2 / 4 

 

P/N 10-5211-501-AZ70-12 • ISS 29JUN16 

Operational settings 

Figure 3: A70E-2 Conventional Zone Interface wiring 

 

Setting the address 

The A70E-2 Conventional Zone Interface contains a 7-way DIP 
switch, which is used to set the device address in binary code. 
The switch may be set to represent all addresses from 1 to 
127. See Figure 3 for the location of the address DIP switch. 

The address is the sum of the switch values, as shown in the 
following table. Note that the switch values determine the 
address, not the switch numbers. 

 

Switch 
number 

Code value 

16 

32 

64 

Power supply selection – J1 

Jumper J1 is used to select between an externally powered or 
loop powered conventional zone. For the location of J1, see 
Figure 3. 

Note: 

Remove both jumpers before inserting either of them. 

External 24 VDC power 

 

Note: 

The device will go into fault if the jumpers are left out or 

if external power is removed when J1 is in the External 24 VDC 
Power position. 

Loop power 

 

Operating mode selection 

A 2-way mode DIP switch is used to select the conventional 
zone operating mode. See Figure 3 for the location of the 
mode DIP switch. 

Table 1: Operating mode selection 

Switch selection 

Mode 

SW 1 and 2 OFF 

Normal mode, see Figure 4 

SW 1 ON and 2 OFF 

Intrinsically safe mode, see Figure 7 

SW 1 and 2 ON 

Intrinsically safe mode, see Figure 7 

SW 1 OFF and 2 ON 

Head-out mode, see Figure 5 and Figure 6 

Note: 

It is not possible to be in both intrinsically safe and head-out 

mode. 

Table 2: LED indicator 

LED indicator  

Status 

Description 

Red alarm LED [1] 

Flashing 

Conventional zone fire 
and/or switched output 
operated 

Yellow fault LED [1] 

Flashing 

Conventional zone fault 

Yellow fault LED 

Double flashing 

Power fault 

[1] Once registered by the panel, the alarm LED output is maintained 
by the panel until reset. 