10.11.2008
v_relais_k1_13_14.vsd
K1
14
13
K1
1
= energized, terminals 13 - 14 bridged
0
= de-energized 13-14 not bridged
Function Status Controller
K1
1 = energized
0 = de-energized
Inverting
OFF
ON
1K
Operation without fault, line supply okay
1
0
2K
Fault with indication by relay
0
1
4K
Exceed Frequency / Speed > setting
“
Set Internal3
”
1
0
8.5.3
Input
“
E1
”
E1 Function
E1 Function
|
1E
|
(factory setting) = speed setting by external signal (0 - 10 V / PWM).
For settings via
|
1E
|
“
E1
”
operates like
“
D1
”
as a digital input (
digital inputs /
function).
E1 Inverting
E1 Inverting
Factory setting inverting to
“
OFF
”
.
For control with inverted setting signal switch to
“
ON
”
(setting signal: 10 - 0 V).
E1 Min.
E1 Min.
Value of the input signal at which the controller starts at minimum modulation.
Setting range: 0 - 100 %
Factory setting: 5 %
E1 max
E1 max
Value of the input signal at which the maximum modulation of the controller is reached.
Setting range: 0 - 100 %
Factory setting: 100 %
Example for signal adaption
Idealized principle diagrams for setting:
“
Min. Speed
”
= 0.0 Hz and
“
Max. Speed
”
= 50.0 Hz
F
out
[Hz]
Si E
0
1
2
3
4
5
6
7
8
9
10
0 – 10 V
15.02.2012
v_e1_adjust_i_basic.vsd
1
E1 min. = 0 %, E1 max. = 100 %
50
2
E1 min. = 25 %, E1 max. = 100 %
40
30
20
10
3
E1 min. = 20 %, E1 max. = 80 %
E1 min. = 0 %, E1 max. = 80 %
4
Fout
Output frequency
Si E
Speed setting signal
Example:
“
E1 min.
”
= 20 %
The controller begins only at approx. 20%
higher signal with minimal modulation.
Example:
“
E1 max.
”
= 80 %
The modulation rises linear to 100% modu-
lation with 80% setting signal.
Operating Instructions
Fcontrol Basic
–
model series FSDM2.5..50AM
Programming
L-BAL-E174-GB 1704 Index 005
Part.-No.
29/49