10.2.6 Intern / Extern Function 6D
¨
Switch over between Set Intern and Set Extern
(for mode speed controller
1.01
)
“Set external 1“ under settings must be programmed to OFF
contact at digital input e. g. Digital IN 1 = D1-D1
Set Intern 1 at opened contakt
↔
Set Extern at closed contact D1 Inverting OFF
Set Intern 1 at closed contakt
↔
Set Extern at opened contact D1 Inverting ON
¨
Switch over between aktiv setting at the unit and external Signal
(for mode controller higher
2.01
)
Contact at digital input e. g. Digital IN 1 = D1-D1
External Setpoint at 1E for E2 Function
External manual operation at 2E for E2 Function
Setting at the unit at opened contact
↔
Signal Extern at closed contact D1 Inverting OFF
Setting at the unit at closed contact
↔
Signal Extern at opened contact D1 Inverting ON
Signal 40%
Controller
3~ 400 V
3~ 78 % = Intern 1
D1 D1
0 1
0
1
3~ 40 % = Extern
E1
External
Setpoint
Signal 40 %
Controller
3~ 400 V
3~ 0-100 %
D1 D1
0 1
1
0
3~ 80 %
Sensor
E1
E2