 

Not enough filtering time 

Put the filtering on manual 24/24 hours to raise 
the temperature. 

Non-complying period of use 

Check whether the heat pump is of the right 
dimension for this period of the year.  

The heat pump is under-dimensioned. 

Check the characteristics of the heat pump 
according to the pool. 

The automatic pool water filler is jammed in open 
position. 

Checking correct operation of the automatic filler. 

The heat insulating cover is not used. 

Put on the heat insulating cover. 

The evaporator is fouled. 

Clean the evaporator (see §3.1) 

The appliance is badly installed. 

The appliance must be installed outdoors. 
Make sure there is no obstacle less than 4 
metres from where the blower is facing, and 0.50 
metre behind the heat pump. 

 

2.2.3 The fan turns but the compressor stops from time to time without an error 
message appearing 

 

Causes 

Verification / solution 

The heat pump does defrosting cycles from time to 
time. 

Normal if the outside temperature is lower than 
12 °C. 

The evaporator is fouled. 

Clean the evaporator. 

 

2.2.4 The heat pump trips out or attempts to start itself from time to time 

 

Causes 

Verification / solution 

The circuit breaker is under dimensioned or badly 
dimensioned. 

Check the circuit breaker (see § 1.4.5.1). 

The cable section is to small. 

Check the cable section (see §1.4.5.3)  

The supply voltage is to low. 

Call your electricity board. 

 

3. Maintenance 

3.1 Maintenance instructions 

 

 

 ensure no foreign bodies obstruct the fan grid, 

 clean the evaporator with a soft brush and a fresh water jet (disconnect the power cable), do not 

twist or bend the metal blades,  

 

 

 

 check the good operation of the regulator,  

 check the safety components, 

 check the tightening and connections of the electric cables and the cleanliness of the electrical 

equipment box, 

 

 

 

Incorrectly tightened terminals may cause overheating of the electrical terminal rail. 

Do not use a high-pressure water jet. 

A general servicing of the appliance is recommended when wintering and restarting, to 
check the proper operation of your appliance, maintain its performance and to prevent some 
breakdowns. 

Servicing costs will be borne by the user, and must be performed by a qualified 
technician.

 

Содержание FP 8M

Страница 1: ...Installation instructions PF 6M 8M 11M 13M 15M Heat pump for swimming pools R f N C 014 A EN Ver 12 2010...

Страница 2: ...0 2 1 Statuses and faults of the regulator 10 2 1 1 Statuses 10 2 1 2 Faults 10 2 1 3 Display the values of sensors ST1 ST2 ST3 and ST4 11 2 2 Malfunctions of the appliance 11 2 2 1 The appliance does...

Страница 3: ...ing If the appliance has been tipped over express reserves in writing to the transporter Elimination or shunting of one of the safety leads automatically to the cancellation of the guarantee as for th...

Страница 4: ...1 with an ambient air of 15 C and a pool water of 26 C humidity 70 in compliance with the French NF 414 standard unit protection class IP 24 refrigerant gas R410A refrigerant charge see product name...

Страница 5: ...4 3 Installing the appliance installed the 5 anti vibration studs supplied see 1 1 2 put onto a stable solid concrete slab type and level surface preserve from risks of flooding due to condensation p...

Страница 6: ...5 1 1 Condensation drainage Caution your appliance can drain several litres of water per day and you are strongly advised to connect the drainage to the sewer connect a 18 interior pipe not supplied...

Страница 7: ...ing function Objective to keep the pool water at the required temperature independent of the filtering time the heat pump triggers the operation of the filter every hour the pool temperature required...

Страница 8: ...ing output terminals 16 17 heat pump B1 regulation electronic card see placing dimensions and description in the appendix Never power the filter pump motor directly through terminals 16 17 located on...

Страница 9: ...pressure to 150 g 0 150 bar open valves 2 3 and 4 completely then half open valve 5 see 1 4 4 the air accumulated in the heat pump condenser unit and in the filter circuit is then evacuated If valves...

Страница 10: ...by mode by pressing and holding for 3 seconds on then appears on the screen for 5 seconds before a small red dot appears open the valve 1 close valves 2 and 3 and open valves 4 and 5 if present ensur...

Страница 11: ...ect the sensor Switch the power supply off or press if dSA flashes Defrost sensor fault ST3 Sensor defective or disconnected terminals 4 6 of the plate B1 Replace or reconnect the sensor Switch the po...

Страница 12: ...an approved technician to check for the presence of an adequate quantity of refrigerant gas in the appliance Switch the power supply off or press if dtd flashes case after stand by following regulator...

Страница 13: ...if the outside temperature is lower than 12 C The evaporator is fouled Clean the evaporator 2 2 4 The heat pump trips out or attempts to start itself from time to time Causes Verification solution Th...

Страница 14: ...es Shipping expenses for the repaired or replaced Products delivered to the client will be borne by us excluding any labour costs travel and or accommodation expenses incurred as the result of repairs...

Страница 15: ...l installer excluding installation via retrofit kit for a period of two years starting from the date mentioned on the invoice as issued by our Client to the end User Users are also required to have an...

Страница 16: ...itrogen brazing etc all brazing work must be carried out by a qualified brazer welder in the case of units filled with R410A refer to the specific indications in the installation instructions this uni...

Страница 17: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 18: ...1 Electric diagram PF 6M 8M...

Страница 19: ...2 PF 11M 13M 15M...

Страница 20: ...Water flow adjusting probe NTC Regulation electronic card Pump control Fuse 3 15A T 250V 5 20 Fan capacitor Compressor capacitor Fan connector Fan Compressor Soft starter Black Blue Brown Grey White...

Страница 21: ...English Base Front pannel cowl Technical door Back pannel Post Grid Regulator 1 water pool inlet 1 water pool outlet Evaporator Stuffing box B1 regulation electronic card Fuse F1 Supply terminal boar...

Страница 22: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 23: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 24: ...023 49180 Saint Barth l my d Anjou cedex France www zodiac poolcare com Innovative pool products and services Produits et services innovants pour la piscine Votre installateur Your installer Plaque si...

Отзывы: