7.3
|
Installation
|
Shutter
◄
Shutter
↑
|
ESC
|
P
↓
Shutter input
Shutter input
0
= Sensor on E1 = Control via offset to setpoint ventilation
(factory setting)
1
= Sensor on E2 = Control independent from the ventilation nominal value
2
= Sensor value via bus from master independently of ventilation setpoint
3
= sensor at E3 = regulation independent of ventilation setpoint (only possible of not
usedas a digital input, internal jumper
“
J2
”
must be pluggedto the right =
“
E3
”
.
Sh. Val<Set=+
Sh. Val<Set=+
Basic control function:
OFF
= shutter open if the current value is higher than the set point = Cooling function
(factory setting)
ON
= shutter open if the current value is less than the set point = Heating function
Ventilation link
Ventilation link = OFF
With the factory setting of
“
OFF
”
, the shutter operates completely independent of the
fan control. I.e., at the values set for the shutter control (offset or setpoint, min, max,
control range).
Ventilation link = 1...100 %
Fan coupling value = ventilation level control (in %) during which the shutter is opened
100 % independent of the settings.
If the ventilation level control is less than the vantilation link, the shutter position is
calculatedas in the following:
Shutter position [%] = Ventilation level control [%] / ventilation link
×
100
Example:
Ventilation link setting = 50 %
Ventilation level control = 40 %
shutter position = 40 % / 50 % x 100 = 80 %
Using this function, suf
cient shutter opening can be ensuredeven during low temper-
atures anda minimal fan preset speed.
7.4
|
Installation
|
Heating 1
◄
Heating1
↑
|
ESC
|
P
↓
H1 Mode
H1 Mode
OFF
= Heating not active
1
= Heating works as a two-point controller via relay
(factory setting)
2
= Heating works as a proportional controller (0 - 10 V)
Heating input
H1 Input
0
= Sensor on E1 = Control via offset to setpoint ventilation
(factory setting)
1
= Sensor on E2 = Control independent from the ventilation nominal value
2
= Sensor value via bus from
“
master
”
independently of ventilation setpoint
3
= sensor at E3 = regulation independent of ventilation setpoint (only possible of not
usedas a digital input, internal jumper
“
J2
”
must be pluggedto the right =
“
E3
”
.
H1 Val<Set=+
H1 Val<Set=+
Basic control function:
OFF
= cooling
ON
= heating
(factory setting)
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB