Example for temperature regulation; for other modes of operation settings in corresponding sensor
unit.
Offset 1 for alarm during exceeding
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
ON
ON
ON = 15°C + 5 K = 20 °C
OFF = 20°C - 2 K = 18 °C
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
k
u
e
h
le
n
_
1
0
k
_
p
o
s
_
o
ff
s
e
t.
v
s
d
Example: Setpoint 15.0
°
C, 5.0 K, Hysteresis 2.0 K
Offset 2 for alarm during undercutting
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
[min]
[
°C
]
ON
OFF = 15°C + 2 K = 17 °C
ON = 20°C - 5K = 15 °C
ON
1
6
.0
3
.2
0
0
7
v
_
re
la
is
_
h
e
iz
e
n
_
9
k
_
n
e
g
_
o
ff
s
e
t.
v
s
d
Example: Setpoint 15.0
°
C, Offset -5.0 K, Hysteresis 2.0 K
9.12
Motor Setup for AM-PREMIUM in ECblue
Motor Setup
Menu group Motor Setup
9.12.1
Setting for Rampup time and Rampdown time
By separate menus for Rampup time and Rampdown time an adjustment is possible to individual
system conditions.
This function is switched behind the actual controller function.
Rampup time
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
Rampdown time
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Factory setting: 10 / 20 / 30 / 40 sec. (depending on device type)
0 .. 100 %
3
4
1
2
09.05.2007
v_hochlaufzeit_ruecklaufzeit.vsd
1
external Signal
2
Setting
3
Rampup time
4
Rampdown time
Operating Instructions
AM-PREMIUM(-W)
–
model series
Programming
L-BAL-E095-GB 1618 Index 006
Part.-No.
60/90