Power2 - - - - - - - - - -
13
ERR_EXT U. OC: ...
SRC_APP. UCE_P: ...
SRC_MOP. UCE_M: ....
Page 12: Power2
Cause for excess current malfunction
Line 2:
ERR_EXT: Excess current message (display is not saved; point is only displayed if excess
current is present
U: Overvoltage error in the DC-link (voltage higher than 850 V DC)
OC: Overcurrent detected by the current sensors (incorrect phase is indicated by letters
U V W)
Line 3:
SRC_APP: Excess current is detected by the application processor.
UCE_P: Error in positive current path in power stage (faulty phase is displayed)
Line 4:
SRC_MOP: Excess current is detected by the motor management processor.
UCE_M: Error in negative current path in power stage (faulty phase is displayed)
During normal operation, no points and phase displays (U V W) should be active
During a malfunction, the displays remain active until the next travel command (with the
exception of ERR_EXT)
Bus Info 1 - - - - - - -
14
Info: xx
0101 / 010106 de
Load: 77% - 12.3A
Page 14: Bus Info 1
Information about the control system
Line 2:
Manufacturer
Line 3:
Software version of control system
Software date of the control system
Operating language set in the control system, display according to ISO639
The operating language of the frequency inverter is automatically adapted.
Line 4 (only with DCP4):
Load in % (0% = cabin empty)
Load-dependent start torque current
Bus Info 2 - - - - - - -
15
B01..4... G....4...
S.1....6. 100
RF UP V_3* MTW
Page 15: Bus Info 2
Online-display
Line 2:
Command and speed bytes
B= command byte
G= speed byte
Line 3:
Status byte
S= Statusbyte
Current operating state of the ZAdyn4C
Line 4:
Display of the actual travel commands:
RF: Controller enable
Travel direction
controlled travel speed
MTW: Motor temperature pre-warning, displayed at overtemperature (for ZAdyn4)
See chapter "Serial Communication / DCP (Drive Control & Position)" for further information
about DCP operation.
Original operating instructions
ZAdyn4C
Parameter list
R-TBA12_01-GB 2104 Index 012
Part.-No. 00163371-GB
117/224
1
2
P
a
ra
m
e
te
r
lis
t
Содержание ZA dyn 4C
Страница 212: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 212 224 ...
Страница 213: ...19 Enclosure Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 213 224 ...
Страница 214: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 214 224 ...
Страница 215: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 215 224 19 Enclosure ...
Страница 216: ...Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 216 224 ...
Страница 217: ...19 Enclosure Original operating instructions ZAdyn4C Enclosure R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 217 224 ...
Страница 220: ...Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 220 224 ...
Страница 221: ...19 Enclosure Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 221 224 ...
Страница 222: ...Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 222 224 ...
Страница 223: ...19 Enclosure Original operating instructions ZAdyn4C R TBA12_01 GB 2104 Index 012 Part No 00163371 GB 223 224 ...