13.2.2
Digital outputs
The ZArec4C has two digital outputs as potential-free relay contacts with N/O switch function.
Technical data
Short-circuit-proof
No
Min. switching capacity
5 mA / 12 VDC
Max. switching capacity
2 A / 250 VAC
Clamping range
max. 2.5 mm
2
13.2.2.1
RDY (O3) digital output - operational
•
Information that the ZArec4C is operational
•
Contact closes as soon as the ZArec4C is started up
•
Contact opens in case of parameter input or a fault
•
After remedying the cause of the fault, the contact closes again
•
When the contact is open, it must be ensured that the EN input is not activated
•
After switching off RDY, the EN input must be deactivated within 1 s
13.2.2.2
Digital output /ERR (O4) - errors requiring switching off
•
Information that the internal temperature limits of the ZArec4C have been exceeded due to over-
loading and other errors, e.g. activation of the EN enable without the RDY output being active
•
If /ERR decreases, the energy supply (via DC cable) must be interrupted by the frequency inverter.
•
Quali
fi
ed personnel must be on site for error analysis and remedy
13.2.3
Connecting digital inputs and outputs
X-IN-OUT
ZArec4C
CL
EN
+24V
(8)
(7)
(6)
(5)
(4)
(3)
(2)
(1)
/ERR
RDY
1
OUT_1
IN_1
IN_2
Connecting digital inputs and outputs
1
Frequency inverter/control
OUT_1
Output activation ZArec4C
IN_1
"ZArec4C ready" input
IN_2
"Error ZArec4C" input
Original operating instructions
ZArec4C
Operating the ZArec4C with the frequency inverters from other manufacturers
R-TBA14_03-GB 1817 Index 007
Part.-No. 00163436-GB
56/64