background image

P/N 10-5211-501-AZ70-12 • ISS 29JUN16 

 

3 of 4 

Figure 6: Head-out detection mode for detectors without an 
in series diode, e.g. Z620-1 &-2 (consult manufacturer) 

 

Figure 7: Intrinsically safe mode (using intrinsically safe 
detectors) 

 

Specifications 

 

Application 

Indoor use 

Power supply requirements 

External power supply 
Loop power 
Max. line drop 

 
19 to 30 VDC 
20 Volt pulsed addressable loop 
2 V 

Current consumption 

See Table 1 

Mechanical 

Material 
Colour 
Dimensions (L x W x H) 
Weight 
Mounting method 

 
Moulded ABS 
White 
85 x 78 x 27 mm 
80 g 
Surface or DIN rail 

Monitoring (conventional zone) 

Open and short circuit fault with a 
3.9 kΩ EOL resistor (normal 
conventional devices) or 8.2 

kΩ 

EOL resistor (intrinsically safe 
devices) 

Head-out operation with 3K9 
resistor available with Z6x0-3 
detectors or other detectors with 
series supply diode. Requires 
base with Schottky diode (for 
example, Z6-BS5. Add a series 
diode to the base – see Figure 6 
to use other detectors). 

Compatibility 

Addressable side 
 
Conventional side (max. 15 
devices) 

 
ZP3 and ZP2 addressable 
systems 
Ziton 610, 620, 630 
Hochiki intrinsically safe devices 
(these must be used in 
conjunction with a GBX2000 
galvanic isolator) 

Callpoint resistor required 

470R or 680R 

Wiring 

Belden 9501 or equivalent 
screened cable 

Operating environment 
 

Temperature  

 

Relative humidity  

 
−10 to +80°C 
20 to 95% noncondensing 

Storage temperature 

−10 to +80°C 

Detector compatibility 

Operating voltage (normal, 
head-out mode) 
Operating voltage (intrinsically 
safe mode) 
Alarm clamp voltage 
Current consumption (all 
detectors, excluding EOL 
resistor) 
Reset supplied by A70 

 
12.5 to 20 VDC 
 
14 to 20 VDC 
 
3 to 9 V 
1.5 mA (normal, head-out mode) 
3 mA (intrinsically safe mode) 
 
2.4 s power disconnect 

 

Table 1: Current consumption 

 

From external supply 

From loop 

Source 

Quiescent 

Worst case 
(S/C fault) 

Quiescent 

Worst case 
(S/C fault) 

Externally 
powered 

7.3 mA  

36.6 mA 

0.8 mA 

10 mA 

Loop 
powered 

 

 

8.3 mA 

24.6 mA 

 

Regulatory information 

This section includes both regulatory information and a 
summary on the declared performance according to the 
Construction Products Regulation 305/2011. For detailed 
information, see the product Declaration of Performance. 

 

Certification 

 

Certification body 

0370 

Declaration of 
Performance number 

360-5211-0399 

Year of first CE 
marking 

10 

Product Identification 

A70E-2

 

Intended use 

See the product Declaration of Performance 

Essential 
characteristics 

See the product Declaration of Performance 

Manufacturer 

United Technologies Safety System Co., Ltd. 
80, Changjiang East Road, QETDZ, 066004 
Qinhuangdao HEBEI, China 

Authorized EU manufacturing representative:  
UTC Fire & Security B.V.  
Kelvinstraat 7, 6003 DH Weert, Netherlands 

 

2012/19/EU (WEEE directive): Products 
marked with this symbol cannot be disposed 
of as unsorted municipal waste in the 
European Union. For proper recycling, return 
this product to your local supplier upon the 
purchase of equivalent new equipment, or 
dispose of it at designated collection points. 
For more information see: 
www.recyclethis.info. 

 

Contact information 

For contact information, see www.utcfssecurityproducts.eu. 

Отзывы: