6.2 Dipswitch functions
Position factory setting for all dipswitches =
|
OFF
|
DIP
Function
OFF
ON
1
no selection
RPM controller
prohibited
2
Signal source of control
Setting of output voltage by exter-
nal signal to
“
E1
”
prohibited
3
Type of Signal
0 - 10 V
2 - 10 V
4
Inverting signal input
0 - 10 V, 2 - 10 V
10 - 0 V, 10 - 2 V
5
Minimum speed cut off
OFF
ON
6
Hardstart function
OFF
ON
7
no function
-
-
8
Function signal output
“
Analog Out 1
”
Constant voltage
“
+ 10 V
”
for exter-
nal potentiometer
0 - 10 V
modulation 0 - 100 %
9
no function
-
-
10
no function
-
-
6.3 Diagram: setting signal and speed
Setting via external signal or external potentiometer
Output voltage from approx. 0 - 100 % of connected line voltage or in range of settings
“
n-min
”
up to
“
n-max
”
.
nM
50 %
100 %
0
1
2
3
4
5
6
7
8
9
10
10
9
8
7
6
5
4
3
2
1
0
0 – 10 V
10 – 0 V
Min.
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
10.06.2011
v_nmotor_0_10v_n-min_n-max.vsd
Si
Idealized principle diagram
nM
Motor speed
Si
Signal
Operating Instructions
Acontrol
PSET6 / PSET10
Base setup
L-BAL-E141-GB 1925 Index 004
Part.-No.