Installation Sheet 

No.: 1776 iss 03 

ZP755HA-2 Addressable Omni-directional Sounder 

Installation sheet 

501-1776ZE-1-03 

ZP755HA-2 Addressable Omni-directional Sounder 

Page 3 

14/11/2006 

Operating Power 

The  ZP755HA-2  can  be  powered  directly  from  its 
address loop (setting 1), or externally from a 24 VDC 
supply (setting 2). See Figure 3. 

Setting the Address

 

The switch is used to set the device address in binary 
code.  The  switch  may  be  set  to  represent  all 
addresses from 1 to 127. See Figure 3. 

 

Figure 3 

Operating Modes 

The  ZP755HA-2sounder  has  2  modes  of  operation, 
which are selected using switch 7 on dipswitch SW2. 
It may be operated as a dedicated sounder or with a 
detector fitted. See Figure 3. 

 

 

 

 

 

 

1. 

Operation as a Stand-alone Sounder 

Own unique loop 
address 

Switch 7 = ON 

1.1  Navigate  to  the  following  menu  to  tag  the 

sounders as SAB: 

ZP3 

Panel 

Menu/Setup/Sounders/SAB/Add 

SAB. 

The Planner program can also be used. 

1.2  To map an alert to evac function the first input 

type  must  be  a  fast  flash  input.  The  sounder 
will  sound  the  alert  tone  in  response  to  a  fast 
flash  input.  The  sounder  will  sound  the  evac 
tone  when  the  input  configured  as  steady  is 
triggered, overriding the alert tone 

Emulation 

The  ZP755HA-2  can  operate  as  a  ZP755HA-2  or 
emulate a ZP754. See Figure 4. 

1. 

ZP755 Mode 

Set  switch  6  (dipswitch  SW2)  to  OFF.  Provides 
user  selectable  2-tone  operation  and  full 
monitoring. 

Operates with ZP3 software 1.18 or higher. 

2. 

ZP754 Emulation Mode 

Set  switch  6  (dipswitch  SW2)  to  ON.  Emulates 
ZP754,  provides  2  fixed  tones.  Use  with  ZP5 
panels or ZP3 panels with legacy software. 

Tone Settings 

See Figure 4 – Operating Modes. 

Two different tones can be programmed to operate 
from the panel. In ZP755HA-2 mode these tones are 
selected  using  switches  1,  2  and  3  on  the  function 
dipswitch SW2. 

For mode selection, refer to Operating Modes. 

Note: 

In the ZP panel I/O mapping menu, outputs are 
programmed as "steady" or "flashing". The link to the 
table on the following page is as follows: 

Tone A = Panel setting "fast flash/slow flash.” 

Tone B = Panel setting "steady.” 