ECI0016PA Data Capture Card User Manual V1.5
14
240
120
60
15
256
128
64
Firstly, check controller states to get the max IO No. and AIO No. of controller itself,
then use CANIO_ADDRESS to configure. When IO/AIO No. of the card and IO/AIO No. of
controller itself repeat, only one is valid. Therefore, it is recommended to configure
CANIO_ADDRESS again to make them different.
ECI0016PA is as CAN communication master station by default, but when it is used
as ZIO expansion module. If you need it is as CAN slave station, it is necessary to
configure CAN address and communication ratio again. It can configure CANIO_ADDRESS
parameter through online command.
According to CAN wiring, then after powered on, set DIP correctly, POWER, RUN and
IO POWER are ON, ALM is off. At the same time, “Controller”—“State the Controller”—
“ZCanNodes” in ZD
evelop shows expansion module information and expanded IO No.
range.
When multiple expansion modules are connected, DIP ID and corresponding resource
No, reference are below:
ALMRM led is ON, please check the wiring, resistor or DIP setting, and whether
controller is set as master station (CANIO_ADDRESS = 32 means main station, others are
slave station.
Example:
CANIO_ADDRESS=1
‘set
CAN ID as 1, now is slave station, 500KBPS, used as ZCAN slave station.
CANIO_ADDRESS=2 + 256
‘set CAN ID as 2, now is slave station, 250KBPS, used as ZCAN slave station.
CANIO_ADDRESS=3 + 512
‘set CAN ID as 3, now is slave station, 125KBPS, used as ZCAN
slave station.
CANIO_ADDRESS=4 + 768
‘set CAN ID as 4, now is slave station, 1MBPS, used as ZCAN slave station.