7
Base setup
7.1
Jumper for the input signal
Jumper position factory setting for 0 - 10 V signal. For temperature sensors (TF..) or sensors with 4 - 20 mA bring the internal
jumper for the external signal in the correct position. Caution- not under voltage! Observe the savety notices! When using
“
other
sensors
”
bring the jumper in the correct position. The adjustment of the measuring range takes place in the Base setup of
respective Mode.
E1 Analog In (factory setting 0 - 10 V)
E2 Analog In for modes with two
sensors
22.01.2008
v_stecker_e2.vsd
TF..
3
1
BN
GN
MBG..-I
24V
E2
MBG..
(4 - 20 mA)
E2
GND
TF..
E2.2
E2.1
4 - 20 mA
(0 - 20 mA)
E2.2
E2.1
TF.. (KTY)
7.1.1
External Setpoint / External speed setting in manual operation
External Setpoint or external manual operation is possible by 0 - 10 V (0 - 20 mA, 4 - 20 mA) Signal at terminals
“
E2
”
and
“
GND
”
. Place internal Jumper
“
E2.1
”
and
“
E2.2
”
for
“
E2 Analog In
”
in correct position.
“
E2
”
Con
fi
guration in base setup. For
Potentiometer Analog Out1 (terminal
“
A
”
) program to function
|
1A
|
=
“
+10 V
”
(like factory setting see IO Setup). If a second
sensor is connected at input 2, external Setpoint or speed setting in manual operation is possible with additional modul
“
Z-
Modul-B
”
(input E3 see IO Setup).
E2 Analog In = factory setting 0 - 10 V
A
E2
GND
0-10 V
Analog In 2
02.12.2009
v_extern_stecker_v.vsd
E2.2
E2.1
10
k
E2 Analog In = 0 - 20 mA / 4 -
20 mA
E2.2
E2.1
Analog In 2
24.01.2008
v_extern_stecker_a.vsd
External Setpoint
via external signal instead of
“
Setpoint 1
”
. The
“
external Setpoint
”
function must be activated in base setup
|
1E
|
for
“
E2 function
”
. The active external Setpoint value is displayed in the
“
info
”
menu group.
External speed setting
in manual operation. The
“
external manual operation
”
function must be activated in the basic settings
|
2E
|
for
“
E2 function
”
. Switchover between settings on the device and external manual operation via the digital input (see IO
Setup:
“
Control / manual operation
”
|
7D
|
).
Operating Instructions
Fcontrol
–
model series FXDM
Base setup
L-BAL-E072-GB 1642 Index 008
Part.-No.
26/105