DIP Switch Settings
4.4
This part introduces how to set the RS485 address setting, factory setting and terminal resistance
setting of the control panel through the DIP switch.
485 address setting
Places 1-6 of the DIP switch are reserved to set device number for RS485 communication. The code
is binary, and the lower places are in the front. When the switch is set to the ON position, it indicates
1 (on); when the switch is set downwards, it indicates 0 (off).
For example, to set a device number 39=1+2+4+32, which corresponds to the binary code 111001,
put places 1, 2, 3, and 6 to the ON position, as illustrated below.
485 address setting table:
Place Address
Switch Setting
1
2
3
4
5
6
Address No.
1
2
4
8
16
32
01
ON
OFF
OFF
OFF
OFF
OFF
02
OFF
ON
OFF
OFF
OFF
OFF
03
ON
ON
OFF
OFF
OFF
OFF
04
OFF
OFF
ON
OFF
OFF
OFF
05
ON
OFF
ON
OFF
OFF
OFF
06
OFF
ON
ON
OFF
OFF
OFF
07
ON
ON
ON
OFF
OFF
OFF
08
OFF
OFF
OFF
ON
OFF
OFF
09
ON
OFF
OFF
ON
OFF
OFF
10
OFF
ON
OFF
ON
OFF
OFF
11
ON
ON
OFF
ON
OFF
OFF
12
OFF
OFF
ON
ON
OFF
OFF
13
ON
OFF
ON
ON
OFF
OFF
14
OFF
ON
ON
ON
OFF
OFF
15
ON
ON
ON
ON
OFF
OFF
16
OFF
OFF
OFF
OFF
ON
OFF
17
ON
OFF
OFF
OFF
ON
OFF
18
OFF
ON
OFF
OFF
ON
OFF
19
ON
ON
OFF
OFF
ON
OFF
20
OFF
OFF
ON
OFF
ON
OFF
21
ON
OFF
ON
OFF
ON
OFF
22
OFF
ON
ON
OFF
ON
OFF
23
ON
ON
ON
OFF
ON
OFF
24
OFF
OFF
OFF
ON
ON
OFF
Содержание InBio160
Страница 1: ...USER MANUAL Applicable Models InBio160 260 460 Pro Access Control Panel Version 1 0 ...
Страница 10: ...6 Indicator Diagram Figure 2 1 Indicators in the InBio460 Pro ...
Страница 13: ...9 Control Panel System Installation 3 3 Figure 3 2 Schematic Diagram of System Installation ...
Страница 15: ...11 InBio260 Pro Terminal connection diagram ...
Страница 16: ...12 InBio460 Pro Terminal connection diagram ...