On group2
On group2
Switch-on value for Group2
Setting range: 0 - 100 %
Factory setting: 50 %
Minimum2
Minimum2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 30 %
Off group3
Off group3
Switch-off value for Group3
Setting range: 0 - 100 %
Factory setting: 100 %
On group3
On group3
Switch-on value for Group3
Setting range: 0 - 100 %
Factory setting: 100 %
Minimum3
Minimum3
Minimum Value for Group3
Setting range: 0 - 100 %
Factory setting: 40 %
Off group4
Off group4
Switch-off value for Group4
Setting range: 0 - 100 %
Factory setting: 100 %
On group4
On group4
Switch-on value for Group4
Setting range: 0 - 100 %
Factory setting: 100 %
Minimum4
Minimum4
Minimum Value for Group4
Setting range: 0 - 100 %
Factory setting: 50 %
Off group5
Off group5
Switch-off value for Group5
Setting range: 0 - 100 %
Factory setting: 100 %
On group5
On group5
Switch-on value for Group5
Setting range: 0 - 100 %
Factory setting: 100 %
Minimum5
Minimum5
Minimum Value for Group5
Setting range: 0 - 100 %
Factory setting: 60 %
Summer mode for group control
Summer mode
Summer mode
This function determines a minimum value for the group control. If the supply air
temperature rises above
“
Summer nom.
”
a minimum value between 0 and100 % is
determined automatically up to
“
Summer cr.
”
(Summer control range).
This function then forces the system to impose increasedventilation at high outside
temperatures even if the stall temperatures are comparatively low andensures max.
possible air circulation.
Summer setpoint
Summer setpoint
Adjustment range: 0.0 - 50.0
°
C
Factory setting: 31.0
°
C
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
31/83