H2 TI
H2 TI
Setting range: 0 - 200 %
Factory setting: 5 %
The start-up temperature is determinedby the regulator basedon the following relation:
Start-up temp. = (setpoint piglet nest
–
room temp.) x eval room temperature
Example with valve in the lead, other arrangements possible
PTE / CTE
RL
VL
FH
MV
0 - 10V
0 -10V
18.09.2008
v_ferkln_warmwa_hzng.VSD
TFR
TFA
A3
E2
E1
RL Return
VL Flow
MV One or three-way valve (0 - 10 V)
TFA Application sensor for water temperature (measured after valve)
FH
´
Piglet nest heating
TFR Room temperature sensor in stall
Example settings
•
Setpoint for piglet nest: 30
°
C
•
room temperature: 24
°
C
•
Evaluation: 2,90
•
VT = (30
°
C
–
24
°
C) x 2.90 + 24
°
C = 41.4
°
C
7.6
|
Installation
|
Setpoint derating
◄
Setp. derating
↑
|
ESC
|
P
↓
Increase
Increase
If the compartment temperature rises above the
“
setpoint
”
+ the
“
control range
”
, the
setpoint is increasedvia an automatic timer per hour by the adjustable value (e.g. 0.2
K/h). The increase is only carriedout up to a max. value (adjustable) via
“
Max. Rising
”
.
Setting range: 0.1...10.0 K/h
Factory setting: 0.2 K/h
Derating
Derating
If the compartment temperature sinks below the settings
“
setpoint
”
+ the
“
control
range
”
, the set point is reset via an automatic timer per hour by the adjustable value
down to the
“
normal set point
”
(
“
setpoint
”
in the
“
Ventilation
”
menu) (e.g. 0.1 K/h).
Setting range: 0.1...10.0 K/h
Factory setting: 0.1 K/h
Operating Instructions
UNIcon / Acontrol
The Installation menu
L-BAL-E051-GB 1035 Index 003
Part.-No. 00163311-GB
26/83