ECI0016PA Data Capture Card User Manual V1.5
AD
Input
Analog input terminal AIN (10)
AD
Input
Analog input terminal AIN (11)
AGND
Public end
Unique public end of this analog
SG
/
Shield
DA0
Output
DA1
Output
AGND
Public end
Unique public end of this analog
SG
/
Shield
Note:
analog input supports single-end input, and the reference ground of sensor needs to be connected to
AGND terminal.
3.4.1.
Analog Input / Output Specification & Wiring
→
Specification
Item
AD (0-11)
DA (0-1)
Resolution
16-bit
12-bit
Data range
0-65535
0-4095
Signal range
-10V-10V input
-10V-10V output
Data refresh
1kHz
1kHz
Voltage input impedance
/ output load
>1MΩ
(voltage input
impedance)
>1KΩ
(voltage output
load)
→
Wiring Reference