The electrical characteristics are within
±
3 percent of the indicated values of Isc, Voc and Pmpp under
test conditions (irradiance of 1000W/cm
2
,AM1.5 spectrum, and a cell temperature of 25
℃
)
●
Under normal conditions, a photovoltaic module is likely to experience conditions that produce more
current and/or voltage than reported at standard test conditions. Accordingly, the values of ISC and VOC marked
on this module should be multiplied by a factor of 1,25when determining component voltage ratings, conductor
current ratings, fuse sizes, and size of controls connected to the PV output."
●
Installation should be in accordance with Australian installation standards AS3000 wiring rules and
AS/NZS 5033.
2、
Operating environment
CLIMATE CONDITION
Install the PV module in the following conditions:
●
Environment temperature
:
-20
℃
to 40
℃。
●
Operating temperature
:
-40
℃
to 80
℃。
●
Waterproof: don’t dip the modules into the water or continually explode under the water device or
fountain.
●
Antisepsis: keep away from salt erode and sulfuration places
●
Do not wear rings, jewelry, watches or other metallic items while working with photovoltaic
modules.
3、
Mounting and notes
●
The modules’ electrical performance in a system is the same. When connected in series, all modules
must have the same amperage. When connected in parallel, the modules must all have the same voltage.
Connect the quantity of modules that match the voltage specifications of the devices used in the system.
The modules must not be connected together to create a voltage that is higher than the permitted
system voltage.
●
To minimize risk in the event of an indirect lightning strike, avoid forming loops when designing the
system.
●
Modules must not be fitted as overhead glazing. Ensure that the mounting system can also withstand
the anticipated wind and snow loads.
●
Precipitate can run off through small openings on the back side of the module. Make sure that the
openings are not masked after mounting.
●
The modules have passed mechanical load test 5400Pa,To avoid exceeding the maximum load,
site-specific live loads such as wind and snow should be taken into account.