15
5 min. after re-start of the heat pump
(fan + compressor), check the water flow pressure gauge display and set valve V3 or
V5 in order to bring the needle into the green zone (beginning of season {cold water}: position at the start of the green zone).
Reminder:
If, when setting the by-pass and setting valves, the flow rate is less than 1.5 m3/h the heat pump will not
function
(the flow switch remains open and the regulator displays the message AId alternating with the water temperature)
. Adjust the setting
valves : -
V5
-
(if present)
or -
V3
- and -
V1
-.
When the heat pump is running :
-
If the flow rate switch switches on or off for a period longer than or equal to 3 s, a timer of 130 seconds* min. is
activated before the unit starts again.
* For information
this time period may increase during a defrost cycle or if the compressor stop time is less than 180 s.
-In case of a power failure, a timer of 125 seconds starts when the power supply is restored before the unit starts again.
Observation:
When the water attains the target temperature (Leds
and
off) the heat pump switches off
automatically.
Reminder:
The 3-phase heat pump is equipped with a phase order control system (
KA1
) used to check that the phase order is correct
at start up (and during operation) and to signal a phase order fault (regulator indicates dCP fault and the green led
KA1
inside the unit is off. The orange led remains on as long as phase L1 is present). In that event, s
witch off and isolate the
unit
and it is sufficient to invert two phase wires directly on the main supply terminal.
ATTENTION !
this operation must be carried out by a qualified and authorised professional
6.3 Checking
Check that the heat pump stops heating when:
• the target temperature on the digital display thermostat is decreased
.
• filtration is switched off or valve V2
or V4 closed.
6.4 Troubleshooting
Faults :
Message
Designation
Cause
Remedy
Reset
Alarm
Control sensor fault
Sensor defective or
disconnected
Replace or reconnect the sensor
Cut power supply or press
button
if dSr starts
blinking
YES
(terminals 0-4)
Anti-frost sensor fault
Sensor defective or
disconnected
Replace or reconnect the sensor
Cut power supply or press
button
if dSA starts
blinking
YES
(terminals 0-4)
Defrost sensor fault
Sensor defective or
disconnected
Replace or reconnect the sensor
Cut power supply or press
button
if dSd starts
blinking
YES
(terminals 0-4)
Low pressure fault in
refrigerating circuit
Insufficient refrigerant
Consult a PSA-approved technician to
look for leaks and refill refrigerant
Automatic
(if less than 4 faults within an
hour) or by pressing the button
if dbP starts blinking
YES
- if more than 4
faults within one
hour -
(terminals 0-4)
High pressure fault in
refrigerating circuit
1- Water and air mixture
passing in the appliance
2- Refrigerant overload
1- Purge hydraulic circuit
2- Consult a PSA-approved technician
to check the refrigerant level
Automatic
(if less than 4 faults within an
hour) or by pressing the button
if dHP starts blinking
YES
- if more than 4
faults within one
hour -
(terminals 0-4)
Normal position of the pressure
gauge needle when the appliance is
off
(compressor and fan(s) OFF).
Attention ! this position may vary
slightly in the « ARRET » zone
depending on water and ambient air
temperatures.
Normal position of the pressure
gauge needle when the
appliance is in operation
(compressor and fan(s) ON).
The position range in the
«CORRECT » zone may vary
depending on water and ambient air
temperatures, or even attain the
«LOW » zone when the water flow
going into the unit is too low.
Info: led
remains on for 120s after a fault is indicated (except in the case of a dC indication when the heat pump remains operational).