1.4.5 Electric connections 

 

1.4.5.1 Voltage and protection 

 

 

 

 the electrical supply of the appliance must come from a protection and switching device (not 

supplied) complying with the standards and regulations in force in the country. 

 an additional protection may be required during installation to guarantee the overvoltage category 

II,  

 the unit is designed for connection to a general power supply with full earth and neutral or neutral 

earth systems, 

 electrical protection: by circuit-breaker (curve D) or fuse (Am) (for calibre, see §1.4.5.3), and with a 

30 mA differential trip switch at the head of the supply line (circuit-breaker or switch), 

 

 

 

1.4.5.2 Connections 

 

 

 

See placing § “dimensions and description” in the appendix 

 

 

 

1.4.5.3 Cable sections

 

 

 

supply cable section: for cables of a maximum length of 20 metres (calculation base: 5A/mm²), 

must be checked and adapted depending on installation conditions.

  

 

PF  

Maximum current 

consumption 

Cable saction 

Electrical protection 

mm² 

 

6M 

3 x 2.5  

3G2.5 

16 

8M 

10 

3 x 2.5  

3G2.5 

16 

11M 

14.5 

3 x 2.5  

3G2.5 

16 

13M 

16.1 

3 x 4 

3G4 

20 

15M 

21.9 

3 x 6  

3G6 

25 

 

1.4.5.4 “Priority Heating” function 

 

Objective: to keep the 

pool water at the required temperature

, independent of the filtering time (the 

heat pump triggers the operation of the filter every hour):  

- the pool temperature > required temperature = the heat pump stops the filter system after 5 
minutes. 
- the pool temperature < required temperature = the heat pump switches on and keeps the filter 
pump running until the correct temperature is attained. 

 
 

 

The appliance must be earthed. 
Risk of electrical shock inside the device. Only a qualified and experienced technician 
can install the device’s cables. 
If the power cable is damaged, it must be replaced by a qualified technician or in a 
Zodiac Pool Care Europe technical station.

 

 acceptable tolerance of tension variation: ± 6% (while working), 

 electric cables shall be fixed, 

 use 

cable suited for outdoor use

of type RO2V or equivalent in countries outside 

the European Community

, and with an outer diameter between 9 and 18 mm,  

 use the stuffing box to bring the supply cable into the appliance 

Prior to any operation, check that the voltage on the identification plate of the 
appliance corresponds to the mains voltage provided on site.

 

Configuration of supply terminal rail 

single-phase 230V-50Hz with phase (L) 

+ neutral (N) + Earth 

Fuse holder F1 

3.15 A Type T 

(timed) 250Vac 

Earth terminal green/yellow 

Содержание FP 8M

Страница 1: ...Installation instructions PF 6M 8M 11M 13M 15M Heat pump for swimming pools R f N C 014 A EN Ver 12 2010...

Страница 2: ...0 2 1 Statuses and faults of the regulator 10 2 1 1 Statuses 10 2 1 2 Faults 10 2 1 3 Display the values of sensors ST1 ST2 ST3 and ST4 11 2 2 Malfunctions of the appliance 11 2 2 1 The appliance does...

Страница 3: ...ing If the appliance has been tipped over express reserves in writing to the transporter Elimination or shunting of one of the safety leads automatically to the cancellation of the guarantee as for th...

Страница 4: ...1 with an ambient air of 15 C and a pool water of 26 C humidity 70 in compliance with the French NF 414 standard unit protection class IP 24 refrigerant gas R410A refrigerant charge see product name...

Страница 5: ...4 3 Installing the appliance installed the 5 anti vibration studs supplied see 1 1 2 put onto a stable solid concrete slab type and level surface preserve from risks of flooding due to condensation p...

Страница 6: ...5 1 1 Condensation drainage Caution your appliance can drain several litres of water per day and you are strongly advised to connect the drainage to the sewer connect a 18 interior pipe not supplied...

Страница 7: ...ing function Objective to keep the pool water at the required temperature independent of the filtering time the heat pump triggers the operation of the filter every hour the pool temperature required...

Страница 8: ...ing output terminals 16 17 heat pump B1 regulation electronic card see placing dimensions and description in the appendix Never power the filter pump motor directly through terminals 16 17 located on...

Страница 9: ...pressure to 150 g 0 150 bar open valves 2 3 and 4 completely then half open valve 5 see 1 4 4 the air accumulated in the heat pump condenser unit and in the filter circuit is then evacuated If valves...

Страница 10: ...by mode by pressing and holding for 3 seconds on then appears on the screen for 5 seconds before a small red dot appears open the valve 1 close valves 2 and 3 and open valves 4 and 5 if present ensur...

Страница 11: ...ect the sensor Switch the power supply off or press if dSA flashes Defrost sensor fault ST3 Sensor defective or disconnected terminals 4 6 of the plate B1 Replace or reconnect the sensor Switch the po...

Страница 12: ...an approved technician to check for the presence of an adequate quantity of refrigerant gas in the appliance Switch the power supply off or press if dtd flashes case after stand by following regulator...

Страница 13: ...if the outside temperature is lower than 12 C The evaporator is fouled Clean the evaporator 2 2 4 The heat pump trips out or attempts to start itself from time to time Causes Verification solution Th...

Страница 14: ...es Shipping expenses for the repaired or replaced Products delivered to the client will be borne by us excluding any labour costs travel and or accommodation expenses incurred as the result of repairs...

Страница 15: ...l installer excluding installation via retrofit kit for a period of two years starting from the date mentioned on the invoice as issued by our Client to the end User Users are also required to have an...

Страница 16: ...itrogen brazing etc all brazing work must be carried out by a qualified brazer welder in the case of units filled with R410A refer to the specific indications in the installation instructions this uni...

Страница 17: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 18: ...1 Electric diagram PF 6M 8M...

Страница 19: ...2 PF 11M 13M 15M...

Страница 20: ...Water flow adjusting probe NTC Regulation electronic card Pump control Fuse 3 15A T 250V 5 20 Fan capacitor Compressor capacitor Fan connector Fan Compressor Soft starter Black Blue Brown Grey White...

Страница 21: ...English Base Front pannel cowl Technical door Back pannel Post Grid Regulator 1 water pool inlet 1 water pool outlet Evaporator Stuffing box B1 regulation electronic card Fuse F1 Supply terminal boar...

Страница 22: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 23: ...N o t e s N o t e n A a n t e k e n i n g N o t a s N o t a...

Страница 24: ...023 49180 Saint Barth l my d Anjou cedex France www zodiac poolcare com Innovative pool products and services Produits et services innovants pour la piscine Votre installateur Your installer Plaque si...

Отзывы: