9
Programming
9.1
Speed controller
1.01
9.1.1
Base setup
1.01
Base setup
Base setup
Mode
Mode
Factory setting Mode:
1.01
E2 Analog In
E2 Analog In
Selection: 0 - 10 V, 0 - 20 mA, 4 - 20 mA, KTY, PT1000 (Inverting
IO Setup)
Factory setting: 0 - 10 V
E3 Function
E3 Function
(only for special applications)
•
Analog input 2
“
E3 function
”
factory set at
“
OFF
”
.
•
For operation with a second signal and switch over via
fl
oating contact set function
for
“
E3
”
to
|
1E
|
(
IO Setup: function
|
4D
|
).
•
For operation with a second signal and automatic control at the higher level. Set
“
E3
”
Function to
|
4E
|
.
•
Measurement value = function
|
7E
|
e.g. for limit indication, display in Info menu
“
E3
Actual
”
.
E3 Analog In
E3 Analog In
As long as no allocation has been carried out display:
|
- - - - -
|
Selection: 0 - 10 V, 0 - 20 mA, 4 - 20 mA, KTY, PT1000 (Inverting
IO Setup)
Factory setting: 0 - 10 V
9.1.2
Setting for operation
1.01
ECblue
Setting
Setting
Set Intern1
Set Intern1
Setting range manual speed setting: 0 rpm...
“
Max. Speed
”
Factory setting: 200 rpm
Set Intern2
Set Intern2
Setting
“
Set Intern 2
”
e.g. reduced value for night operation.
Switch over intern 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IO Setup).
Min. Speed
Min. Speed
Setting range: 0 rpm...
“
Max. Speed
”
Factory setting: 0 rpm
Max. Speed
Max. Speed
Setting range: Rated speed ...0 rpm (takes priority over setting
“
Min. Speed
”
)
Factory setting: Rated speed
Set external1
Set external1
“
ON
”
(factory setting) = speed setting by external Signal
“
OFF
”
= Setting
“
Set Intern1
”
Operating Instructions
AM-PREMIUM(-W)
–
model series
Programming
L-BAL-E095-GB 1618 Index 006
Part.-No.
18/90