Additional menu item for mode
5.02
with outside-temperature dependent target-setpoint
Outside-temperature dependent target-setpoint
Außentemperatur
P-min SA
[m
3
/h]
-15 °C
min. Temperatur
30 °C
T-Start
Sollwert 1
[m
3
/h]
Sollwert 2
[m
3
/h]
07.02.2007
v_sollwert_aussentemp_abhaengig_m3h.vsd
S1
Setpoint1
S2
Setpoint2
P-Min SA
Minimum air volume
T-min
Minimum temperature
T-Start
Setpoint reducing will start below this outside temperature
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
to
“
Analog In
2
”
) when being operated as a air volume regu-
lation device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active Setpoint 1/2 is automatically
changed proportional to the measured outside
temperature (
Info:
“
Setpoint control
”
).
T-Band SA
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
T-Start SA
T-Start SA
Setpoint reducing will start below this outside temperature
P-Min SA
P-Min SA
Minimum pressure for very low outside temperature
Operating Instructions
AM-PREMIUM(-W)
–
model series
Programming
L-BAL-E095-GB 1618 Index 006
Part.-No.