17.6
Checking the motor phases
To avoid unde
fi
ned motor activities due to wrong connection, short circuit , broken wires, etc, the
motor phases will be checked during the start procedure. Therefor the current in the phases U/V/W
will be measured before the brakes are opening.
The monitoring function extends the start-up procedure by approx. 300 ms. In the case of the factory
setting "Single" and the correct test result, this only happens during initial travel once the frequency
inverter has been switched on.
If during the inspection an error is detected the error message
E412 - MOT:UVW fail
is displayed.
The different monitoring functions can be selected in the menu
ZA-Intern/UVW_CHK
. The factory
setting is "Single".
Function
Designation
Single
The motor phases are checked during initial travel once the frequency inverter has
been switched on. If the check is successful, no further monitoring is performed.
If the examination is incorrect, with each start an examination is made until a correct
examination could be accomplished.
Cont
Motor phases will be check with each travel
Off
Checking of the motor phases is deactivated
The testing voltage can be selected in the menu
ZA-Intern/UVW_PEK
an. The factory setting is
"f(P)".
Function
Designation
f(P)
The testing voltage depends on the nominal voltage of the motor, which is entered in
the menu
"Motor name plate"
. In case of an error the testing voltage is displayed in
the error message.
1V ... 10V
Selecting the testing voltage between 1 V and 10 V.
In case of an error the testing voltage is displayed in the error message.
15V
Test voltage 15 V.
Error "E412 - MOT:UVW fail" occurs, but the motor connection is correct
If the error "E412 - MOT:UVW fail" occurs even though the motor is connected correct, maybe the
testing voltage is to small. The testing voltage has to be increased manually.
17.7
Field weakening
The operation with
fi
eld weakening is only possible with asynchronous motor.
If the required motor speed for an asynchronous motor n* is above the rated speed n of the motor, the
ZAdyn4C automatically switches over to operation in the
fi
eld weakening range.
In operation with
fi
eld weakening the magnetizing current I_0 is reduced over the complete speed
range of the motor. The cos phi of the motor data will be increased. Thereby the required speed will be
reached.
The original and the new calculated motor data can be compared in the
Info/page05
menu.
Original operating instructions
ZAdyn4C
Special functions
R-TBA12_01-GB 2104 Index 012
Part.-No. 00163371-GB
189/224
1
7
S
p
e
c
ia
l
fu
n
c
ti
o
n
s
Содержание ZA dyn 4C
Страница 212: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 212 224 ...
Страница 213: ...19 Enclosure Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 213 224 ...
Страница 214: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 214 224 ...
Страница 215: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 215 224 19 Enclosure ...
Страница 216: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 216 224 ...
Страница 217: ...19 Enclosure Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 217 224 ...
Страница 220: ...Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 220 224 ...
Страница 221: ...19 Enclosure Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 221 224 ...
Страница 222: ...Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 222 224 ...
Страница 223: ...19 Enclosure Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 223 224 ...