PINs
PIN
Function
PIN 0010
Opening service menu, if PIN-protection activated
PIN 1234
Opening
“
setting
”
.
if
“
set protection
”
=
“
ON
”
(
Controller Setup)
PIN 9090
Restore user setting
PIN 9091
Save user setting (corresponds function
“
Save user setup
”
=
“
ON
”
Controller Setup)
PIN 9095
Restore factory setting = delivery status
Exception in ECblue Basic
The following parameters are not set back: Min. Speed, Max. Speed, all settings in Motor
Setup.
11
Diagnostics menu
Diagnostic
The diagnostics menu supplies information about the momentary operating condition
of the device.
00056:46:13
O
= Operation,
T
= Time,
C
= Controller
The time counting runs, as soon as mains voltage is connected (without fault).
If events step on (Motor fault, External Error, etc.), the period of operation is stored at
this time (
Events).
00056:46:13
O
= Operation,
T
= Time,
M
= Motor
The time counting runs as soon as a modulation of the controller is present
DC-Voltage
For 1 ~ types
ZK voltage constant at approx. 400 V
The PFC (Power Factor Controller) makes it mostly independent of the mains voltage.
DC-Voltage
For 3 ~ types
The intermediate circuit voltage without load is the peak value of the input voltage.
In a three-phase supply network with 400 V, an intermediate circuit voltage of ca. 565 V
results. This voltage sinks slightly under load.
Line voltage
Line voltage
Heatsink
Display of DC-Choke or Capacitor temperature. In case of temperature increase above
predetermined threshold value (from 90
°
C) the output power will be automatic re-
duced.
Capacitor
Display of DCLink Elco temperature. During impermissibly high levels (from 75
°
C on),
the output power is automatically reduced.
At 90
°
C switch off.
E2-KTY
Signal height at analog input E2 (Analog In 2)
E2-Current
Operating Instructions
AM-PREMIUM(-W)
–
model series
Diagnostics menu
L-BAL-E095-GB 1618 Index 006
Part.-No.
86/90