9.5.1.3
Heating H1 via the 0...10 V signal (linear)
In Installation menu:
“
H1 mode
”
=
|
2
|
for proportional controller.
The
“
K2
”
heating relay is connectedin parallel in order to activate, for example, a gas valve.
If a proportional regulator (linear 0 - 10 V) is programmedfor heating circuit 10 an assignedheating
relay switches on parallel to it, e.g. to activate a gas valve, factory setting = K2 (
“
Installation
” – “
IO
Setup
”
.
The heating, activated through the 0 - 10 V signal, is indicated in the display with the
re symbol as
soon as the activation exceeds
“
0 %
”
.
H1 Offset
H1 Offset
Example for 0...10 V control based on the ventilation setpoint
(In installation menu:
“
H1 input
”
=
|
0
|
for input
“
E1
”
(i.e. like actual value for ventilation).
•
Current heating value = Current ventilation value (i.e., temperature from sensor
on input
“
E1
”
)
•
Heating relatedto the ventilation setpoint (i.e. offset adjustment in Kelvin)
Setting range: -10.0...+40.0
°
C
Factory setting: -2.0
°
C
or
H1 Setpoint
H1 Setpoint
Example for 0...10 V control independent of the ventilation nominal value
(In Installation menu:
“
H1 input
”
=
|
1
|
for sensor at input
“
E2
”
,
|
2
|
for
“
BUS
”
from
“
Master
”
or
|
3
|
for sensor at input
“
E3
”
).
•
Heating is adjustable as a separate setpoint (i.e. in
°
C)
•
Setting range: -10.0...+40.0
°
C
•
Factory setting: -2.0
°
C
H1 Pband
H1 Pband
Setting range: -10.0...+10.0 K
Factory setting: 2.0 K
H1 Minimum
H1 Minimum
Setting range: 0...100 %
Factory setting: 0 %
H1 maximum
H1 maximum
Setting range: 0...100 %
Factory setting: 100 %
Heating or cooling function dependent on the setting in the installation menu
“
Heating1
”
-
“
H1actual < set = n+
”
Heating function
H
max.
12.08.2008
v_heiz_0_10_heiz.vsd
S / V
A [°C]
M [%]
H
min.
R
M Heating circuit level control (without output curve)
H max. H1 maximum
H min. H1 Minimum
R H1 Pband
S/ V H1 Offset or Setpoint
A Compartment temperature
Cooling function
H
max.
12.08.2008
v_heiz_0_10_kuehl.vsd
S / V
A [°C]
M [%]
H
min.
R
M Heating circuit level control (without output curve)
H max. H1 maximum
H min. H1 Minimum
R H1 Pband
S/ V H1 Offset or Setpoint
A Compartment temperature
Operating Instructions
UNIcon / Acontrol
Settings for operation
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
59/83