Variant 2: one controlledandthree not controlledgroups
25.09.2008
v_dia_group_varia2.vsd
100%
GAM
G1
G2
G3
G4
n G1 100%: 100%
n G1 100%: 80%
OFF G2:
45 %
ON G2:
50 %
OFF G3:
55 %
ON G3:
60 %
ON G4:
80 %
OFF G4:
75 %
G2 Min: 0%
G3 Min: 30%
G4 Min: 60%
nM
[%]
G1, G2, G3, G4 Group1, 2, 3, 4
G2 Min, G3 Min, G4 Min Minimum2, 3, 4
OFF G2, G3, G4 Off group2, 3, 4
ON G2, G3, G4 On group2, 3, 4
n G1 Speed Group1
GAM Total exhaust air volume
Increasing or constant values must always be enteredin the order of settings starting with group 1.
For the setting Speed
“
Group1 100%
”
100 % is normally set. For heat exchanger operation it may be useful for the speedof
group 1 to reach 100 % earlier (setting e.g. 80 %) to take the air resistance of the heat exchanger into account.
7.11
|
Installation
|
Bus
◄
Bus
↑
|
ESC
|
P
↓
Address
Address
Address (factory setting Slave mit Address 32).
On the
“
master
”
the address is automatically set to 1 (display - - - -).
The address from 2..32 can be set for slaves.
Setting range: 2...32
Factory setting: 32
Bus mode
Bus mode
0: Modbus Slave (factory setting)
1: Modbus Master
2: Modbus passive master for combination with Alarmcon
3: ZABus Slave
4: ZABus Master
The following settings are possible only at the Master(Master mode 1, 2 or 4), for operation as Slave
display: - - - - -
Number slaves
Number slaves
Number of slaves connectedto the
“
master
”
Setting range: 1...31
Factory setting: 1
Group1 (7)
Group1(7)
Setting range Address: OFF-1...31 (Factory setting: OFF)
Setting range Function: K1 - K2 - K3 - PWM - A1 - A2 - A3
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
34/83