8.6.4 Additional menu item for mode 5.02 with outside-temperature dependent Setpoint
An outside temperature compensation can be activated (sensor connection E2 to analog IN 2) when being operated as a
air volume regulation device. An optimal building climate, e.g., can be achieved through this. Through this function, the
set and active Setpoint1/2 is automatically changed proportional to the measured outside temperature (
F
Info: “Setpoint
control“).
Temperature band Setpoint decrease
The temperature range in which the active Setpoint1/2 is continuously changed according
to the outside temperature
Setting range is adjustable from “OFF“ (OFF= no outiside temperature influence) to 40 K
Start Temperatur
Starting from the outside temperature, the target default value is reduced in the set
temperature range up to the “P-min” setting
Minimum Volume Setpoint
Setpoint that is not to be undercut even during very low outside temperatures. The
adjustment range is dependent on the sensor measurement range and programmed „K
Factor.
↓
↑
↓
↑