8.3
Con
fi
guring the ZArec4C
When starting up the ZArec4C in combination with ZAdyn it is not necessary to enter parameters on
the ZArec4C.
8.4
Parameterisation of the ZAdyn
In order to be able to use the ZArec4C in combination with ZAdyn, the following parameters must be
set in the menu of the ZAdyn:
Select "ZArec" in the parameter
Encoder & BC / BC_TYPE
.
Encoder & BC
|
-
"
BC_Type BR11
|
-
"
ZArec
BR/BC - Type
Information
This setting should also be made if an additional external brake resistor is used, or if a 2nd parameter
set is used.
In the
Control
menu, parameterise the digital input of the ZAdyn (preferably I08) connected to the
digital RDY output to "ZR_RDY".
Control
|
-
"
f_I08
00: Free
|
-
"
44: ZR_RDY
Function of input
In the
Control
menu parameterise the digital output of the ZAdyn (preferably f_5) connected to the
digital input EN to "ZR_EN".
Control
|
-
"
f_O5
Off
|
-
"
ZR_EN
Function of output
9
Parameter list
The individual parameters are subdivided into various menus based on their functions.
Information
Not all the described parameters are freely accessible and visible. The display depends on the
selected functions and settings in the ZArec4C.
9.1
LCD & Password menu
Selecting the desired operating language
Parameter
Designation
Value range
Factory set-
ting
LCD
Select the desired operating language.
Deutsch
English
Deutsch
9.2
Basics
Parameter
Designation
Value range
Factory set-
ting
U_GRID
Entering the mains rated voltage
380...400 V
400 V
F_GRID
Entering the mains rated frequency
50 Hz
60 Hz (on request)
50 Hz
U_DC_RF
Input of the nominal voltage for return feed operation
630...730 V
670 V
T_STDBY
Input of time since last travel until the ZArec4C switches to
standby mode
0...65535 s
240 s
Original operating instructions
ZArec4C
Parameter list
R-TBA14_03-GB 1817 Index 007
Part.-No. 00163436-GB