Handbook
Ucontrol
type-lines PXDM
Date 06/04
TBL02_55-GB06/04
Part.-No. 00153239-GB
Page 43 / 105
8.4 Pressure control for condensers refirgeration
3.01
..
3.04
8.4.1 Basic setting
3.01
..
3.04
Basic device settings are carried out in two steps:
1
Place the internal plug (jumper) for the external default signal in the correct position. Caution – not under voltage!
Observe the safety notices!
2
Switch the voltage on and select mode of operation (general controller function) factory setting
1.01
= speed controller.
If necessary configuration of sensors.
1
Type of signal
Input Analog IN 1
INFO
0-10 V
No PINs with
jumper bridged
For pressure sensor with 0-10 V signal
proportional so measuring range
Factroy setting !
0-20 mA / 4-20 mA
Lower PINs
with jumper
bridged
Pressure sensor with 4-20 mA signal
For Ziehl-Abegg pressure sensors type
DSF2-25 put in down position
Connection for pressure sensor type DSF..at „Analog IN 1“
Input 2 is automatically activated upon selection of operating modes with 2-sensors
3.03
and
3.04
. The jumpers E 2.1 (J2)
and E 2.2 (J3) must be inserted in accordance with the sensor signal.
For sensors typ DSF.. at „Analog IN 2“
J4 J5
E1.1 E1.2
J4 J5
E1.1 E1.2
Sensor DSF2-25
(4-20 mA)
E1
24V
GND
1 2
DSF2-25
Sensor DSF2-25
(4-20 mA)
E2
24V
GND
1 2
DSF2-25
J2 J3
E2.1 E2.2